background image

• VRV

®

 Systems • Indoor Units

139

• Indoor Units • CONCEALED CEILING UNIT • FXMQ-PVE

5

Capacity tables

5 - 2 Heating capacity tables

FXMQ-P

CA08A056

TC: Total capacity;kW – SHC: Sensible capacity;kW

Unit size

Nominal 
capacity

Outdoor air temp.

Indoor air temperature

16.0

18.0

20.0

21.0

22.0

24.0

°

CDB

°

CWB

KW

KW

KW

KW

KW

KW

100

12.5

-19.8 -20.0  7.4  7.4  7.3 7.3 7.3 7.3 
-18.8 -19.0  7.6  7.6

 

7.6  7.5

 

7.5  7.5 

-16.7 -17.0  8.0  8.0

 

8.0  8.0

 

8.0  8.0 

-14.7 -15.0  8.5  8.5

 

8.4  8.4

 

8.4  8.4 

-12.6 -13.0  8.9  8.9

 

8.9  8.9

 

8.9  8.8 

-10.5 -11.0  9.4  9.3

 

9.3  9.3

 

9.3  9.3 

-9.5 -10.0  9.6  9.6

 

9.5  9.5

 

9.5  9.5 

-8.5 -9.1  9.8  9.8

 

9.7  9.7

 

9.7  9.7 

-7.0 -7.6 10.1 10.1 10.1

 

10.1 10.1

 

10.0 

-5.0 -5.6 10.6 10.5 10.5

 

10.5 10.5

 

10.5 

-3.0 -3.7 11.0 11.0 10.9

 

10.9 10.9

 

10.9 

0.0 -0.7 11.6 11.6 11.6

 

11.6 11.6

 

10.9 

3.0 2.2 12.3 12.3 12.2

 

12.1 

11.7

 

10.9 

5.0 4.1 12.7 12.7 12.5

 

12.1 

11.7

 

10.9 

7.0 6.0 13.1

 

13.1 

12.5

 12.1

 11.7

 10.9 

9.0 7.9 13.5 13.3 12.5

 

12.1 

11.7

 

10.9 

11.0 

9.8 

14.0 

13.3 

12.5

 12.1

 11.7

 10.9 

13.0 

11.8 

14.1 

13.3 

12.5

 12.1

 11.7

 10.9 

15.0 13.7 14.1 13.3 12.5

 

12.1

 

11.7

 

10.9 

125

16.0

-19.8 -20.0  9.4  9.4 9.4 9.4 9.4 9.3 
-18.8 -19.0  9.7  9.7

 

9.7  9.7

 

9.6  9.6 

-16.7 

-17.0 

10.3 

10.3 

10.2

 10.2

 10.2

 10.2 

-14.7 

-15.0 

10.9 

10.8 

10.8

 10.8

 10.8

 10.7 

-12.6 

-13.0 

11.4 

11.4 

11.4

 11.4

 11.3

 11.3 

-10.5 

-11.0 

12.0 

12.0 

11.9

 11.9

 11.9

 11.9 

-9.5 -10.0 12.3 12.2 12.2

 

12.2 12.2

 

12.2 

-8.5 -9.1 12.5 12.5 12.5

 

12.5 12.4

 

12.4 

-7.0 -7.6 13.0 12.9 12.9

 

12.9 12.9

 

12.8 

-5.0 -5.6 13.5 13.5 13.5

 

13.4 13.4

 

13.4 

-3.0 -3.7 14.1 14.0 14.0

 

14.0 14.0

 

13.9 

0.0 -0.7 14.9 14.9 14.8

 

14.8 14.8

 

13.9 

3.0 2.2 15.7 15.7 15.7

 

15.5 

15.0

 

13.9 

5.0 4.1 16.3 16.2 16.0

 

15.5 

15.0

 

13.9 

7.0 6.0 16.8

 

16.8 

16.0

 15.5

 15.0

 13.9 

9.0 7.9 17.3 17.0 16.0

 

15.5 

15.0

 

13.9 

11.0 

9.8 

17.9 

17.0 

16.0

 15.5

 15.0

 13.9 

13.0 

11.8 

18.1 

17.0 

16.0

 15.5

 15.0

 13.9 

15.0 13.7 18.1 17.0 16.0

 

15.5

 

15.0

 

13.9 

Summary of Contents for VRSIII-S Series

Page 1: ...technical data Concealed ceiling unit FXMQ PVE air conditioning systems EEDEN08 204 2e...

