
Si34-601A
Troubleshooting (OP: Unified ON/OFF Controller)
Troubleshooting
313
[CHECK 4] Check for causes of drop in low pressure
Referring to the Fault Tree Analysis (FTA) shown below, probe the faulty points.
Abnormally low
low-pressure
(Low evaporating
temperature)
[In cooling]
(See *1.)
Faulty low
pressure
control
Faulty
compressor
capacity
control
Faulty low pressure sensor
←
Are the electrical characteristics normal?
Faulty control PCB
←
Is the pressure value checked with the Service Checker
corresponding to the measurement of the pressure sensor?
Faulty low
pressure
protection
control
Faulty low pressure sensor
←
Are the electrical characteristics normal?
Faulty hot gas solenoid valve
←
Are the coil resistance and insulation normal?
Faulty control PCB
←
Is the pressure value checked with the Service Checker
corresponding to the measurement of the pressure sensor?
[In both cooling
and heating]
(See *2.)
[In cooling]
If the indoor unit
electronic
expansion valve is
throttled too much:
(See *3.)
Faulty indoor
unit electronic
expansion valve
Faulty valve coil
Faulty valve body
←
Are the coil resistance and insulation normal?
Faulty
control
Faulty gas pipe
thermistor of indoor unit
Faulty liquid pipe thermistor
of indoor unit
Faulty control PCB
←
Check for the thermistor resistance and connection.
←
Check for the thermistor resistance and connection.
←
Is the pressure value checked with the Service Checker
corresponding to the measurement of the pressure sensor?
Faulty outdoor
unit electronic
expansion valve
Faulty valve coil
Faulty valve body
←
Are the coil resistance and insulation
normal?
[In heating]
If the outdoor unit
electronic
expansion valve
excessively
throttled:
(See *4.)
Faulty
control
Faulty low pressure sensor
Faulty suction pipe thermistor
Faulty control PCB
←
Are the electrical characteristics normal?
←
Check for the thermistor resistance and
connection.
[In cooling]
Low suction
air temperature
of the
evaporator
[In heating]
Low suction air
temperature of
indoor unit
Short circuit
←
Is the suction air temperature not less than 14˚C
←
Is the indoor temperature not more than 14˚C
Low ambient temperature
Faulty suction air thermistor of indoor unit
←
Is the connector properly connected?
Are the thermistor resistance characteristics normal?
Low suction air temperature of outdoor unit
←
Is the outdoor temperature not less than -20˚C
Faulty outdoor temperature thermistor of outdoor unit
←
Is the connector properly connected?
Are the thermistor resistance characteristics normal?
High pipe
resistance
Abnormal piping length
Bent or crashed pipe
Clogging of foreign particles
Stop valve closed
←
Does the piping length fall in the permissible range?
←
Conduct visual checks for pipe conditions.
←
Is there any temperature difference caused before
and after the filter or branch pipe?
←
Check to be sure the stop valve is open.
Less
circulation
quantity of
refrigerant
Degradation
in condensing
capacity
Inadequate refrigerant quantity
←
Refer to page 275.
Moisture choke
←
Eliminate moisture by vacuum operation.
Dirty
evaporator
Decreased
fan airflow
rate
Decreased
fan output
Faulty fan motor
←
Can the fan motor be rotated with hands?
Are the motor coil resistance and insulation normal?
←
Is the heat exchanger clogged?
Faulty control PCB
(Including capacity setting)
←
If a spare PCB is mounted, is the capacity
setting properly made?
High air
passage
resistance
Dirty filter
←
Is there any obstacle in the air passage?
←
Is the air filter clogged?
Obstacle
*1: For details of the compressor capacity control while in cooling, refer to “Compressor PI Control” on page 95.
*2: The “low pressure protection control” includes low pressure protection control and hot gas bypass control. For details, refer to page 119.
*3: In cooling, the indoor unit electronic expansion valve is used for “superheated degree control”. (For details, refer to page 135.)
*4: In heating, the outdoor unit electronic expansion valve (EV1) is used for “superheated degree control of outdoor unit heat exchanger”.
(For details, refer to page 107.)
Faulty electronic
expansion valve
control
SDK04009
Summary of Contents for VRV III RXYQ5-54PY1
Page 1: ...RXYQ5 54PY1 R 410A Heat Pump 50Hz Si34 601A...
Page 101: ...Refrigerant Flow for Each Operation Mode Si34 601A 90 Refirgerant Circuit...
Page 153: ...Outline of Control Indoor Unit Si34 601A 142 Function...
Page 219: ...Troubleshooting by Remote Controller Si34 601A 208 Troubleshooting...
Page 226: ...Si34 601A Troubleshooting by Remote Controller Troubleshooting 215...
Page 325: ...Troubleshooting OP Unified ON OFF Controller Si34 601A 314 Troubleshooting...
Page 327: ...Piping Diagrams Si34 601A 316 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ5PY1 3D050782...
Page 328: ...Si34 601A Piping Diagrams Appendix 317 RXYQ8P 3D050783...
Page 329: ...Piping Diagrams Si34 601A 318 Appendix RXYQ10P 12PY1 3D050784...
Page 330: ...Si34 601A Piping Diagrams Appendix 319 RXYQ14P 16P 18PY1 3D050785...
Page 336: ...Si34 601A Wiring Diagrams for Reference Appendix 325 RXYQ8PY1 3D050454J...
Page 337: ...Wiring Diagrams for Reference Si34 601A 326 Appendix RXYQ10PY1 3D050455H...
Page 338: ...Si34 601A Wiring Diagrams for Reference Appendix 327 RXYQ12PY1 3D051890G...
Page 339: ...Wiring Diagrams for Reference Si34 601A 328 Appendix RXYQ14P 16P 18PY1 3D050456H...
Page 344: ...Si34 601A Wiring Diagrams for Reference Appendix 333 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 346: ...Si34 601A Wiring Diagrams for Reference Appendix 335 FXZQ20M 25M 32M 40M 50M7V1B 3D038359...
Page 347: ...Wiring Diagrams for Reference Si34 601A 336 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Page 352: ...Si34 601A Wiring Diagrams for Reference Appendix 341 FXMQ200MA 250MAVE 3D039621B...
Page 353: ...Wiring Diagrams for Reference Si34 601A 342 Appendix FXHQ32MA 63MA 100MAVE 3D039801D...
Page 356: ...Si34 601A Wiring Diagrams for Reference Appendix 345 FXUQ71MA 100MA 125MAV1 3D044973A...
Page 357: ...Wiring Diagrams for Reference Si34 601A 346 Appendix FXMQ125MF 200MF 250MFV1 3D044996C...
Page 358: ...Si34 601A Wiring Diagrams for Reference Appendix 347 BEVQ71MA 100MA 125MAVE 3D044901B...
Page 381: ...Method of Checking The Inverter s Power Transistors and Diode Modules Si34 601A 370 Appendix...
Page 395: ...Si34 601A iv Index...