19. Low Ambient Cooling Enhancement
REYQ72 - 384TAYCA
REYQ-T series include a feature for Low Ambient Cooling.
The function enhances REYQ-T series as follows:
• Allows operation to –4ºFDB (–20ºCDB) ambient temperature in cooling mode. (Normal limit is 23ºFDB (–5ºCDB).)
• Operation below 23ºFDB (–5ºCDB) requires the addition of wind covers onto the outdoor unit.*
Application Rules:
• Total connection index of each system is limited to 50-130% when height difference is 0-194 ft. (0-50 m), 80-130% when 194-295 ft.
(50-90 m).
• All units on the system must be connected to a Branch Selector Box, Low ambient cooling is only available on indoor unit
connected to a single branch selector box. Single and Multi-port Branch Selector Boxes may be combined on one system but all
indoor units connected to a multi branch selector box will operate as standard without the low ambient cooling function.
• Function is engaged by a field setting on the outdoor unit (to enable Low Ambient Cooling) and a dip switch setting is necessary on
the Single Branch Selector Boxes BSQ-T series serving the indoor units NOT subject to Low Ambient Cooling requirements.
• During operation below 23ºFDB (–5ºCDB), the available cooling capacity decreases as follows:
14ºFDB (–10ºCDB) - Reduces to 80% of nominal.
5ºFDB (–15ºCDB) - Reduces to 65% of nominal.
–4ºFDB (–20ºCDB) - Reduces to 60% of nominal. (Only applicable to Single-port Branch Selector Boxes)
• The operating sound level of the Single Branch Selector Boxes BSQ-T series could increase 3 dB(A) higher than maximum while
the system is operating in the Low Ambient Cooling mode. It is recommended to locate units away from zones sensitive to sound
levels.
• Allowable height difference between outdoor and indoor units (when outdoor unit is below) is limited to 130 ft. (40 m). (Normal limit
is 195 ft. (60 m).)
* Contact your local Daikin representative for wind cover specification requirements and part numbers.
Summary of Contents for VRV IV REYQ-TAYCA
Page 1: ...EDUS371706C D 202002 Engineering Data Heat Recovery 60 Hz Design Manual REYQ TAYCA 575 V ...
Page 2: ......
Page 27: ...25 REYQ TAYCA EDUS371706C D 10 Dimensions REYQ72 168TAYCA C 3D107340A ...
Page 32: ...30 REYQ TAYCA EDUS371706C D 12 Center of Gravity REYQ72 120TAYCA 4D107384 ...
Page 33: ...31 REYQ TAYCA EDUS371706C D REYQ144 168TAYCA 4D107385 ...
Page 35: ...33 REYQ TAYCA EDUS371706C D 14 Piping Diagrams REYQ72 120TAYCA 3D107166 ...
Page 36: ...34 REYQ TAYCA EDUS371706C D REYQ144 168TAYCA 3D107167 ...
Page 43: ...41 REYQ TAYCA EDUS371706C D 18 Operation Limits REYQ72 384TAYCA 3D107375 ...
Page 45: ...43 REYQ TAYCA EDUS371706C D 20 Sound Levels Reference Data REYQ72TAYCA 4D107379B ...
Page 46: ...44 REYQ TAYCA EDUS371706C D REYQ96TAYCA 4D107380A ...
Page 47: ...45 REYQ TAYCA EDUS371706C D REYQ120TAYCA 4D107381A ...
Page 48: ...46 REYQ TAYCA EDUS371706C D REYQ144TAYCA 4D107382A ...
Page 49: ...47 REYQ TAYCA EDUS371706C D REYQ168TAYCA 4D107383A ...
Page 58: ...56 REYQ TAYCA EDUS371706C D 3P558142 1B ...
Page 59: ...57 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Page 60: ...58 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Page 61: ...59 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Page 62: ...60 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Page 63: ...61 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Page 64: ...62 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Page 65: ...63 REYQ TAYCA EDUS371706C D Collective Indications Label 3P385987 1A ...
Page 66: ...64 REYQ TAYCA EDUS371706C D 3P385987 1A ...
Page 77: ......
Page 78: ......
Page 79: ......