Transmission 

and Power 

wiring must be 

as  Figure 20. 

Earth wire from field 

Figure 20 

• Power wiring and earth wires

Open the electrical component box cover.
Then, lead the electric wires into the air conditioner though

electric-wire-through part and connect them to the terminal

block 3P. In addition, be sure to gather the wiring protective

sleeves into the electrical component box.

• Remote controller wiring and transmission wiring

Lead the electric wires into the air conditioner though

electric-wire-through part and connect them to the

terminal block 6P.  In addition,  be sure to gather the wiring

protective sleeves into the electrical component box.

[Wiring example] 

-& 

Caution----------------

• The electric wires must be passed through the electric­

wire-through part.

• Wrap the sealing material @) to the strong current and weak

current electric wires as the figure below.

System 1 

Power supply 

Single phase 

~220-240V 

50Hz 

L  N 

[Sealing  material's wrapping  method] 

1  remote controller controls 1  indoor unit 

Power supply 

Single phase 

~ 220-240V 

50Hz 

Power supply 

Single phase 

~ 220-240V 

50Hz 

Remote controller 

(optional accessory) 

Remote controller 

(optional accessory) 

Remote controller 

(optional accessory) 

Figure 21 

System 2  Group control or 2 remote controllers control 

1  indoor unit 

Power supply 

Single phase 

~220-240V 

50Hz 

L  N 

Outdoor unit 

i  - -

""  �  I  Note: No need to input the indoor unit address during group control. 

L_  _  J 

(After turning on the power supply, it will be set automatically.) 

Remote controller  For group control For two

(optional accessory)  remote controllers' control

Remote controller Remote controller 

,(optional accessory)1 

2 remote controllers 

Figure 22 

System 3  When equipped with a BS unit 

Power supply 

control 1  unit 

Single phase 

~ 220-240V 

Outdoor unit 

BS unit 

50Hz 

I  - - --, 

Remote controller 

(optional accessory) 

Figure 23 

[Note] 

1. If there is no need to install the earth leakage circuit

breaker: mount the line breaker or load switch with fuse.

If there is a need to install the earth leakage circuit

breaker: mount the earth leakage circuit breaker

compatible with appliances for grounding,  over load

and short circuit protection.

2. The remote controller wiring (P1  and P2) and

transmission wiring (F1  and F2) is of no polarity.

<Precautions to power wiring connection> 

• Never connect two wires of different size to the same power

supply terminal. (Loose electric wire connection may cause

abnormal heating.)

• When connecting to the terminal blocks, use the circular

terminal with insulation sleeve.  If not available,  connect

the wires of the same size to the sides respectively as

shown in the figure.

Insulation sleeve 

Circular terminal 

Power wiring 

11 

Summary of Contents for VRV FXKQ32AV16

Page 1: ...NUAL VRV Model Ceiling Mounted Cassette Single Flow Type FXKQ32AV16 FXKQ40AV16 FXKQS0AV16 FXKQ63AV16 CAREFULLY READ THESE INSTRUCTIONS BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE...

Page 2: ...rain piping installation 8 9 Electrical wiring work 9 9 1 Overview 9 9 2 Specifications of the standard electric wires 9 9 3 Electrical characteristics 10 10 Wiring example 10 10 1 How to connect powe...

Page 3: ...as well as this manual 2 An insufficient power supply capacity or improper electrical operation may lead to electric shocks or fire hazards indoor unit as far away from fluorescent lamps as possible...

Page 4: ...ince R41 0A is a mixed refrigerant the required additional refrigerant must be charged in its liquid state If the system is charged with refrigerant in its gaseous state due to composition change the...

Page 5: ...perate normally or nameplate of the unit with parts burnt out Are the wiring and piping The unit doesn t connected properly operate normally or with parts burnt out Is the unit earthed safely Due to l...

Page 6: ...instances 2 Perform installation with a lifting screw Study if the ceiling is strong enough to hold the weight of the indoor unit If the ceiling is not strong enough reinforce the ceiling in advance R...

Page 7: ...quipped with a built in drain pump and float switch Adjust the levelness using a level meter or polyethylene pipe filled with water Levelness of unit should not exceed 0 5 deg down at opposite side of...

Page 8: ...ommended and only use in emergency It s necessary to use the torque wrench to install the units If you have to install the units but without the torque wrench then perform installation based on follow...

Page 9: ...in stagnates in the drain piping the piping may be clogged To prevent the piping from bending and sagging down secure them every 1 1 5m using slings Use the accessory drain hose CD and metal clip The...

Page 10: ...efer to the Remote controller installation manual included with it All wiring work must be carried out by the qualified electricians The system includes several indoor units Name each indoor unit afte...

Page 11: ...on wiring weak current Remote controller wiring weak current Caution Outside the air conditioner don t route the remote controller wiring and transmission wiring together with other electrical wiring...

Page 12: ...or 2 remote controllers control 1 indoor unit Power supply Single phase 220 240V 50Hz L N H Outdoor unit i I Note No need to input the indoor unit address during group control L_ _ J Afterturning on...

Page 13: ...anel s connecting wires refer to the panel installation manual for derailed information 11 Decorative panel installation for test run To perform test run without installing the decorative panel read t...

Page 14: ...13...

Page 15: ...DAIKIN VRV Model Ceiling Mounted Cassette Single Flow Type FXKQ32AV16 FXKQ40AV16 FXKQ50AV16 FXKQ63AV16 OPERATION MANUAL...

Page 16: ...injury or property damage or even serious injury under some circumstances After reading keep this manual in a convenient place so that you can refer to it whenever necessary If the equipment is trans...

Page 17: ...ner in places with excessive oily smoke such as cooking rooms or in places with flammable gas corrosive gas or metal dust Using the air conditioner in such places may cause a fire or air conditioner f...

Page 18: ...ury or electric shocks To avoid injury do not touch the air inlet or aluminum fins of the air conditioner Do not place objects in direct proximity of the outdoor unit and do not let leaves and other d...

Page 19: ...not clean the product with organic solvents such as paint thinner Using the organic solvents may result in cracks electric shocks or fire hazards Ask the technical expertise to install the optional ac...

Page 20: ...leakage electric shocks and fire hazards The refrigerant within the air conditioner is safe Generally it is unlikely to leak However in case of a refrigerant leakage in the rooms it may generate harmf...

Page 21: ...d by refrigerant flow in the air conditioner During cooling or heating operation this sound can be heard while discharging the water gathered in the air conditioner through the drain pump The sound ca...

Page 22: ...rate and direction set properly Does the voltage comply with the instructions of the operation installation manual Is the air filter dirty Are the indoor and outdoor unit s suction inlet and air outle...

Reviews: