Si39-306
Troubleshooting by Remote Controller
Troubleshooting
145
Outdoor
Unit
LA
9
9
9
Malfunction of power unit
—
LC
9
9
9
Malfunction of transmission between inverter and
control PC board
P1
9
9
9
Inverter over-ripple protection
P4
9
9
9
Malfunction of inverter radiating fin temperature rise
sensor
PJ
9
9
9
Mismatching of Inverter·Fan driver
194
System
U0
8
7
9
Low pressure drop due to refrigerant shortage or
electronic expansion valve failure
U1
9
9
9
Reverse phase / open phase
U2
9
9
9
Power supply insufficient or instantaneous failure
U3
9
9
9
Check operation is not conducted.
U4
9
9
9
Malfunction of transmission between indoor and
outdoor units
U5
9
9
9
Malfunction of transmission between remote
controller and indoor unit
U5
7
8
7
Failure of remote controller PC board or setting
during control by remote controller
U7
9
9
9
Malfunction of transmission between outdoor units
U8
9
9
7
Malfunction of transmission between master and
slave remote controllers (malfunction of slave remote
controller)
U9
9
9
9
Malfunction of transmission between indoor unit and
outdoor unit in the same system
UA
9
9
9
Excessive number of indoor units etc.
UC
8
8
8
Address duplication of central remote controller
UE
9
9
9
Malfunction of transmission between central remote
controller and indoor unit
UF
9
9
9
Refrigerant system not set, incompatible wiring /
piping
UH
9
9
9
Malfunction of system, refrigerant system address
undefined
Centrali
zed
Control
and
Schedu
le
Timer
M1
8
or
7
9
9
PC board defect
M8
8
or
7
9
9
Malfunction of transmission between optional
controllers for centralized control
MA
8
or
7
9
9
Improper combination of optional controllers for
centralized control
MC
8
or
7
9
9
Address duplication, improper setting
Heat
Reclai
m
Ventilat
ion
64
8
7
9
Indoor unit’s air thermistor error
—
65
8
7
9
Outside air thermistor error
—
68
8
7
9
—
6A
8
7
9
Damper system alarm
—
6A
9
9
9
Damper thermistor error
—
6F
8
7
9
Malfunction of simple remote controller
—
6H
8
7
9
Malfunction of door switch or connector
—
94
9
9
9
Internal transmission error
—
Malfunction
code
Operation
lamp
Inspection
display
Unit No.
Malfunction contents
Page
Referred
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.
Summary of Contents for VRV II REYQ8MY1B
Page 19: ...Model Selection Si39 306 8 General Information...
Page 150: ...Si39 306 Troubleshooting by Remote Controller Troubleshooting 139...
Page 250: ...Si39 306 Piping Diagrams Appendix 239 REYQ14MY1B REYQ16MY1B 4D042070A...
Page 252: ...Si39 306 Piping Diagrams Appendix 241 1 3 BS Unit BSVQ100MV1 BSVQ160MV1 BSVQ250MV1 4D042115...
Page 254: ...Si39 306 Wiring Diagrams for Reference Appendix 243 REYQ14MY1B REYQ16MY1B 3D038572...
Page 256: ...Si39 306 Wiring Diagrams for Reference Appendix 245 REYQ18 20 22 24 26 28 30 32MY1B 3D043436...
Page 257: ...Wiring Diagrams for Reference Si39 306 246 Appendix REYQ34 36 38 40 42 44 46 48MY1B 3D043437...
Page 259: ...Wiring Diagrams for Reference Si39 306 248 Appendix FXCQ40M 50M 80M 125MVE 3D039557A...
Page 260: ...Si39 306 Wiring Diagrams for Reference Appendix 249 FXZQ20M 25M 32M 40M 50MVE 3D038359...
Page 262: ...Si39 306 Wiring Diagrams for Reference Appendix 251 FXKQ25M 32M 40M 63MVE 3D039564A...
Page 264: ...Si39 306 Wiring Diagrams for Reference Appendix 253 FXMQ40M 50M 63M 80M 100M 125MVE 3D039620A...
Page 265: ...Wiring Diagrams for Reference Si39 306 254 Appendix FXMQ200M 250MVE 3D039621A...
Page 266: ...Si39 306 Wiring Diagrams for Reference Appendix 255 FXHQ32M 63M 100MVE 3D039801C...
Page 267: ...Wiring Diagrams for Reference Si39 306 256 Appendix FXAQ20M 25M 32MVE 40M 50M 63MVE 3D034206A...
Page 283: ...REFNET Pipe System Si39 306 272 Appendix...
Page 284: ...Si39 306 Appendix 273 DPSOH RI RQQHFWLRQ 5 7 SH 5 4 0 HDW 5HFRYHU...
Page 285: ...Si39 306 274 Appendix...
Page 291: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 306 280 Appendix...