background image

• VRV

®

 Systems • Indoor Units

141

• Indoor Units • CONCEALED CEILING UNIT • FXMQ-PVE

6

Dimensional drawing & centre of gravity

6 - 1 Dimensional drawing

FXMQ100,125P

3D060162

12 Drain hose (accessory)

O.D. ø 32 (outlet)

11 Socket (for maintenance)

VP25 (O.D. ø 32 /I.D. ø 25)

10 Hook

For M10

9

Air suction flange

8

Air discharge flange

7

Power supply connection

6

Interunit wiring connection

5

Control box (inside)

4

Ground terminal (in control box)

M4

3

Drain pipe connection

VP25 (O.D. ø 32 /I.D. ø 25)

2

Gas pipe connection

ø 15.9 flale connection

1

Liquid pipe connection

ø 9.5 flale connection

ITEM PART NAME

REMARK

40-ø 4.7 hole

(All around)

(Suspention bolt position)

Air Outlet

48-ø 4.7 hole

(All around)

or less

Air Inlet

20 - 8x12 oblong hole
(All around)

450 or mo

re

(s

ervi

ce

 space)

700 or more

(service space)

View

(From the Air Outlet)

Inspection hatch 450 or more

700 or Less

Adj

ustabl

e

(467 or m

ore)

Air outlet

Ceiling

Floor surface

30

0 or mor

e

Air Inlet
(Note 2)

(N

ot

e 4)

2500 o

r more

(A

 case wi

thout the 

ce

ilin

g)

20 - 8x12 oblong hole

(All around)

(From the air inlet)

300 or less

Fig. A

View B-1

View B-2

Inspection hatch 2

Air 

outlet

Air 

inlet

Control box

<Inspection hatch>
(Ceiling opening)

Control box

Inspection hatch

Ceiling

Inspection hatch 

Ceiling

Inspection hatch (450mmx450mm)

Inspection hatch (°450)

Control box

Control box

Control box

Inspection hatch 3

or

 more

or

 le

ss

or

 m

or

e

or more

NOTES

1

Location of MANUFACTURE’S LABEL: 
Control box surface

2

Mount the air filter at the suction side.
(Select its colorimethod (gravity method) 50% or 
more)

3

Do not locate things should not be wet under the 
indoor unit.
Dews may droop when humidity reaches over 80%, 
or a drain gets stuck, or air filters are not clean.

4

Space for Service Works

According to any one of below 1) - 3), secure a space for service works, such 
as, checking and maintenance of control box and drain pumps, etc.

1) One inspection hatch (450x450) on the control box side and a space of 

300mm or more under the unit. (Fig.A)

2) One inspection hatch (450x450) on the control box side and 2 (two) 

inspection hatches under the unit (Arrow view B-1)

3) 3 (three) inspection hatches under the unit and the control box. (Arrow view B-2)

FXMQ100,125P

3D060162

12 Drain hose (accessory)

O.D. ø 32 (outlet)

11 Socket (for maintenance)

VP25 (O.D. ø 32 /I.D. ø 25)

10 Hook

For M10

9

Air suction flange

8

Air discharge flange

7

Power supply connection

6

Interunit wiring connection

5

Control box (inside)

4

Ground terminal (in control box)

M4

3

Drain pipe connection

VP25 (O.D. ø 32 /I.D. ø 25)

2

Gas pipe connection

ø 15.9 flale connection

1

Liquid pipe connection

ø 9.5 flale connection

ITEM PART NAME

REMARK

40-ø 4.7 hole

(All around)

(Suspention bolt position)

Air Outlet

48-ø 4.7 hole

(All around)

or less

Air Inlet

20 - 8x12 oblong hole
(All around)

450 or mo

re

(s

ervi

ce

 space)

700 or more

(service space)

View

(From the Air Outlet)

Inspection hatch 450 or more

700 or Less

Adj

ustabl

e

(467 or m

ore)

Air outlet

Ceiling

Floor surface

30

0 or mor

e

Air Inlet
(Note 2)

(N

ot

e 4)

2500 o

r more

(A

 case wi

thout the 

ce

ilin

g)

