background image

10

RXYQ-AATJA / RXYQ-AAYDA 

EDUS342305-D

4.  External Appearance

4.1  Outdoor Units

Single Outdoor Units

RXYQ72AATJA

RXYQ72AAYDA

6 ton

RXYQ96AATJA    RXYQ120AATJA

RXYQ144AATJA  RXYQ168AATJA

RXYQ96AAYDA    RXYQ120AAYDA

RXYQ144AAYDA  RXYQ168AAYDA

8, 10, 12, 14 ton

RXYQ192AATJA  RXYQ216AATJA  RXYQ240AATJA

RXYQ192AAYDA  RXYQ216AAYDA  RXYQ240AAYDA

16, 18, 20 ton

Summary of Contents for VRV EMERION RXYQ-AATJA

Page 1: ...RXYQ AATJA 208 230 V RXYQ AAYDA 460 V Design Manual EDUS342305 D 202303 Engineering Data Heat Pump 60 Hz...

Page 2: ......

Page 3: ...nnectable Indoor Units 16 7 Specifications 17 7 1 RXYQ AATJA 17 7 2 RXYQ AAYDA 24 8 Dimensions 31 9 Service Space 37 10 Center of Gravity 39 11 Foundation Drawing 42 12 Piping Diagrams 45 13 Wiring Di...

Page 4: ...tting 86 22 1 FXFQ T 86 22 2 FXZQ TB 86 22 3 FXUQ PA 86 22 4 FXEQ P 86 22 5 FXDQ M 87 22 6 FXSQ TB 87 22 7 FXMQ TB 87 22 8 FXMQ M 87 22 9 FXHQ M 88 22 10 FXAQ P 88 22 11 FXLQ M FXNQ M 88 22 12 FXTQ TA...

Page 5: ...nt floor heating or hydronic heating Auto charge function facilitates ease of installation Hot gas defrost circuit allows installation without base pan heater Service window provides quick access to m...

Page 6: ...nor revision Power supply symbol TJ 3 phase 208 230 V 60 Hz YD 3 phase 460 V 60 Hz Indicates minor change category Indicates major design category Capacity indication in cooling Refrigerant Q R410A In...

Page 7: ...h 60 60 000 Btu h 12 12 000 Btu h 36 36 000 Btu h 72 72 000 Btu h 15 15 000 Btu h 42 42 000 Btu h 96 96 000 Btu h Refrigerant Q R410A Shape F Ceiling mounted cassette Round flow with sensing Z VISTA 2...

Page 8: ...000 Btu h 72 72 000 Btu h 96 96 000 Btu h Refrigerant Q R410A Shape M Ceiling mounted duct Series category X Inverter Unit category F Indoor unit for air cooled type Outdoor Air Processing Unit U G 3...

Page 9: ...AATJA RXYQ288AATJA RXYQ312AATJA RXYQ336AATJA RXYQ360AATJA Outdoor unit 1 RXYQ120AATJA RXYQ144AATJA RXYQ144AATJA RXYQ168AATJA RXYQ168AATJA Outdoor unit 2 RXYQ144AATJA RXYQ144AATJA RXYQ168AATJA RXYQ168A...

Page 10: ...blow cassette type FXEQ 07P 09P 12P 15P 18P 24P Slim ceiling mounted duct type FXDQ 07M 09M 12M 18M 24M MSP concealed ducted unit FXSQ 05TB 07TB 09TB 12TB 15TB 18TB 24TB 30TB 36TB 48TB 54TB Ceiling mo...

Page 11: ...essing Unit Series Model name Power supply Standard FXMQ 48MF 72MF 96MF VJU VJ 1 phase 208 230 V 60 Hz U VJU Standard symbol Energy Recovery Ventilator VAM series Series Model name Power supply Standa...

Page 12: ...oor Units Single Outdoor Units RXYQ72AATJA RXYQ72AAYDA 6 ton RXYQ96AATJA RXYQ120AATJA RXYQ144AATJA RXYQ168AATJA RXYQ96AAYDA RXYQ120AAYDA RXYQ144AAYDA RXYQ168AAYDA 8 10 12 14 ton RXYQ192AATJA RXYQ216AA...

Page 13: ...ATJA RXYQ312AATJA RXYQ336AATJA RXYQ264AAYDA RXYQ288AAYDA RXYQ312AAYDA RXYQ336AAYDA 22 24 26 28 ton RXYQ360AATJA RXYQ360AAYDA 30 ton RXYQ384AATJA RXYQ408AATJA RXYQ432AATJA RXYQ456AATJA RXYQ480AATJA RXY...

Page 14: ...YFQ60C3W1W Shown with BYFQ60C3W1S Ceiling suspended type FXHQ M 4 way blow ceiling suspended type FXUQ PA Wall mounted type FXAQ P One way blow cassette type FXEQ P Floor standing type FXLQ M Slim cei...

Page 15: ...13 RXYQ AATJA RXYQ AAYDA EDUS342305 D 4 3 Air Treatment Equipment Outdoor air processing unit FXMQ MF Energy recovery ventilator VAM series VAM G...

Page 16: ...YQ240AATJA RXYQ240AAYDA 20 25 0 70 3 1 l RXYQ264AATJA RXYQ264AAYDA 22 27 5 77 4 2 l l RXYQ288AATJA RXYQ288AAYDA 24 30 0 84 4 2 ll RXYQ312AATJA RXYQ312AAYDA 26 32 5 91 4 2 l l RXYQ336AATJA RXYQ336AAYDA...

Page 17: ...it 6 14 ton 50 200 1 180 1 200 1 100 100 2 130 3 16 20 ton 180 1 180 1 Double outdoor units 160 1 160 1 Note 1 If the operational capacity of indoor units is more than 130 low airflow operation is enf...

Page 18: ...216 RXYQ216AATJA RXYQ216AAYDA 108 to 280 432 37 20 240 RXYQ240AATJA RXYQ240AAYDA 120 to 312 480 41 Double outdoor units 22 264 RXYQ264AATJA RXYQ264AAYDA 132 to 343 528 45 24 288 RXYQ288AATJA RXYQ288A...

Page 19: ...53 9 8 965 253 9 Direct driv e Direct driv e Direct driv e 3 8 9 5 C1220T 3 8 9 5 C1220T 1 2 12 7 C1220T brazing connection brazing connection brazing connection 3 4 19 1 C1220T 7 8 22 2 C1220T 1 1 8...

Page 20: ...3 13 665 386 9 Direct driv e Direct driv e Direct driv e 1 2 12 7 C1220T 5 8 15 9 C1220T 5 8 15 9 C1220T brazing connection brazing connection brazing connection 1 1 8 28 6 C1220T 1 1 8 28 6 C1220T 1...

Page 21: ...low rate cf m m min 14 510 410 8 14 510 410 8 Direct driv e Direct driv e 5 8 15 9 C1220T 5 8 15 9 C1220T brazing connection brazing connection 1 1 8 28 6 C1220T 1 3 8 34 9 C1220T brazing connection b...

Page 22: ...0 65 2 0 65 2 0 65 2 0 65 2 0 65 2 Airf low rate cf m m min 8 965 253 9 9 935 281 3 9 935 281 3 9 935 281 3 9 935 281 3 9 935 281 3 Direct driv e Direct driv e Direct driv e 3 4 19 1 C1220T 3 4 19 1 C...

Page 23: ...0 65 2 0 65 2 0 95 2 0 95 2 0 95 2 Airf low rate cf m m min 9 935 281 3 9 935 281 3 9 935 281 3 13 665 386 9 13 665 386 9 13 665 386 9 Direct driv e Direct driv e Direct driv e 3 4 19 1 C1220T 3 4 19...

Page 24: ...0 95 2 0 95 2 0 95 2 0 95 2 0 95 2 0 95 2 Airf low rate cf m m min 13 665 386 9 14 510 410 8 14 510 410 8 14 510 410 8 14 510 410 8 14 510 410 8 Direct driv e Direct driv e Direct driv e 3 4 19 1 C12...

Page 25: ...peller f an Motor output kW 0 95 2 0 95 2 Airf low rate cf m m min 14 510 410 8 14 510 410 8 Direct driv e 3 4 19 1 C1220T brazing connection 1 5 8 41 3 C1220T brazing connection lbs kg 904 410 904 41...

Page 26: ...9 Direct driv e Direct driv e Direct driv e 3 8 9 5 C1220T 3 8 9 5 C1220T 1 2 12 7 C1220T brazing connection brazing connection brazing connection 3 4 19 1 C1220T 7 8 22 2 C1220T 1 1 8 28 6 C1220T br...

Page 27: ...65 386 9 Direct driv e Direct driv e Direct driv e 1 2 12 7 C1220T 5 8 15 9 C1220T 5 8 15 9 C1220T brazing connection brazing connection brazing connection 1 1 8 28 6 C1220T 1 1 8 28 6 C1220T 1 1 8 28...

Page 28: ...rate cf m m min 14 510 410 8 14 510 410 8 Direct driv e Direct driv e 5 8 15 9 C1220T 5 8 15 9 C1220T brazing connection brazing connection 1 1 8 28 6 C1220T 1 3 8 34 9 C1220T brazing connection brazi...

