(2}Check if the drainage is proper after completing installation. 

After completing wiring installation 

• To prevent water from gathering in the electrical

components such as the drain pump, add about

1 000CC water slowly from the air outlet. Check the

drainage condition in accordance with the "12. Field

settings and test run" while performing cooling

operation.

During wiring installation 

-& 

Caution---------------

• All electrical work (including grounding engineering)

must be carried out by the electricians with professional

qualifications.

• If the electricians are absent from the site, check the

drainage using steps 3 to 6 after the system test run is

stopped.

1. Remove the electrical component box cover and

concect the single-phase 50Hz, 220-240V power

circuit to the L and N of the power terminal block.

2. Check if the electrical component box cover has

been fastened completely before turning on the

power supply.

3. To prevent water from gathering in the electrical

components such as the drain pump, add about

1 000CC water slowly from the air outlet.

4. Turn on the power supply to start the drain pump. It is

possible to check the drainage condition through the

transparent part of the drain socket.  {The drain pump

will stop automatically after 10 minutes.)

(Unit 

[mm]) 

100 

�-¥'��f's�����-�---

Plastic water 

bottle 

(Outlet pipe 

about100mm 

long) 

Figure 18 

Terminal 

block 

Figure 19 

Service water outlet 

(With rubber stopper) 

discharge of water 

gathered in drain pan 

through this outlet 

[Water adding method] 

• 

'-y---' 

Power supply Single phase 

'"'-'220-240V 50Hz 

-& 

Caution---------------

• Be careful that the fan is also rotating now.

• Do not touch the drain pump to prevent electric shocks.

5. After completing drainage inspection (Figures 18 and

19), shut off the power supply and remove the power

wiring.

6. Attach the electrical component box cover as original.

9. Electrical wiring work

9-1.0verview

• Always shut down the power supply before performing any

electrical work.

• All locally-purchased parts & materials and electrical work

must comply with local codes.

• Use copper conductors only.
• When performing the electrical wiring work, refer to the

"wiring diagram" labeled to inside casing near EL box.

• For details of the remote controller's wiring, refer to the

"Remote controller installation manual" included with it.

• All wiring work must be carried out by the qualified

electricians.

• The system includes several indoor units. Name each

indoor unit after A unit,  B unit.... and make sure that the 

numbers of the wires connected from the terminal blocks 

are consist with that of the outdoor unit and BS unit. 

Incorrect wire and piping connection between the indoor 

unit and outdoor unit will result in the air conditioning 

system abnormally operating. To prevent error occurring, 

perform wiring by referring to [Wiring example]. 

• Be sure to install a line breaker or earth leakage circuit

breaker near the power supply.

• Do not connect the earth wire to the gas pipes, water pipes,

lightning rods or telephone earth wires.

• Gas pipes: gas leakage can cause explosion or fire.

• Water pipes: cannot be grounded if hard polyethylene

pipes are used.

• Telephone earth wires and lighting rods: the ground

potential when struck by lightning gets extremely high.

• To prevent short circuit of the power wiring, terminals with

insulation sleeves must be used.

• Do not turn on the power supply (line breaker or earth

leakage circuit breaker) before completing all electrical

work.

9-2.Specifications of the standard electric wires

Power wiring, etc.

Power supply wiring 

Remote controller wiring 

Transmission wiring 

Model 

Field 

fuses  Wiring 

Size 

Wiring 

Size 

-a-

FXKQ32AV16 

Vinyl cord 

H05VV-U3G  2.5 mm'  with sheath 

0.75-

FXKQ40AV16 

16A 

or cable 

1.25 mm' 

FXKQ50AV16 

NOTE 4, 5)  NOTE 7) 

(2 core) 

FXKQ63AV16 

NOTE 6) 

Note

-a-

1. It is possible to have the overcurrent circuit breaker

instead of the fuse.

2. If the electric wires are located in the places where they

are easy to be touched by personnel, mount the earth

leakage circuit breaker to prevent electric shocks.

3. Use the earth leakage circuit breaker compatible with

the appliances for grounding over-current protection

and short circuit protection.  If the ground protection

special appliance is mounted to the earth leakage circuit

breaker, be sure to mount a line breaker together.

4. Shows only in case of protected piping. Use H07RN-F in

case of no protection.