20 - 8x12 oblong hole

(All around)

(From the air inlet)

300 or less

Fig. A

View B-1

View B-2

Inspection hatch 2

Air 

outlet

Air 

inlet

Control box

<Inspection hatch>
(Ceiling opening)

Control box

Inspection hatch

Ceiling

Inspection hatch 

Ceiling

Inspection hatch (450mmx450mm)

Inspection hatch (°450)

Control box

Control box

Control box

Inspection hatch 3

or

 more

or

 le

ss

or

 m

or

e

or more

NOTES

1

Location of MANUFACTURE’S LABEL: 
Control box surface

2

Mount the air filter at the suction side.
(Select its colorimethod (gravity method) 50% or 
more)

3

Do not locate things should not be wet under the 
indoor unit.
Dews may droop when humidity reaches over 80%, 
or a drain gets stuck, or air filters are not clean.

4

Space for Service Works

According to any one of below 1) - 3), secure a space for service works, such 
as, checking and maintenance of control box and drain pumps, etc.

1) One inspection hatch (450x450) on the control box side and a space of 

300mm or more under the unit. (Fig.A)

2) One inspection hatch (450x450) on the control box side and 2 (two) 

inspection hatches under the unit (Arrow view B-1)

3) 3 (three) inspection hatches under the unit and the control box. (Arrow view B-2)

FXMQ-P

3D028952

Cord oulet hole

Staple

EXPOSED BODY, EXPOSED CORD

Remote control 

• REMOTE CONTROL DIMENSIONS

• INSTALLATION METHOD

N

OTE

1

Remote control cord and staple are not attached. They are field 
supplied parts.

• Specifications of cord

For Australia

For other countries

Type

Shield wire
(insulated thickness: 1mm or more)

Vinyl cord with sheath or cable 
(insulated thickness: 1mm or more)

Size

0.75~1.25mm²

Total
length

500m

EXPOSED BODY, EMBEDDED CORD

EXPOSED BODY, EMBEDDED CODE

Remote control 

(Between 

remote control 

and control box)

Control box

Remote control 

Through hole

Conduit

Summary of Contents for VRSIII-S Series

Page 1: ...technical data Concealed ceiling unit FXMQ PVE air conditioning systems EEDEN08 204 2e...

Page 2: ...ecifications 3 2 Safety device settings 4 3 Options 4 4 Control systems 5 5 Capacity tables 6 Cooling capacity tables 6 Heating capacity tables 8 6 Dimensional drawing centre of gravity 10 Dimensional...

Page 3: ...irect drive Piping connections Liquid OD Type Flare connection Diameter mm 6 35 9 52 9 52 9 52 9 52 9 52 Gas Type Flare connection Diameter mm 12 7 15 9 15 9 15 9 15 9 15 9 Drain Diameter mm VP25 I D...

Page 4: ...mum fuse amps MFA A 16 16 16 16 16 16 Full load amps FLA A 1 1 1 3 1 4 1 8 2 3 2 7 Voltage range Minimum V 10 Maximum V 10 Notes Voltage range units are suitable for use on electrical systems where vo...

Page 5: ...443 NOTE 1 See the latest for the modification marks Model DUCT TYPE Item FXMQ40PVE FXMQ50PVE FXMQ63PVE FXMQ80PVE FXMQ100PVE FXMQ125PVE High efficiency filter 65 KAF372AA56 KAF372AA80 KAF372AA160 90 K...

Page 6: ...ensor KRCS01 1B 7 Mounting plate for adapter PCB Note 2 3 KRP4A96 8 Central remote control DCS302CA61 8 1 Electrical box with earth terminal 3 blocks KJB311AA 9 Unified on off control DSC301BA61 9 1 E...

Page 7: ...5 4 1 5 2 4 5 5 6 4 6 5 9 4 6 6 0 4 4 6 1 3 7 33 0 3 8 3 6 4 5 4 1 5 2 4 5 5 6 4 6 5 8 4 5 5 9 4 3 6 0 3 7 35 0 3 8 3 6 4 5 4 1 5 2 4 5 5 6 4 6 5 7 4 5 5 8 4 3 5 9 3 6 37 0 3 8 3 6 4 5 4 1 5 2 4 5 5...

Page 8: ...6 4 9 0 7 3 10 5 8 3 11 2 8 5 11 5 8 5 11 8 8 2 12 1 7 9 35 0 7 6 6 4 9 0 7 3 10 5 8 3 11 2 8 5 11 3 8 4 11 6 8 1 11 9 7 8 37 0 7 6 6 4 9 0 7 3 10 5 8 3 11 0 8 4 11 2 8 3 11 4 8 0 11 7 7 7 39 0 7 6 6...

Page 9: ...8 5 8 5 8 5 5 3 0 2 2 6 2 6 2 6 2 6 1 5 9 5 5 5 0 4 1 6 4 6 4 6 3 6 1 5 9 5 5 7 0 6 0 6 6 6 6 6 3 6 1 5 9 5 5 9 0 7 9 6 8 6 7 6 3 6 1 5 9 5 5 11 0 9 8 7 0 6 7 6 3 6 1 5 9 5 5 13 0 11 8 7 1 6 7 6 3 6...

Page 10: ...9 5 0 4 1 12 7 12 7 12 5 12 1 11 7 10 9 7 0 6 0 13 1 13 1 12 5 12 1 11 7 10 9 9 0 7 9 13 5 13 3 12 5 12 1 11 7 10 9 11 0 9 8 14 0 13 3 12 5 12 1 11 7 10 9 13 0 11 8 14 1 13 3 12 5 12 1 11 7 10 9 15 0...

Page 11: ...ntrol box Arrow view B 2 According to any one of below 1 3 secure a space for service works such as checking and maintenance of control box and drain pumps etc FXMQ50 63 80P 3D060161 12 Drain hose acc...

Page 12: ...M10 9 Air suction flange 8 Air discharge flange 7 Power supply connection 6 Interunit wiring connection 5 Control box inside 4 Ground terminal in control box M4 3 Drain pipe connection VP25 O D 32 I...

Page 13: ...hatch 450mmx450mm Inspection hatch 450 Control box Control box Control box Inspection hatch 3 or more or less or more or more NOTES 1 Location of MANUFACTURE S LABEL Control box surface 2 Mount the a...

Page 14: ...VRV Systems Indoor Units 143 Indoor Units CONCEALED CEILING UNIT FXMQ PVE 6 Dimensional drawing centre of gravity 6 2 Centre of gravity FXMQ P 4D060438 MODEL NAME FXMQ40P FXMQ50 63 80P FXMQ100 125P...

Page 15: ...ts CONCEALED CEILING UNIT FXMQ PVE VRV Systems Indoor Units 144 7 Piping diagram FXMQ P 4D034245C Heat exchanger Fan Gas pipe connection port Liquid pipe connection port Filter Filter Electronic expan...

Page 16: ...250V R2T Thermistor liquid Wired remote control F2U Fuse T 5A 250V R3T Thermistor gas R1T Thermistor air F3U Fuse T 6 3A 250V R4T Thermistor discharge air SS1 Selector switch main sub F4U Fuse T 6 3A...

Page 17: ...hreshold hearing for continuous noise FXMQ50P Scale Air flow rate HH H L A 41 0 39 0 37 0 C 46 0 44 0 42 0 Discharge Suction 1m 2m Duct Duct 1 5m Microphone 4D060447 NOTES 1 Over All dB B G N is alrea...

Page 18: ...hreshold hearing for continuous noise FXMQ100P Scale Air flow rate HH H L A 43 0 41 0 39 0 C 49 0 46 0 44 0 Discharge Suction 1m 2m Duct Duct 1 5m Microphone 4D060449 NOTES 1 Over All dB B G N is alre...

Page 19: ...e value in this figure shows ESP in rating air flow Range of available air flow rate in HH rating EPS HH rating ESP L rating ESP HH min ESP L min ESP mmH2O mmH2O mmH2O mmH2O FXMQ80P 3D060459 External...

Page 20: ...ons are subject to change without prior notice Daikin Europe N V explicitly rejects any liability for any direct or indirect damage In the broadest sense arising from or related to the use and or inte...

Reviews: