Field Setting from Outdoor Unit
SiBE341027
76
Test Operation
21
Refrigerant
recovery/vacuuming
mode setting
k
h
k
h
k
h
k
Refrigerant recovery / vacuuming: OFF
k h h h h h k
∗
Refrigerant recovery / vacuuming: ON
k h h h h k h
22
Low night noise
setting
k
h
k
h
k
k
h
OFF
k h h h h h h
∗
Level 1 (outdoor fan with 6 step or lower)
k h h h h h k
Level 2 (outdoor fan with 5 step or lower)
k h h h h k h
Level 3 (outdoor fan with 4 step or lower)
k h h h h k k
25
Setting of external
low noise level
k
h
k
k
h
h
k
Level 1 (outdoor fan with 6 step or lower)
k h h h h h k
Level 2 (outdoor fan with 5 step or lower)
k h h h h k h
∗
Level 3 (outdoor fan with 4 step or lower)
k h h h k h h
26
Low night noise
operation start
setting
k
h
k
k
h
k
h
About 20:00
k h h h h h k
About 22:00
k h h h h k h
∗
About 24:00
k h h h k h h
27
Low night noise
operation end
setting
k
h
k
k
h
k
k
About 6:00
k h h h h h k
About 7:00
k h h h h k h
About 8:00
k h h h k h h
∗
28
Power transistor
check mode
k
h
k
k
k
h
h
OFF
k h h h h h k
∗
ON
k h h h h k h
29
Capacity priority
setting
k
h
k
k
k
h
k
OFF
k h h h h h k
∗
ON
k h h h h k h
30 Demand setting 1
k
h
k
k
k
k
h
60 % demand
k h h h h h k
70 % demand
k h h h h k h
∗
80 % demand
k h h h k h h
32
Normal demand
setting
k
k
h
h
h
h
h
OFF
k h h h h h k
∗
ON
k h h h h k h
35
Setting of difference
in height for the
outdoor unit
k
k
h
h
h
k
k
Normal
k h h h h h h
∗
65 m or less
k h h h k h k
38
Emergency
operation
(Master unit with
multi-outdoor-unit
system is inhibited to
operate.)
k
k
h
h
k
k
h
OFF
k h h h h h k
∗
Master unit operation: Inhibited
k h h h h k h
39
Emergency
operation
(Slave unit 1 and 2
with multi-outdoor-
unit system is
inhibited to operate.)
k
k
h
h
k
k
k
OFF
k h h h h h k
∗
Slave unit 1 operation: Inhibited
k h h h h k h
40
Emergency
operation
(Slave unit 3 with
multi-outdoor-unit
system is inhibited to
operate.)
k
k
h
k
h
h
h
OFF
k h h h h h k
∗
Slave unit 2 operation: Inhibited
k h h h h k h
55
Master-slave set-up
for multi outdoor
units
k
k
k
h
h
k
k
Automatic judgement
k h h h h h h
∗
Master
k h h h h h k
Slave 1
k h h h h k h
Slave 2
k h h h h k k
Slave 3
k h h h k h h
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
∗
Factory set