Page 29: ...0 65 2 0 65 2 0 65 2 0 65 2 Airf low rate cf m m min 8 965 253 9 9 935 281 3 9 935 281 3 9 935 281 3 9 935 281 3 9 935 281 3 Direct driv e Direct driv e Direct driv e 3 4 19 1 C1220T 3 4 19 1 C1220T...

Page 30: ...0 65 2 0 95 2 0 95 2 0 95 2 Airf low rate cf m m min 9 935 281 3 9 935 281 3 9 935 281 3 13 665 386 9 13 665 386 9 13 665 386 9 Direct driv e Direct driv e Direct driv e 3 4 19 1 C1220T 3 4 19 1 C122...

Page 31: ...2 0 95 2 0 95 2 0 95 2 0 95 2 0 95 2 Airf low rate cf m m min 13 665 386 9 14 510 410 8 14 510 410 8 14 510 410 8 14 510 410 8 14 510 410 8 Direct driv e Direct driv e Direct driv e 3 4 19 1 C1220T 3...

Page 32: ...ller f an Motor output kW 0 95 2 0 95 2 Airf low rate cf m m min 14 510 410 8 14 510 410 8 Direct driv e 3 4 19 1 C1220T brazing connection 1 5 8 41 3 C1220T brazing connection lbs kg 915 415 915 415...

Page 33: ...g connection method front and bottom sides see the installation manual 2 Gas pipe 1 Brazing connection Liquid pipe 3 8 Brazing connection 3 Refer to Florida Miami Dade Wind Code for anchor and tie dow...

Page 34: ...connection method front and bottom sides see the installation manual 2 Gas pipe Liquid pipe 1 2 Brazing connection 3 Refer to Florida Miami Dade Wind Code for anchor and tie down cable requirements in...

Page 35: ...A Notes 1 For piping connection method front and bottom sides see the installation manual 2 Gas pipe 1 1 8 Brazing connection Liquid pipe 5 8 Brazing connection 3 Refer to Florida Miami Dade Wind Code...

Page 36: ...efer to Florida Miami Dade Wind Code for anchor and tie down cable requirements in case of compliance with this code is required in a project 6 It is not mandatory but recommended to leave 710mm dista...

Page 37: ...wing figure 3 When installing the units the most appropriate pattern should be selected from Installation and repair space drawing in order to obtain the best fit in the space available always bearing...

Page 38: ...de service spaces respectively as shown in the following figure 3 When installing the units the most appropriate pattern should be selected from Installation and repair space drawing in order to obtai...

Page 39: ...ould be added to the front and suction side service spaces respectively as shown in the following figure 3 When installing the units the most appropriate pattern should be selected from Installation a...

Page 40: ...added to the front and suction side service spaces respectively as shown in the following figure 3 When installing the units the most appropriate pattern should be selected from Installation and repai...

Page 41: ...39 RXYQ AATJA RXYQ AAYDA EDUS342305 D 10 Center of Gravity RXYQ72AATJA RXYQ72AAYDA 4D145101...

Page 42: ...40 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ96AATJA RXYQ120AATJA RXYQ144AATJA RXYQ168AATJA RXYQ96AAYDA RXYQ120AAYDA RXYQ144AAYDA RXYQ168AAYDA 4D145100...

Page 43: ...41 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ192AATJA RXYQ216AATJA RXYQ240AATJA RXYQ192AAYDA RXYQ216AAYDA RXYQ240AAYDA 4D145059...

Page 44: ...ain water from the equipment installation area Notes 2 The surface shall be finished with mortar The corner edges shall be chamfered 3 When the foundation is built on a concrete floor rubble is not ne...

Page 45: ...foundation to thoroughly drain water from the equipment installation area Notes 2 The surface shall be finished with mortar The corner edges shall be chamfered 3 When the foundation is built on a con...

Page 46: ...to thoroughly drain water from the equipment installation area Notes 2 The surface shall be finished with mortar The corner edges shall be chamfered 3 When the foundation is built on a concrete floor...

Page 47: ...45 RXYQ AATJA RXYQ AAYDA EDUS342305 D 12 Piping Diagrams RXYQ72AATJA RXYQ72AAYDA 3D144830A...

Page 48: ...46 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ96AATJA RXYQ120AATJA RXYQ144AATJA RXYQ168AATJA RXYQ96AAYDA RXYQ120AAYDA RXYQ144AAYDA RXYQ168AAYDA 3D144828A...

Page 49: ...47 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ192AATJA RXYQ216AATJA RXYQ240AATJA RXYQ192AAYDA RXYQ216AAYDA RXYQ240AAYDA 3D143019A...

Page 50: ...TO INDOOR OUTDOOR TRANSMISSION F1 F2 OUTDOOR OUTDOOR TRANSMISSION F1 F2 OUTDOOR MULTI TRANSMISSION Q1 Q2 REFER TO THE INSTALLATION MANUAL 5 HOW TO USE BS1 3 SWITCH REFER TO SERVICE PRECAUTIONS LABEL...

Page 51: ...AGNETIC RELAY A1P X1M TERMINAL BLOCK POWER SUPPLY K3R MAGNETIC RELAY A3P A6P X1M TERMINAL BLOCK CONTROL A1P L1R L2R REACTOR X2M TERMINAL BLOCK RELAY M1C M2C MOTOR COMPRESSOR Y1E ELEC EXP VALVE MAIN M1...

Page 52: ...NG TO INDOOR OUTDOOR TRANSMISSION F1 F2 OUTDOOR OUTDOOR TRANSMISSION F1 F2 OUTDOOR MULTI TRANSMISSION Q1 Q2 REFER TO THE INSTALLATION MANUAL 5 HOW TO USE BS1 3 SWITCH REFER TO SERVICE PRECAUTIONS LABE...

Page 53: ...2R REACTOR X1M TERMINAL BLOCK CONTROL A1P M1C M2C MOTOR COMPRESSOR X2M TERMINAL BLOCK RELAY M1F M2F MOTOR FAN Y1E ELEC EXP VALVE MAIN PS SWITCHING POWER SUPPLY A1P A3P A6P A8P Y2E ELEC EXP VALVE REFRI...

Page 54: ...52 RXYQ AATJA RXYQ AAYDA EDUS342305 D 14 Field Wiring RXYQ72 240AATJA RXYQ72 240AAYDA 3D144741...

Page 55: ...53 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ264 480AATJA RXYQ264 480AAYDA 3D144742...

Page 56: ...54 RXYQ AATJA RXYQ AAYDA EDUS342305 D 15 Electrical Characteristics 15 1 RXYQ AATJA RXYQ72 240AATJA 3D144751...

Page 57: ...55 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ264 480AATJA 3D144752...

Page 58: ...56 RXYQ AATJA RXYQ AAYDA EDUS342305 D 15 2 RXYQ AAYDA RXYQ72 240AAYDA 3D144753...

Page 59: ...57 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ264 480AAYDA 3D144754...

Page 60: ...58 RXYQ AATJA RXYQ AAYDA EDUS342305 D 16 Operation Limits RXYQ72 480AATJA RXYQ72 480AAYDA 3D134600A...

Page 61: ...59 RXYQ AATJA RXYQ AAYDA EDUS342305 D 17 Sound Levels Reference Data RXYQ72AATJA AAYDA 4D144743...

Page 62: ...60 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ96AATJA AAYDA 4D144744...

Page 63: ...61 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ120AATJA AAYDA 4D144745...

Page 64: ...62 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ144AATJA AAYDA 4D144746...

Page 65: ...63 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ168AATJA AAYDA 4D144747...

Page 66: ...64 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ192AATJA AAYDA 4D144748...

Page 67: ...65 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ216AATJA AAYDA 4D144749...

Page 68: ...66 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ240AATJA AAYDA 4D144750...

Page 69: ...branch 2 This reducer pipe kit is required for RXYQ264 480A models REFNET joint kit at the first branch from the outdoor units KHRP26A33T9 KHRP26A33TA KHRP26M72TU9 KHRP26M72TUA KHRP26M73TU9 KHRP26M73T...

Page 70: ...of the peak load of each room Define required total heat load to outdoor unit Indoor unit capacity corrected for indoor air temperature WB Required heat load Safety factor for the indoor units Yes No...

Page 71: ...13 7 157 1 14 00 30 7 32 2 16 8 16 8 24 9 23 4 14 1 14 1 173 0 16 00 36 1 36 4 13 3 13 3 21 5 21 2 13 0 13 0 167 8 Total heat load MBH From the above heat load calculation the maximum heat load for th...

Page 72: ...5 55 8 39 0 56 8 37 4 TC Total capacity MBH SHC Sensible heat capacity MBH Selection results of indoor units Room A Room B Room C Room D Room E Room F Room G Room H Max heat load MBH 36 1 36 4 17 3 1...

Page 73: ...ted Duct Type Middle and High Static Pressure FXMQ 07PB 09PB 12PB 15PB 18PB 24PB 30PB 36PB 48PB 54PB VJU Calculate the total CI of the indoor units Total CI 15 2 18 2 36 2 48 2 234 2 Provisionally sel...

