background image

or other field-supply parts for the newly-mounted 

ceiling. Before continuing installation, adjust the 

clearance between the lifting screw and the ceiling to 

50-80mm.

[Installation example] 

222222221 

Figure 5 

Roof 

Long nut or thread 

line equipment 

Ceiling 

Note) All the above parts are supplied at the installation site. 

5. Indoor unit installation

Be sure to use only the specified parts for installation 

work. 

installation procedure for locations with newly­

mounted ceiling: 

(1) --+ (2) --+ (3) --+ (4) --+ (5)

Installation procedure for locations with existing ceiling:

(1) --+ (3) --+ (4) --+ (5)

(1 )Temporarily  install the indoor units 

• Attach the hanger bracket to the lifting screw. Be sure to

secure the hanger bracket firmly at the upper and lower

ends using the nuts and hanger washers®· The washer
fixing  plate (!)  can  prevent  the  hanger  washer ® from
slipping off.

Hanger washers@ 

(accessories) 

Hanger bracket 

Washer Clamp (7) 

(accessory) 

Insert 

Upper side nut 

[Secure the hanger bracket] 

[Washer clamp(7} fixing method] 

Figure 6 

Figure 7 

(2)For dimensions of the ceiling opening, refer to the

paper board for ceiling opening. Consult your builder or

carpenter for details.

• Center of the ceiling opening is marked on the paper

board for ceiling  opening.  Center of the units is in line

with that of the ceiling opening.

• Fix the paper board for ceiling opening to the units

using 4 screws ®·  In this case, make the hole on the

unit's hanger bracket corresponded to the mounting

hole on the paper board for ceiling opening.

• Relative positions of the main unit and ceiling are marked

on the paper board for ceiling opening. Adjust the height
of the unit body accordingly.

□  □ 

Screws@ 

(accessories) 

Paper board for ceiling opening 

(within the bottom box) 

[Secure the mounting paper pattern] 

Figure 8 

(3)Adjust the levelness of the air conditioner.

• The  indoor  unit  is  equipped  with  a  built-in  drain  pump

and float switch. Adjust the levelness using a level meter
or polyethylene pipe filled with water.

Levelness of unit should not exceed 0.5 deg down at opposite 

side of drain pump. 

Level 

meter 

Vinyl Tube 

-�Caution---------------­

If the unit tilts to the opposite flow direction of the condensed 

water,  the  float  switch  will  not  operate  normally,  which  will 

cause water leakage. 

(4)Pull out the inserted washer fixing plate(!) which is used

to prevent the washer from slipping off and tighten the 
upper nut.

(5)Remove the paper board for ceiling opening.

6. Decorative panel installation

<Refer to panel operation & installation manual for 

detailed decorative panel installation.> 

7. Refrigerant piping installation

<For installing the refrigerant piping of the outdoor unit, 

refer to the installation manual included with the outdoor 

unit.> 

<Insulate both gas side piping and liquid  side piping 

effectively. Otherwise, it may cause water leakage. Use 

the insulation material which can withstand high 

temperature of 120  °C or more. Besides, reinforce the 

insulation of the refrigerant piping in accordance with 

the installation environment. If not reinforced, 

condensation could form on the surface of the 

insulation material.> 

<Be sure to check the refrigerant is R41 0A before 

performing refrigerant piping installation. Adopting 

other refrigerants may result in the abnormal operation 

of the unit.> 

-�Caution---------------­

This product is a dedicated model for the new refrigerant R41 0A. 
Always follow instructions below to perform installation work. 

• Be sure to use the special pipe cutters and flaring tools for

R410A.

• When connecting the flaring,  only coat the refrigerant oil

(ester or ether oil) to the inner side of the flaring.

• Always use the flaring nut included with the unit. (Do not

use other flaring nuts such as  1-type flaring nut. Using

other flaring nuts may lead to refrigerant leakage.)

• To prevent entry of any dirt, dust or moisture into the piping,

adjust the piping through pinching or sealing methods.

Summary of Contents for VRV FXKQ32AV16

Page 1: ...NUAL VRV Model Ceiling Mounted Cassette Single Flow Type FXKQ32AV16 FXKQ40AV16 FXKQS0AV16 FXKQ63AV16 CAREFULLY READ THESE INSTRUCTIONS BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE...

Page 2: ...rain piping installation 8 9 Electrical wiring work 9 9 1 Overview 9 9 2 Specifications of the standard electric wires 9 9 3 Electrical characteristics 10 10 Wiring example 10 10 1 How to connect powe...

Page 3: ...as well as this manual 2 An insufficient power supply capacity or improper electrical operation may lead to electric shocks or fire hazards indoor unit as far away from fluorescent lamps as possible...

Page 4: ...ince R41 0A is a mixed refrigerant the required additional refrigerant must be charged in its liquid state If the system is charged with refrigerant in its gaseous state due to composition change the...

Page 5: ...perate normally or nameplate of the unit with parts burnt out Are the wiring and piping The unit doesn t connected properly operate normally or with parts burnt out Is the unit earthed safely Due to l...

Page 6: ...instances 2 Perform installation with a lifting screw Study if the ceiling is strong enough to hold the weight of the indoor unit If the ceiling is not strong enough reinforce the ceiling in advance R...

Page 7: ...quipped with a built in drain pump and float switch Adjust the levelness using a level meter or polyethylene pipe filled with water Levelness of unit should not exceed 0 5 deg down at opposite side of...

Page 8: ...ommended and only use in emergency It s necessary to use the torque wrench to install the units If you have to install the units but without the torque wrench then perform installation based on follow...

Page 9: ...in stagnates in the drain piping the piping may be clogged To prevent the piping from bending and sagging down secure them every 1 1 5m using slings Use the accessory drain hose CD and metal clip The...

Page 10: ...efer to the Remote controller installation manual included with it All wiring work must be carried out by the qualified electricians The system includes several indoor units Name each indoor unit afte...

Page 11: ...on wiring weak current Remote controller wiring weak current Caution Outside the air conditioner don t route the remote controller wiring and transmission wiring together with other electrical wiring...

Page 12: ...or 2 remote controllers control 1 indoor unit Power supply Single phase 220 240V 50Hz L N H Outdoor unit i I Note No need to input the indoor unit address during group control L_ _ J Afterturning on...

Page 13: ...anel s connecting wires refer to the panel installation manual for derailed information 11 Decorative panel installation for test run To perform test run without installing the decorative panel read t...

Page 14: ...13...

Page 15: ...DAIKIN VRV Model Ceiling Mounted Cassette Single Flow Type FXKQ32AV16 FXKQ40AV16 FXKQ50AV16 FXKQ63AV16 OPERATION MANUAL...

Page 16: ...injury or property damage or even serious injury under some circumstances After reading keep this manual in a convenient place so that you can refer to it whenever necessary If the equipment is trans...

Page 17: ...ner in places with excessive oily smoke such as cooking rooms or in places with flammable gas corrosive gas or metal dust Using the air conditioner in such places may cause a fire or air conditioner f...

Page 18: ...ury or electric shocks To avoid injury do not touch the air inlet or aluminum fins of the air conditioner Do not place objects in direct proximity of the outdoor unit and do not let leaves and other d...

Page 19: ...not clean the product with organic solvents such as paint thinner Using the organic solvents may result in cracks electric shocks or fire hazards Ask the technical expertise to install the optional ac...

Page 20: ...leakage electric shocks and fire hazards The refrigerant within the air conditioner is safe Generally it is unlikely to leak However in case of a refrigerant leakage in the rooms it may generate harmf...

Page 21: ...d by refrigerant flow in the air conditioner During cooling or heating operation this sound can be heard while discharging the water gathered in the air conditioner through the drain pump The sound ca...

Page 22: ...rate and direction set properly Does the voltage comply with the instructions of the operation installation manual Is the air filter dirty Are the indoor and outdoor unit s suction inlet and air outle...

Reviews: