Outdoor Unit
LA
9
9
9
Malfunction of power unit
—
LC
9
9
9
Malfunction of transmission between inverter and
control PC board
P1
9
9
9
Inverter over-ripple protection
P4
9
9
9
Malfunction of inverter radiating fin temperature rise
sensor
PJ
9
9
9
Faulty field setting after replacing main PC board or
faulty combination of PC board
System
U0
8
7
9
Low pressure drop due to refrigerant shortage or
electronic expansion valve failure
U1
9
9
9
Reverse phase / open phase
U2
9
9
9
Power supply insufficient or instantaneous failure
U3
9
9
9
Check operation is not completed.
U4
9
9
9
Malfunction of transmission between indoor and
outdoor units
U5
9
9
9
Malfunction of transmission between remote
controller and indoor unit
U5
7
8
7
Failure of remote controller PC board or setting
during control by remote controller
U7
9
9
9
Malfunction of transmission between outdoor units
U8
9
9
7
Malfunction of transmission between main and sub
remote controllers (malfunction of sub remote controller)
U9
9
9
9
Malfunction of transmission between indoor unit and
outdoor unit in the same system
UA
9
9
9
Improper combination of indoor and outdoor units,
indoor units and remote controller
UC
8
8
8
Address duplication of central remote controller
UE
9
9
9
Malfunction of transmission between central remote
controller and indoor unit
UF
9
9
9
Refrigerant system not set, incompatible wiring /
piping
UH
9
9
9
Malfunction of system, refrigerant system address
undefined
Central
Remote
Controller
and
Schedule
Timer
M1
8
or
7
9
9
Central remote controller PC board defect
Schedule timer PC board defect
M8
8
or
7
9
9
Malfunction of transmission between optional
controllers for centralized control
MA
8
or
7
9
9
Improper combination of optional controllers for
centralized control
MC
8
or
7
9
9
Address duplication, improper setting
Heat
Reclaim
Ventilation
64
8
7
9
Indoor unit’s air thermistor error
—
65
8
7
9
Outside air thermistor error
—
6A
8
7
9
Damper system alarm
—
6A
9
9
9
Damper thermistor error
—
6F
8
7
9
Malfunction of simple remote controller
—
6H
8
7
9
Malfunction of door switch or connector
—
94
9
9
9
Internal transmission error
—
8
: ON
7
: OFF
9
: Blink
Malfunction
code
Operation
lamp
Inspection
display
Unit No.
Malfunction contents
Page
Referred
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.
Summary of Contents for VRV III RXYQ5-54PY1
Page 1: ...RXYQ5 54PY1 R 410A Heat Pump 50Hz Si34 601A...
Page 101: ...Refrigerant Flow for Each Operation Mode Si34 601A 90 Refirgerant Circuit...
Page 153: ...Outline of Control Indoor Unit Si34 601A 142 Function...
Page 219: ...Troubleshooting by Remote Controller Si34 601A 208 Troubleshooting...
Page 226: ...Si34 601A Troubleshooting by Remote Controller Troubleshooting 215...
Page 325: ...Troubleshooting OP Unified ON OFF Controller Si34 601A 314 Troubleshooting...
Page 327: ...Piping Diagrams Si34 601A 316 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ5PY1 3D050782...
Page 328: ...Si34 601A Piping Diagrams Appendix 317 RXYQ8P 3D050783...
Page 329: ...Piping Diagrams Si34 601A 318 Appendix RXYQ10P 12PY1 3D050784...
Page 330: ...Si34 601A Piping Diagrams Appendix 319 RXYQ14P 16P 18PY1 3D050785...
Page 336: ...Si34 601A Wiring Diagrams for Reference Appendix 325 RXYQ8PY1 3D050454J...
Page 337: ...Wiring Diagrams for Reference Si34 601A 326 Appendix RXYQ10PY1 3D050455H...
Page 338: ...Si34 601A Wiring Diagrams for Reference Appendix 327 RXYQ12PY1 3D051890G...
Page 339: ...Wiring Diagrams for Reference Si34 601A 328 Appendix RXYQ14P 16P 18PY1 3D050456H...
Page 344: ...Si34 601A Wiring Diagrams for Reference Appendix 333 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 346: ...Si34 601A Wiring Diagrams for Reference Appendix 335 FXZQ20M 25M 32M 40M 50M7V1B 3D038359...
Page 347: ...Wiring Diagrams for Reference Si34 601A 336 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Page 352: ...Si34 601A Wiring Diagrams for Reference Appendix 341 FXMQ200MA 250MAVE 3D039621B...
Page 353: ...Wiring Diagrams for Reference Si34 601A 342 Appendix FXHQ32MA 63MA 100MAVE 3D039801D...
Page 356: ...Si34 601A Wiring Diagrams for Reference Appendix 345 FXUQ71MA 100MA 125MAV1 3D044973A...
Page 357: ...Wiring Diagrams for Reference Si34 601A 346 Appendix FXMQ125MF 200MF 250MFV1 3D044996C...
Page 358: ...Si34 601A Wiring Diagrams for Reference Appendix 347 BEVQ71MA 100MA 125MAVE 3D044901B...
Page 381: ...Method of Checking The Inverter s Power Transistors and Diode Modules Si34 601A 370 Appendix...
Page 395: ...Si34 601A iv Index...