19
REYQ-TAYCA EDUS371706C-D
8.3 Limitation of Capacity Index for Heat Recovery
Single Branch Selector unit
Model
BSQ36TVJ
BSQ60TVJ
BSQ96TVJ
Maximum number of connectable indoor units
4
8
8
Total capacity index of connectable indoor units
unit ≤ 36
36 < unit ≤ 60
60 < unit ≤ 96
Multi Branch Selector unit
Model
BS4Q54TVJ
BS6Q54TVJ
BS8Q54TVJ
BS10Q54TVJ
BS14Q54TVJ
Maximum number of connectable indoor units
20
30
40
41
41
Maximum number of connectable indoor units per
branch
5
5
5
5
5
Number of branches
4
6
8
10
12
Maximum capacity index of connectable indoor
units
144 or less
216 or less
290 or less
290 or less
290 or less
Maximum capacity index of connectable indoor
units per branch (*1)
54 or less
54 or less
54 or less
54 or less
54 or less
Note:
*1. When the total capacity of indoor units to be connected downstream is larger than 54 (Max. 96), use a junction pipe kit (KHRP26A250T, optional
parts) to join two connections downstream from the Branch Selector unit.
High and low pressure
gas piping
Suction gas piping
Liquid piping
Indoor unit
(Heating)
Indoor unit
(Cooling)
Indoor unit*
(Cooling only)
Heat Recovery operation!
For indoor units used for cooling only (do not connect to Branch Selector unit when using for Heat Recovery),
total capacity index must be 50% or less than the capacity index of the outdoor units.
Branch
Selector
unit
Branch
Selector
unit
Heat Recovery
Outdoor unit
Summary of Contents for VRV IV REYQ-TAYCA
Page 1: ...EDUS371706C D 202002 Engineering Data Heat Recovery 60 Hz Design Manual REYQ TAYCA 575 V ...
Page 2: ......
Page 27: ...25 REYQ TAYCA EDUS371706C D 10 Dimensions REYQ72 168TAYCA C 3D107340A ...
Page 32: ...30 REYQ TAYCA EDUS371706C D 12 Center of Gravity REYQ72 120TAYCA 4D107384 ...
Page 33: ...31 REYQ TAYCA EDUS371706C D REYQ144 168TAYCA 4D107385 ...
Page 35: ...33 REYQ TAYCA EDUS371706C D 14 Piping Diagrams REYQ72 120TAYCA 3D107166 ...
Page 36: ...34 REYQ TAYCA EDUS371706C D REYQ144 168TAYCA 3D107167 ...
Page 43: ...41 REYQ TAYCA EDUS371706C D 18 Operation Limits REYQ72 384TAYCA 3D107375 ...
Page 45: ...43 REYQ TAYCA EDUS371706C D 20 Sound Levels Reference Data REYQ72TAYCA 4D107379B ...
Page 46: ...44 REYQ TAYCA EDUS371706C D REYQ96TAYCA 4D107380A ...
Page 47: ...45 REYQ TAYCA EDUS371706C D REYQ120TAYCA 4D107381A ...
Page 48: ...46 REYQ TAYCA EDUS371706C D REYQ144TAYCA 4D107382A ...
Page 49: ...47 REYQ TAYCA EDUS371706C D REYQ168TAYCA 4D107383A ...
Page 58: ...56 REYQ TAYCA EDUS371706C D 3P558142 1B ...
Page 59: ...57 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Page 60: ...58 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Page 61: ...59 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Page 62: ...60 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Page 63: ...61 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Page 64: ...62 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Page 65: ...63 REYQ TAYCA EDUS371706C D Collective Indications Label 3P385987 1A ...
Page 66: ...64 REYQ TAYCA EDUS371706C D 3P385987 1A ...
Page 77: ......
Page 78: ......
Page 79: ......