Field Setting
Si39-306
118
Test Operation
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
∗
Factory set
0
EMG (emergency
operation)
INV compressor
operation inhibited.
8
7
7
7
7
7
7
Normal operation
8777778
∗
Emergency operation
8777787
1
—
2
Low noise/demand
address
8
7
7
7
7
8
7
Address
0
8777777
∗
Binary number
1
8777778
(6 digits)
~
31
8788888
5
Indoor forced fan H
8
7
7
7
8
7
8
Normal operation
8777778
∗
Indoor forced fan H
8777787
6
Indoor forced
operation
8
7
7
7
8
8
7
Normal operation
8777778
∗
Indoor forced operation
8777787
8
Te setting
8
7
7
8
7
7
7
High
8777877
Normal (factory setting)
8777787
∗
Low
8777778
9
Tc setting
8
7
7
8
7
7
8
High
8777877
Normal (factory setting)
8777787
∗
Low
8777778
10 Defrost setting
8
7
7
8
7
8
7
Quick defrost
8777877
Normal (factory setting)
8777787
∗
Slow defrost
8777778
11
Sequential operation
setting
8
7
7
8
7
8
8
OFF
8777778
ON
8777787
∗
12
External low noise/
demand setting
8
7
7
8
8
7
7
External low noise/demand:
NO
8777778
∗
External low noise/demand:
YES
8777787
13 Airnet address
8
7
7
8
8
7
8
Address
0
8777777
∗
Binary number
1
8777778
(6 digits)
~
63
8788888
18
High static pressure
setting
8
7
8
7
7
8
7
High static pressure setting:
OFF
8777778
∗
High static pressure setting:
ON
8777787
19
Emergency
operation
(STD compressor is
inhibited to operate.)
8
7
8
7
7
8
8
OFF
8777777
∗
STD 1, 2 operation: Inhibited
8777778
STD 2 operation: Inhibited
8777787
20
Additional refrigerant
operation setting
8
7
8
7
8
7
7
Refrigerant charging: OFF
8777778
∗
Refrigerant charging: ON
8777787
21
Refrigerant recovery
mode setting
8
7
8
7
8
7
8
Refrigerant recovery: OFF
8777778
∗
Refrigerant recovery: ON
8777787
22
Night-time low noise
setting
8
7
8
7
8
8
7
OFF
8777777
∗
Level 1 (outdoor fan with 8 step or lower)
8777778
Level 2 (outdoor fan with 7 step or lower)
8777787
Level 3 (outdoor fan with 6 step or lower)
8777788
25 Low noise setting
8
7
8
8
7
7
8
Level 1 (outdoor fan with 8 step or lower)
8777778
Level 2 (outdoor fan with 7 step or lower)
8777787
∗
Level 3 (outdoor fan with 6 step or lower)
∗
8777877
Summary of Contents for VRV II REYQ8MY1B
Page 19: ...Model Selection Si39 306 8 General Information...
Page 150: ...Si39 306 Troubleshooting by Remote Controller Troubleshooting 139...
Page 250: ...Si39 306 Piping Diagrams Appendix 239 REYQ14MY1B REYQ16MY1B 4D042070A...
Page 252: ...Si39 306 Piping Diagrams Appendix 241 1 3 BS Unit BSVQ100MV1 BSVQ160MV1 BSVQ250MV1 4D042115...
Page 254: ...Si39 306 Wiring Diagrams for Reference Appendix 243 REYQ14MY1B REYQ16MY1B 3D038572...
Page 256: ...Si39 306 Wiring Diagrams for Reference Appendix 245 REYQ18 20 22 24 26 28 30 32MY1B 3D043436...
Page 257: ...Wiring Diagrams for Reference Si39 306 246 Appendix REYQ34 36 38 40 42 44 46 48MY1B 3D043437...
Page 259: ...Wiring Diagrams for Reference Si39 306 248 Appendix FXCQ40M 50M 80M 125MVE 3D039557A...
Page 260: ...Si39 306 Wiring Diagrams for Reference Appendix 249 FXZQ20M 25M 32M 40M 50MVE 3D038359...
Page 262: ...Si39 306 Wiring Diagrams for Reference Appendix 251 FXKQ25M 32M 40M 63MVE 3D039564A...
Page 264: ...Si39 306 Wiring Diagrams for Reference Appendix 253 FXMQ40M 50M 63M 80M 100M 125MVE 3D039620A...
Page 265: ...Wiring Diagrams for Reference Si39 306 254 Appendix FXMQ200M 250MVE 3D039621A...
Page 266: ...Si39 306 Wiring Diagrams for Reference Appendix 255 FXHQ32M 63M 100MVE 3D039801C...
Page 267: ...Wiring Diagrams for Reference Si39 306 256 Appendix FXAQ20M 25M 32MVE 40M 50M 63MVE 3D034206A...
Page 283: ...REFNET Pipe System Si39 306 272 Appendix...
Page 284: ...Si39 306 Appendix 273 DPSOH RI RQQHFWLRQ 5 7 SH 5 4 0 HDW 5HFRYHU...
Page 285: ...Si39 306 274 Appendix...
Page 291: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 306 280 Appendix...
Page 305: ...Si39 306 iv Index...