70
RXYQ-AATJA / RXYQ-AAYDA
EDUS342305-D
Capacity table of indoor unit
Cooling Capacity
Model
Capacity
indication
Indoor air temp.°FWB (Te: 43°F (6°C))
61
64
67
70
72
75
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
MBH
MBH
MBH
MBH
MBH
MBH
MBH
MBH
MBH
MBH
MBH
MBH
FXMQ07PBVJU
07
5.7
5.5
6.4
5.9
7.2
6.1
7.3
6.5
7.4
5.8
7.6
5.8
FXMQ09PBVJU
09
7.5
6.9
8.5
7.3
9.5
7.8
9.7
8.1
9.8
7.1
10.0
7.2
FXMQ12PBVJU
12
9.5
8.5
10.7
9.1
12.0
9.7
12.2
10.0
12.4
9.2
12.6
9.2
FXMQ15PBVJU
15
11.2
10.2
12.7
10.7
14.2
11.4
14.5
11.6
14.7
11.5
14.9
9.6
FXMQ18PBVJU
18
14.2
13.9
16.1
14.7
18.0
15.6
18.4
16.1
18.6
14.6
18.9
12.1
FXMQ24PBVJU
24
19.0
16.5
21.5
17.7
24.0
18.8
24.5
19.2
24.8
17.9
25.3
20.1
FXMQ30PBVJU
30
23.7
20.8
26.8
22.3
30.0
23.8
30.6
24.4
31.0
22.5
31.6
22.5
FXMQ36PBVJU
36
28.4
25.0
32.2
26.9
36.0
28.8
36.7
30.0
37.2
27.7
37.9
27.7
FXMQ48PBVJU
48
37.9
31.3
43.0
33.6
48.0
35.8
49.0
36.9
49.6
34.7
50.5
33.2
FXMQ54PBVJU
54
42.6
35.2
48.3
37.8
54.0
40.3
55.1
41.5
55.8
39.0
56.8
37.4
TC: Total capacity: MBH
SHC: Sensible heat capacity: MBH
Selection results of indoor units
Room A
Room B
Room C
Room D
Room E
Room F
Room G
Room H
Max. heat load
(MBH)
36.1
36.4
17.3
17.3
30.9
30.8
14.1
14.1
Selected IDU
FXMQ48PBVJU FXMQ48PBVJU FXMQ18PBVJU FXMQ18PBVJU FXMQ36PBVJU FXMQ36PBVJU FXMQ15PBVJU FXMQ15PBVJU
Corrected TC
(MBH)
48.0
48.0
18.0
18.0
36.0
36.0
14.2
14.2
*
In case of selection based on Total Heat Load and Sensible Heat Load, select indoor units which satisfy not only the Total Heat Load but also
the Sensible Heat Load of each room. The sensible heat capacity of indoor units is to be corrected for indoor air temperature. If the design
temperature of indoor air falls between temperatures listed in table, calculate sensible heat capacity by using the bypass factor calculated by
interpolation for each indoor air temperature.
[3] Selection of outdoor unit
[3] –1 Define the required total heat load from the indoor units to the outdoor unit
Define the required total heat load (A) based on (1) the sum of the peak load of each room or (2) the system peak load.
In this example, select an outdoor unit by (2).
Therefore, (A) = 173.0 MBH
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 2: ......
Page 41: ...39 RXYQ AATJA RXYQ AAYDA EDUS342305 D 10 Center of Gravity RXYQ72AATJA RXYQ72AAYDA 4D145101...
Page 47: ...45 RXYQ AATJA RXYQ AAYDA EDUS342305 D 12 Piping Diagrams RXYQ72AATJA RXYQ72AAYDA 3D144830A...
Page 54: ...52 RXYQ AATJA RXYQ AAYDA EDUS342305 D 14 Field Wiring RXYQ72 240AATJA RXYQ72 240AAYDA 3D144741...
Page 55: ...53 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ264 480AATJA RXYQ264 480AAYDA 3D144742...
Page 57: ...55 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ264 480AATJA 3D144752...
Page 58: ...56 RXYQ AATJA RXYQ AAYDA EDUS342305 D 15 2 RXYQ AAYDA RXYQ72 240AAYDA 3D144753...
Page 59: ...57 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ264 480AAYDA 3D144754...
Page 62: ...60 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ96AATJA AAYDA 4D144744...
Page 63: ...61 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ120AATJA AAYDA 4D144745...
Page 64: ...62 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ144AATJA AAYDA 4D144746...
Page 65: ...63 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ168AATJA AAYDA 4D144747...
Page 66: ...64 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ192AATJA AAYDA 4D144748...
Page 67: ...65 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ216AATJA AAYDA 4D144749...
Page 68: ...66 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ240AATJA AAYDA 4D144750...
Page 77: ...75 RXYQ AATJA RXYQ AAYDA EDUS342305 D 2P714094C...
Page 78: ...76 RXYQ AATJA RXYQ AAYDA EDUS342305 D 2P714094C...
Page 79: ...77 RXYQ AATJA RXYQ AAYDA EDUS342305 D 2P714094C...
Page 80: ...78 RXYQ AATJA RXYQ AAYDA EDUS342305 D 2P714094C...
Page 81: ...79 RXYQ AATJA RXYQ AAYDA EDUS342305 D 2P714094C...
Page 83: ...81 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ96 168AATJA AAYDA 3P714085A...
Page 84: ...82 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ192 240AATJA AAYDA 3P714074A...
Page 95: ......