5. Supply cords shall not be lighter than polychloroprene

sheathed flexible cord (code designation 60245 IEC 57)

6. Vinyl cord with sheath or cable (Insulated thickness : 1 mm

or more) 

7.  Wiring size and length  must comply with  local codes or

IEC 60335-1 (Table 11)

Summary of Contents for VRV FXKQ32AV16

Page 1: ...NUAL VRV Model Ceiling Mounted Cassette Single Flow Type FXKQ32AV16 FXKQ40AV16 FXKQS0AV16 FXKQ63AV16 CAREFULLY READ THESE INSTRUCTIONS BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE...

Page 2: ...rain piping installation 8 9 Electrical wiring work 9 9 1 Overview 9 9 2 Specifications of the standard electric wires 9 9 3 Electrical characteristics 10 10 Wiring example 10 10 1 How to connect powe...

Page 3: ...as well as this manual 2 An insufficient power supply capacity or improper electrical operation may lead to electric shocks or fire hazards indoor unit as far away from fluorescent lamps as possible...

Page 4: ...ince R41 0A is a mixed refrigerant the required additional refrigerant must be charged in its liquid state If the system is charged with refrigerant in its gaseous state due to composition change the...

Page 5: ...perate normally or nameplate of the unit with parts burnt out Are the wiring and piping The unit doesn t connected properly operate normally or with parts burnt out Is the unit earthed safely Due to l...

Page 6: ...instances 2 Perform installation with a lifting screw Study if the ceiling is strong enough to hold the weight of the indoor unit If the ceiling is not strong enough reinforce the ceiling in advance R...

Page 7: ...quipped with a built in drain pump and float switch Adjust the levelness using a level meter or polyethylene pipe filled with water Levelness of unit should not exceed 0 5 deg down at opposite side of...

Page 8: ...ommended and only use in emergency It s necessary to use the torque wrench to install the units If you have to install the units but without the torque wrench then perform installation based on follow...

Page 9: ...in stagnates in the drain piping the piping may be clogged To prevent the piping from bending and sagging down secure them every 1 1 5m using slings Use the accessory drain hose CD and metal clip The...

Page 10: ...efer to the Remote controller installation manual included with it All wiring work must be carried out by the qualified electricians The system includes several indoor units Name each indoor unit afte...

Page 11: ...on wiring weak current Remote controller wiring weak current Caution Outside the air conditioner don t route the remote controller wiring and transmission wiring together with other electrical wiring...

Page 12: ...or 2 remote controllers control 1 indoor unit Power supply Single phase 220 240V 50Hz L N H Outdoor unit i I Note No need to input the indoor unit address during group control L_ _ J Afterturning on...

Page 13: ...anel s connecting wires refer to the panel installation manual for derailed information 11 Decorative panel installation for test run To perform test run without installing the decorative panel read t...

Page 14: ...13...

Page 15: ...DAIKIN VRV Model Ceiling Mounted Cassette Single Flow Type FXKQ32AV16 FXKQ40AV16 FXKQ50AV16 FXKQ63AV16 OPERATION MANUAL...

Page 16: ...injury or property damage or even serious injury under some circumstances After reading keep this manual in a convenient place so that you can refer to it whenever necessary If the equipment is trans...

Page 17: ...ner in places with excessive oily smoke such as cooking rooms or in places with flammable gas corrosive gas or metal dust Using the air conditioner in such places may cause a fire or air conditioner f...

Page 18: ...ury or electric shocks To avoid injury do not touch the air inlet or aluminum fins of the air conditioner Do not place objects in direct proximity of the outdoor unit and do not let leaves and other d...

Page 19: ...not clean the product with organic solvents such as paint thinner Using the organic solvents may result in cracks electric shocks or fire hazards Ask the technical expertise to install the optional ac...

Page 20: ...leakage electric shocks and fire hazards The refrigerant within the air conditioner is safe Generally it is unlikely to leak However in case of a refrigerant leakage in the rooms it may generate harmf...

Page 21: ...d by refrigerant flow in the air conditioner During cooling or heating operation this sound can be heard while discharging the water gathered in the air conditioner through the drain pump The sound ca...

Page 22: ...rate and direction set properly Does the voltage comply with the instructions of the operation installation manual Is the air filter dirty Are the indoor and outdoor unit s suction inlet and air outle...

Reviews: