40
REYQ-TAYCA
EDUS371706C-D
17. Electrical Characteristics
REYQ72 - 384TAYCA
Model name
Units
Power supply
Comp.
OFM
SCCR
Hz Volts Min. Max.
MCA
MOP
RLA
kW
FLA
REYQ72TAYCA
60 575 518 632
15.1
20
7.5
0.7 × 2
1.0 × 2
SCCR kA rms,
Symmetrical
@600 V MAX: 5
REYQ96TAYCA
60 575 518 632
16.8
20
8.4
0.7 × 2
1.0 × 2
REYQ120TAYCA
60 575 518 632
18.2
25
10.2
0.7 × 2
1.0 × 2
REYQ144TAYCA
60 575 518 632
22.3
30
15.4
0.7 × 2
1.0 × 2
REYQ168TAYCA
60 575 518 632
24.9
30
17.7
0.7 × 2
1.0 × 2
REYQ192TAYCA
REYQ96TAYCA
60 575 518 632 16.8 + 16.8 20 + 20
8.9 + 8.9
(0.7 × 2) × 2 (1.0 × 2) × 2
REYQ96TAYCA
REYQ216TAYCA
REYQ96TAYCA
60 575 518 632 16.8 + 18.2 20 + 25 10.3 + 10.3 (0.7 × 2) × 2 (1.0 × 2) × 2
REYQ120TAYCA
REYQ240TAYCA
REYQ120TAYCA
60 575 518 632 18.2 + 18.2 25 + 25 10.8 + 10.8 (0.7 × 2) × 2 (1.0 × 2) × 2
REYQ120TAYCA
REYQ264TAYCA
REYQ120TAYCA
60 575 518 632 18.2 + 22.3 25 + 30 11.9 + 15.2 (0.7 × 2) × 2 (1.0 × 2) × 2
REYQ144TAYCA
REYQ288TAYCA
REYQ144TAYCA
60 575 518 632 22.3 + 22.3 30 + 30 15.7 + 15.7 (0.7 × 2) × 2 (1.0 × 2) × 2
REYQ144TAYCA
REYQ312TAYCA
REYQ144TAYCA
60 575 518 632 22.3 + 24.9 30 + 30 16.8 + 16.8 (0.7 × 2) × 2 (1.0 × 2) × 2
REYQ168TAYCA
REYQ336TAYCA
REYQ168TAYCA
60 575 518 632 24.9 + 24.9 30 + 30 18.1 + 18.1 (0.7 × 2) × 2 (1.0 × 2) × 2
REYQ168TAYCA
REYQ360TAYCA
REYQ120TAYCA
60 575 518 632 18.2 + 18.2
+ 18.2
25 + 25
+ 25
11.8 + 11.8
+ 11.8
(0.7 × 2) × 3 (1.0 × 2) × 3
REYQ120TAYCA
REYQ120TAYCA
REYQ384TAYCA
REYQ120TAYCA
60 575 518 632 18.2 + 18.2
+ 22.3
25 + 25
+ 30
12.2 + 12.2
+ 15.8
(0.7 × 2) × 3 (1.0 × 2) × 3
REYQ120TAYCA
REYQ144TAYCA
Symbols:
MCA: Min. Circuit Amps. (A)
MOP: Max. Overcurrent Protector (A)
RLA: Rated Load Amps. (A)
OFM: Outdoor Fan Motor
kW:
Rated Motor Output (kW)
FLA: Full Load Amps. (A)
SCCR: Short-Circuit Current Rating
Note:
1. RLA is based on the following conditions.
Indoor temp. 80°FDB (26.7°CDB) / 67°FWB (19.4°CWB)
Outdoor temp. 95°FDB (35.0°CDB)
2. Voltage range
Units are designed to operate only at the rated voltage provided in the table above.
3. The maximum percent unbalance of phase voltage shall be 2%.
4. Select wire size based on the value of MCA.
5. MOP is used to select the circuit breaker.
C: 3D107369A, 3D107370C, 3D107371C
Summary of Contents for VRV IV REYQ-TAYCA
Page 1: ...EDUS371706C D 202002 Engineering Data Heat Recovery 60 Hz Design Manual REYQ TAYCA 575 V ...
Page 2: ......
Page 27: ...25 REYQ TAYCA EDUS371706C D 10 Dimensions REYQ72 168TAYCA C 3D107340A ...
Page 32: ...30 REYQ TAYCA EDUS371706C D 12 Center of Gravity REYQ72 120TAYCA 4D107384 ...
Page 33: ...31 REYQ TAYCA EDUS371706C D REYQ144 168TAYCA 4D107385 ...
Page 35: ...33 REYQ TAYCA EDUS371706C D 14 Piping Diagrams REYQ72 120TAYCA 3D107166 ...
Page 36: ...34 REYQ TAYCA EDUS371706C D REYQ144 168TAYCA 3D107167 ...
Page 43: ...41 REYQ TAYCA EDUS371706C D 18 Operation Limits REYQ72 384TAYCA 3D107375 ...
Page 45: ...43 REYQ TAYCA EDUS371706C D 20 Sound Levels Reference Data REYQ72TAYCA 4D107379B ...
Page 46: ...44 REYQ TAYCA EDUS371706C D REYQ96TAYCA 4D107380A ...
Page 47: ...45 REYQ TAYCA EDUS371706C D REYQ120TAYCA 4D107381A ...
Page 48: ...46 REYQ TAYCA EDUS371706C D REYQ144TAYCA 4D107382A ...
Page 49: ...47 REYQ TAYCA EDUS371706C D REYQ168TAYCA 4D107383A ...
Page 58: ...56 REYQ TAYCA EDUS371706C D 3P558142 1B ...
Page 59: ...57 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Page 60: ...58 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Page 61: ...59 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Page 62: ...60 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Page 63: ...61 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Page 64: ...62 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Page 65: ...63 REYQ TAYCA EDUS371706C D Collective Indications Label 3P385987 1A ...
Page 66: ...64 REYQ TAYCA EDUS371706C D 3P385987 1A ...
Page 77: ......
Page 78: ......
Page 79: ......