Troubleshooting by Remote Controller
SiBE341027
152
Service Diagnosis
2.31 Power Supply Insufficient or Instantaneous Failure
Remote
Controller
Display
U2
Applicable
Models
RQYQ-PY1B
Method of Error
Detection
Detection of voltage of main circuit capacitor built in the inverter PCB and power supply voltage.
Error Decision
Conditions
When the voltage aforementioned is not less than 190V.
Supposed
Causes
Power supply insufficient
Instantaneous power failure
Open phase
Defective inverter PCB
Defective outdoor service monitor PCB
Defective compressor
Defective main circuit wiring
Defective fan motor
Defective connection of signal cable