Field Setting
Si34-601A
174
Test Operation
3.2
Field Setting from Outdoor Unit
3.2.1
Field Setting from Outdoor Unit
List of Field Setting Items
This following section indicates the list of field setting items. For the lists of dip switch contents,
Setting mode 1, and Setting mode 2, refer to information in tables shown on the following page
onward.
For setting items of (*1), refer to detailed information provided on page 161 onward.
Setting item
Content and objective of setting
Overview of setting procedure
Function
setting
1
Setting of COOL/
HEAT selection
(*1)
COOL/HEAT selection methods are
possible to select from the following
(1) Control by each outdoor unit using the
indoor unit remote controller
(2) Control by each outdoor unit using the
COOL/HEAT selection remote
controller
(3) Batch control by outdoor unit group
using the indoor unit remote controller
(4) Batch control by outdoor unit group
using the COOL/HEAT selection
remote controller
In order to use the COOL/HEAT selection
remote controller, set the DS1-1 on the
outdoor unit PC board to OUT.
For outdoor unit group control, set the
system to "BATCH MASTER" or "SLAVE"
while in "Setting mode 1". Then, make
setting of COOL/HEAT batch address.
2
Setting of low noise
operation (*1)
A. Use external input to step down the upper
limit of the fan (factory set to Step 8),
providing low noise level.
(1) Mode 1: Step 6 or lower
(2) Mode 2: Step 5 or lower
(3) Mode 3: Step 4 or lower
Use the "External control adaptor for
outdoor unit".
Set to "External control adaptor for outdoor
unit" with No. 12 of "Setting mode 2" and
select the mode with No. 25.
If necessary, set the "Capacity priority
setting" to ON with No. 29.
B. The low noise operation aforementioned is
enabled in nighttime automatic low noise
operation mode.
Start time: Possible to select in the range of
20:00 to 24:00 hours.
End time: Possible to select in the range of
06:00 to 08:00 hours.
(Use the said time as a guide since the
start time and the end time are estimated
according to outdoor temperatures.)
Make this setting while in "Setting mode 2".
Select a mode with No. 22 of "Setting mode
2".
Select the start time with No. 26 and the
end time with No. 27.
If necessary, set the "Capacity priority
setting" to ON with No. 29.
3
Setting of demand
operation (*1)
Used to place limits on the compressor
operating frequency to control the upper
limit of power consumption.
(1) Mode 1 of Demand 1: 60% or less of
rating
(2) Mode 2 of Demand 1: 70% or less of
rating
(3) Mode 3 of Demand 1: 80% or less of
rating
(4) Demand 2: 40% or less of rating
For setting with the use of "external control
adapter":
Set the system to "External control adaptor
for outdoor unit" with No. 12 of Setting
mode 2" and select the mode with No. 30.
For setting only in "Setting mode 2":
Set the system to Normal demand mode
with No. 32 of "Setting mode 2" and select
the mode with No. 30.
4
Setting of AirNet
address
Used to make address setting with AirNet
connected.
Set the AirNet to an intended address
using binary numbers with No. 13 of
"Setting mode 2".
5
Setting of hot water
heater
Make this setting to conduct heating
operation using the hot water heater.
Set No. 16 of "Setting mode 2" to ON.
6
Setting of high
static pressure
Make this setting to operate a system with
diffuser duct while in high static pressure
mode. (Use this setting mode when shields
are installed on upper floors or balconies.)
* In order to mount the diffuser duct, remove
the cover from the outdoor unit fan.
Set No. 18 of "Setting mode 2" to ON.
Summary of Contents for VRV III RXYQ5-54PY1
Page 1: ...RXYQ5 54PY1 R 410A Heat Pump 50Hz Si34 601A...
Page 101: ...Refrigerant Flow for Each Operation Mode Si34 601A 90 Refirgerant Circuit...
Page 153: ...Outline of Control Indoor Unit Si34 601A 142 Function...
Page 219: ...Troubleshooting by Remote Controller Si34 601A 208 Troubleshooting...
Page 226: ...Si34 601A Troubleshooting by Remote Controller Troubleshooting 215...
Page 325: ...Troubleshooting OP Unified ON OFF Controller Si34 601A 314 Troubleshooting...
Page 327: ...Piping Diagrams Si34 601A 316 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ5PY1 3D050782...
Page 328: ...Si34 601A Piping Diagrams Appendix 317 RXYQ8P 3D050783...
Page 329: ...Piping Diagrams Si34 601A 318 Appendix RXYQ10P 12PY1 3D050784...
Page 330: ...Si34 601A Piping Diagrams Appendix 319 RXYQ14P 16P 18PY1 3D050785...
Page 336: ...Si34 601A Wiring Diagrams for Reference Appendix 325 RXYQ8PY1 3D050454J...
Page 337: ...Wiring Diagrams for Reference Si34 601A 326 Appendix RXYQ10PY1 3D050455H...
Page 338: ...Si34 601A Wiring Diagrams for Reference Appendix 327 RXYQ12PY1 3D051890G...
Page 339: ...Wiring Diagrams for Reference Si34 601A 328 Appendix RXYQ14P 16P 18PY1 3D050456H...
Page 344: ...Si34 601A Wiring Diagrams for Reference Appendix 333 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 346: ...Si34 601A Wiring Diagrams for Reference Appendix 335 FXZQ20M 25M 32M 40M 50M7V1B 3D038359...
Page 347: ...Wiring Diagrams for Reference Si34 601A 336 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Page 352: ...Si34 601A Wiring Diagrams for Reference Appendix 341 FXMQ200MA 250MAVE 3D039621B...
Page 353: ...Wiring Diagrams for Reference Si34 601A 342 Appendix FXHQ32MA 63MA 100MAVE 3D039801D...
Page 356: ...Si34 601A Wiring Diagrams for Reference Appendix 345 FXUQ71MA 100MA 125MAV1 3D044973A...
Page 357: ...Wiring Diagrams for Reference Si34 601A 346 Appendix FXMQ125MF 200MF 250MFV1 3D044996C...
Page 358: ...Si34 601A Wiring Diagrams for Reference Appendix 347 BEVQ71MA 100MA 125MAVE 3D044901B...
Page 381: ...Method of Checking The Inverter s Power Transistors and Diode Modules Si34 601A 370 Appendix...
Page 395: ...Si34 601A iv Index...