Example of connection (R-410A Type)
Si34-601A
364
Appendix
∗
Note 1
When the equivalent pipe length between outdoor and indoor units is 90m or more, the size of main pipes (both gas-side and liquid-side) must be increased.
Depending on the length of the piping, the capacity may drop, but even in such case it is able to increase the size of main pipes.
∗
Note 2
Allowable length after the first refrigerant branch kit to indoor units is 40 m or less, however it can be extended up to
90
m if all the following conditions are satisfied. (In case of
“ Branch with REFNET joint ”
)
∗
Note 3
If the pipe size above the REFNET header is
φ
34.9 or more, KHRP26M73HP is required.
Diameter of above case
Model
Gas
Liquid
RXYQ5 Type
φ
19.1
φ
12.7
RXYQ8 Type
φ
22.2
φ
25.4*
φ
12.7
RXYQ10 Type
Not
Increased
Not
Increased
φ
15.9
RXYQ12 Type
Not
Increased
φ
15.9
RXYQ14 Type
RXYQ16 Type
RXYQ20 Type
RXYQ22 Type
RXYQ24 Type
RXYQ26 Type
RXYQ28 Type
RXYQ34 Type
RXYQ36 Type
RXYQ38 Type
RXYQ40 Type
RXYQ48 Type
RXYQ50 Type
RXYQ52 Type
RXYQ54 Type
φ
31.8*
φ
15.9
RXYQ18 Type
φ
31.8*
φ
19.1
Model
Gas
Liquid
φ
31.8*
φ
19.1
φ
31.8*
φ
19.1
Not
Increased
φ
19.1
φ
38.1*
φ
22.2
φ
38.1*
φ
22.2
RXYQ30 Type
φ
38.1*
φ
22.2
RXYQ32 Type
φ
38.1*
φ
22.2
Model
Gas
Liquid
φ
38.1*
φ
22.2
Not
Increased
Not
Increased
Not
Increased
φ
22.2
φ
22.2
φ
22.2
RXYQ42 Type
RXYQ44 Type
Not
Increased
Not
Increased
φ
22.2
φ
22.2
RXYQ46 Type
Not
Increased
φ
22.2
Model
Gas
Liquid
Not
Increased
Not
Increased
Not
Increased
Not
Increased
φ
22.2
φ
22.2
φ
22.2
φ
22.2
*If available on the site, use this size.
Otherwise, it can not be increased.
*If available on the site, use this size. Otherwise it can not be increased.
Required Conditions
Example Drawings
1. It is necessary to increase the pipe size between the first branch kit
and the final branch kit. (Reducers must be procured on site)
2. For calculation of Total extension length, the actual length of
above pipes must be doubled. (except main pipe and the pipes
that are not increased)
3. Indoor unit to the nearest branch kit
≤
40 m
4. The difference between
[Outdoor unit to the farthest indoor unit] and [Outdoor unit
to the nearest indoor unit]
≤
40 m
8 b + c + d + e + f + g + p
≤
90 m
increase the pipe size of b, c, d, e, f, g
a + b × 2 + c × 2 + d × 2 + e × 2 + f × 2 + g × 2
+ h + i + j + k + l + m + n + p
≤
1000 m
h, i, j....... p
≤
40 m
The farthest indoor unit 8
The nearest indoor unit 1
( a + b + c + d + e + f + g + p ) - ( a + h )
≤
40 m
Increase the pipe size as follows
φ
9.5
→ φ
12.7
φ
12.7
→ φ
15.9
φ
15.9
→ φ
19.1
φ
19.1
→ φ
22.2
φ
22.2
→ φ
25.4*
φ
28.6
→ φ
31.8*
φ
34.9
→ φ
38.1*
a
A
B
C
D
E
F
G
b
c
d
e
f
g
h
i
j
k
l
m
n
1
2
3
4
5
6
7
8
H1
p
Outdoor unit
REFNET joint (A-G)
Indoor units ( 1 - 8 )
Outdoor unit
Main pipes
Increase
The first refrigerant branch kit
Indoor unit
Summary of Contents for VRV III RXYQ5-54PY1
Page 1: ...RXYQ5 54PY1 R 410A Heat Pump 50Hz Si34 601A...
Page 101: ...Refrigerant Flow for Each Operation Mode Si34 601A 90 Refirgerant Circuit...
Page 153: ...Outline of Control Indoor Unit Si34 601A 142 Function...
Page 219: ...Troubleshooting by Remote Controller Si34 601A 208 Troubleshooting...
Page 226: ...Si34 601A Troubleshooting by Remote Controller Troubleshooting 215...
Page 325: ...Troubleshooting OP Unified ON OFF Controller Si34 601A 314 Troubleshooting...
Page 327: ...Piping Diagrams Si34 601A 316 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ5PY1 3D050782...
Page 328: ...Si34 601A Piping Diagrams Appendix 317 RXYQ8P 3D050783...
Page 329: ...Piping Diagrams Si34 601A 318 Appendix RXYQ10P 12PY1 3D050784...
Page 330: ...Si34 601A Piping Diagrams Appendix 319 RXYQ14P 16P 18PY1 3D050785...
Page 336: ...Si34 601A Wiring Diagrams for Reference Appendix 325 RXYQ8PY1 3D050454J...
Page 337: ...Wiring Diagrams for Reference Si34 601A 326 Appendix RXYQ10PY1 3D050455H...
Page 338: ...Si34 601A Wiring Diagrams for Reference Appendix 327 RXYQ12PY1 3D051890G...
Page 339: ...Wiring Diagrams for Reference Si34 601A 328 Appendix RXYQ14P 16P 18PY1 3D050456H...
Page 344: ...Si34 601A Wiring Diagrams for Reference Appendix 333 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 346: ...Si34 601A Wiring Diagrams for Reference Appendix 335 FXZQ20M 25M 32M 40M 50M7V1B 3D038359...
Page 347: ...Wiring Diagrams for Reference Si34 601A 336 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Page 352: ...Si34 601A Wiring Diagrams for Reference Appendix 341 FXMQ200MA 250MAVE 3D039621B...
Page 353: ...Wiring Diagrams for Reference Si34 601A 342 Appendix FXHQ32MA 63MA 100MAVE 3D039801D...
Page 356: ...Si34 601A Wiring Diagrams for Reference Appendix 345 FXUQ71MA 100MA 125MAV1 3D044973A...
Page 357: ...Wiring Diagrams for Reference Si34 601A 346 Appendix FXMQ125MF 200MF 250MFV1 3D044996C...
Page 358: ...Si34 601A Wiring Diagrams for Reference Appendix 347 BEVQ71MA 100MA 125MAVE 3D044901B...
Page 381: ...Method of Checking The Inverter s Power Transistors and Diode Modules Si34 601A 370 Appendix...
Page 395: ...Si34 601A iv Index...