Page 74: ...unit calculate the capacity B corrected for outdoor air temperature indoor air temperature and connection ratio In case the outdoor air temperature the indoor air temperature or the connection ratio f...

Page 75: ...actor per feet of piping 5 F 14 F 23 F 32 F 41 F 50 F 59 F 68 F 0 328 0 305 0 282 0 256 0 233 0 210 0 187 0 161 41 F 0 000 50 F 0 000 59 F 0 013 68 F 0 030 77 F 0 046 86 F 4 0 072 2 93 F 3 R 95 F 5 0...

Page 76: ...74 RXYQ AATJA RXYQ AAYDA EDUS342305 D 20 Caution Label 20 1 Cautions on Service RXYQ AATJA AAYDA 2P714094C...

Page 77: ...75 RXYQ AATJA RXYQ AAYDA EDUS342305 D 2P714094C...

Page 78: ...76 RXYQ AATJA RXYQ AAYDA EDUS342305 D 2P714094C...

Page 79: ...77 RXYQ AATJA RXYQ AAYDA EDUS342305 D 2P714094C...

Page 80: ...78 RXYQ AATJA RXYQ AAYDA EDUS342305 D 2P714094C...

Page 81: ...79 RXYQ AATJA RXYQ AAYDA EDUS342305 D 2P714094C...

Page 82: ...80 RXYQ AATJA RXYQ AAYDA EDUS342305 D 20 2 Collective Indications Label RXYQ72AATJA AAYDA 3P714062A...

Page 83: ...81 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ96 168AATJA AAYDA 3P714085A...

Page 84: ...82 RXYQ AATJA RXYQ AAYDA EDUS342305 D RXYQ192 240AATJA AAYDA 3P714074A...

Page 85: ...ceeded in the unlikely event of major leak in the system and this in accordance to the local applicable regulations and standards Maximum concentration level The maximum charge of refrigerant and the...

Page 86: ...facility is divided into 2 entirely independent refrigerant systems then use the amount of refrigerant with which each separate system is charged Step 2 Calculate the smallest room volume ft m In cas...

Page 87: ...nstalled If the result of the above calculation exceeds the maximum concentration level then make similar calculations for the second then third smallest room and so until the result falls short of th...

Page 88: ...board fuse 250 V 3 15 A 250 V 3 15 A 250 V 3 15 A 250 V 3 15 A 250 V 3 15 A 250 V 3 15 A Fan motor thermal fuse F C Fan motor thermal protector F C Drain pump fuse F C C 4D137360 22 3 FXUQ PA Model FX...

Page 89: ...48TBVJU FXSQ54TBVJU Printed circuit board fuse 250 V 3 15 A 250 V 3 15 A 250 V 3 15 A 250 V 3 15 A 250 V 3 15 A Printed circuit board fuse fan driver 250 V 6 3 A 250 V 6 3 A 250 V 6 3 A 250 V 6 3 A 25...

Page 90: ...ON 248 120 or less OFF 275 18 135 10 ON 248 120 or less C 3D045646B 22 12 FXTQ TA Model FXTQ09TAVJUA FXTQ12TAVJUA FXTQ18TAVJUA FXTQ24TAVJUA FXTQ30TAVJUA Model with factory disconnect FXTQ09TAVJUD FXTQ...

Page 91: ...89 RXYQ AATJA RXYQ AAYDA EDUS342305 D Appendix 1 Introduction 90 1 1 ED Book List 90 1 2 Publication List of Engineering Data for VRV Products 91...

Page 92: ...e FXDQ M EDUS39 600A F2 MSP Concealed Ducted Unit FXSQ TB EDUS392235 F17 HSP Concealed Ducted Unit FXMQ TB EDUS392236 F4 Ceiling Mounted Duct Type FXMQ M EDUS39 900B F11 Ceiling Suspended Type FXHQ M...

Page 93: ...da Design manual EDUS371704C D Feb 2020 Capacity table EDUS371704C C 575 V REYQ TAYCA Canada Design manual EDUS371706C D Capacity table EDUS371706C C H P 208 230 V 460 V RXYQ TATJA TAYDA USA Canada De...

Page 94: ...cealed Floor Standing Type FXLQ07 24MVJU FXNQ07 24MVJU USA EDUS391502A F7 Jan 2021 Low temperature hydrobox HXY48TAVJU USA EDUS392021 F18 Sep 2020 AHU Integration Kit Re Heat EKEQDCBAV3 US USA EDUS392...

Page 95: ......

Page 96: ...or explosion Use only those parts and accessories supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessori...

Reviews: