Specifications
Si39-306
34
Specifications
Wall Mounted Type
Notes:
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length:7.5m,
level difference: 0m.
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m,
level difference; 0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
Model
FXAQ20MVE
FXAQ25MVE
FXAQ32MVE
1 Cooling Capacity (19.5°CWB)
kcal/h
2,000
2,500
3,150
Btu/h
7,900
9,900
12,500
kW
2.3
2.9
3.7
2 Cooling Capacity (19.0°CWB)
kW
2.2
2.8
3.6
3 Heating Capacity
kcal/h
2,200
2,800
3,400
Btu/h
8,500
10,900
13,600
kW
2.5
3.2
4.0
Casing Color
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
Dimensions: (H×W×D)
mm
290×795×230
290×795×230
290×795×230
Coil (Cross
Fin Coil)
Rows×Stages×Fin Pitch
mm
2×14×1.4
2×14×1.4
2×14×1.4
Face Area
m²
0.161
0.161
0.161
Fan
Model
QCL9661M
QCL9661M
QCL9661M
Type
Cross Flow Fan
Cross Flow Fan
Cross Flow Fan
Motor Output × Number
of Units
W
40×1
40×1
40×1
Air Flow Rate (H/L)
m³/min
7.5/4.5
8/5
9/5.5
cfm
265/159
282/177
318/194
Drive
Direct Drive
Direct Drive
Direct Drive
Temperature Control
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Sound Absorbing Thermal Insulation Material
Foamed Polystyrene /
Foamed Polyethylene
Foamed Polystyrene /
Foamed Polyethylene
Foamed Polystyrene /
Foamed Polyethylene
Air Filter
Resin Net (Washable)
Resin Net (Washable)
Resin Net (Washable)
Piping
Connections
Liquid Pipes
mm
φ
6.4 (Flare Connection)
φ
6.4 (Flare Connection)
φ
6.4 (Flare Connection)
Gas Pipes
mm
φ
12.7 (Flare Connection)
φ
12.7 (Flare Connection)
φ
12.7 (Flare Connection)
Drain Pipe
mm
VP13
(External Dia. 18 Internal Dia. 13)
VP13
(External Dia. 18 Internal Dia. 13)
VP13
(External Dia. 18 Internal Dia. 13)
Machine Weight
kg
11
11
11
5 Sound Level (H/L)
dBA
35/29
36/29
37/29
Safety Devices
Fuse
Fuse
Fuse
Refrigerant Control
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Connectable outdoor unit
R410A M Series
R410A M Series
R410A M Series
Standard Accessories
Operation Manual, Installation
Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.
Operation Manual, Installation
Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.
Operation Manual, Installation
Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.
Drawing No.
3D039370
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Summary of Contents for VRV II REYQ8MY1B
Page 19: ...Model Selection Si39 306 8 General Information...
Page 150: ...Si39 306 Troubleshooting by Remote Controller Troubleshooting 139...
Page 250: ...Si39 306 Piping Diagrams Appendix 239 REYQ14MY1B REYQ16MY1B 4D042070A...
Page 252: ...Si39 306 Piping Diagrams Appendix 241 1 3 BS Unit BSVQ100MV1 BSVQ160MV1 BSVQ250MV1 4D042115...
Page 254: ...Si39 306 Wiring Diagrams for Reference Appendix 243 REYQ14MY1B REYQ16MY1B 3D038572...
Page 256: ...Si39 306 Wiring Diagrams for Reference Appendix 245 REYQ18 20 22 24 26 28 30 32MY1B 3D043436...
Page 257: ...Wiring Diagrams for Reference Si39 306 246 Appendix REYQ34 36 38 40 42 44 46 48MY1B 3D043437...
Page 259: ...Wiring Diagrams for Reference Si39 306 248 Appendix FXCQ40M 50M 80M 125MVE 3D039557A...
Page 260: ...Si39 306 Wiring Diagrams for Reference Appendix 249 FXZQ20M 25M 32M 40M 50MVE 3D038359...
Page 262: ...Si39 306 Wiring Diagrams for Reference Appendix 251 FXKQ25M 32M 40M 63MVE 3D039564A...
Page 264: ...Si39 306 Wiring Diagrams for Reference Appendix 253 FXMQ40M 50M 63M 80M 100M 125MVE 3D039620A...
Page 265: ...Wiring Diagrams for Reference Si39 306 254 Appendix FXMQ200M 250MVE 3D039621A...
Page 266: ...Si39 306 Wiring Diagrams for Reference Appendix 255 FXHQ32M 63M 100MVE 3D039801C...
Page 267: ...Wiring Diagrams for Reference Si39 306 256 Appendix FXAQ20M 25M 32MVE 40M 50M 63MVE 3D034206A...
Page 283: ...REFNET Pipe System Si39 306 272 Appendix...
Page 284: ...Si39 306 Appendix 273 DPSOH RI RQQHFWLRQ 5 7 SH 5 4 0 HDW 5HFRYHU...
Page 285: ...Si39 306 274 Appendix...
Page 291: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 306 280 Appendix...
Page 305: ...Si39 306 iv Index...