Page 2: ...ecifications 3 2 Safety device settings 4 3 Options 4 4 Control systems 5 5 Capacity tables 6 Cooling capacity tables 6 Heating capacity tables 8 6 Dimensional drawing centre of gravity 10 Dimensional...

Page 3: ...irect drive Piping connections Liquid OD Type Flare connection Diameter mm 6 35 9 52 9 52 9 52 9 52 9 52 Gas Type Flare connection Diameter mm 12 7 15 9 15 9 15 9 15 9 15 9 Drain Diameter mm VP25 I D...

Page 4: ...mum fuse amps MFA A 16 16 16 16 16 16 Full load amps FLA A 1 1 1 3 1 4 1 8 2 3 2 7 Voltage range Minimum V 10 Maximum V 10 Notes Voltage range units are suitable for use on electrical systems where vo...

Page 5: ...443 NOTE 1 See the latest for the modification marks Model DUCT TYPE Item FXMQ40PVE FXMQ50PVE FXMQ63PVE FXMQ80PVE FXMQ100PVE FXMQ125PVE High efficiency filter 65 KAF372AA56 KAF372AA80 KAF372AA160 90 K...

Page 6: ...ensor KRCS01 1B 7 Mounting plate for adapter PCB Note 2 3 KRP4A96 8 Central remote control DCS302CA61 8 1 Electrical box with earth terminal 3 blocks KJB311AA 9 Unified on off control DSC301BA61 9 1 E...

Page 7: ...5 4 1 5 2 4 5 5 6 4 6 5 9 4 6 6 0 4 4 6 1 3 7 33 0 3 8 3 6 4 5 4 1 5 2 4 5 5 6 4 6 5 8 4 5 5 9 4 3 6 0 3 7 35 0 3 8 3 6 4 5 4 1 5 2 4 5 5 6 4 6 5 7 4 5 5 8 4 3 5 9 3 6 37 0 3 8 3 6 4 5 4 1 5 2 4 5 5...

Page 8: ...6 4 9 0 7 3 10 5 8 3 11 2 8 5 11 5 8 5 11 8 8 2 12 1 7 9 35 0 7 6 6 4 9 0 7 3 10 5 8 3 11 2 8 5 11 3 8 4 11 6 8 1 11 9 7 8 37 0 7 6 6 4 9 0 7 3 10 5 8 3 11 0 8 4 11 2 8 3 11 4 8 0 11 7 7 7 39 0 7 6 6...

Page 9: ...8 5 8 5 8 5 5 3 0 2 2 6 2 6 2 6 2 6 1 5 9 5 5 5 0 4 1 6 4 6 4 6 3 6 1 5 9 5 5 7 0 6 0 6 6 6 6 6 3 6 1 5 9 5 5 9 0 7 9 6 8 6 7 6 3 6 1 5 9 5 5 11 0 9 8 7 0 6 7 6 3 6 1 5 9 5 5 13 0 11 8 7 1 6 7 6 3 6...

Page 10: ...9 5 0 4 1 12 7 12 7 12 5 12 1 11 7 10 9 7 0 6 0 13 1 13 1 12 5 12 1 11 7 10 9 9 0 7 9 13 5 13 3 12 5 12 1 11 7 10 9 11 0 9 8 14 0 13 3 12 5 12 1 11 7 10 9 13 0 11 8 14 1 13 3 12 5 12 1 11 7 10 9 15 0...

Page 11: ...ntrol box Arrow view B 2 According to any one of below 1 3 secure a space for service works such as checking and maintenance of control box and drain pumps etc FXMQ50 63 80P 3D060161 12 Drain hose acc...

Page 12: ...M10 9 Air suction flange 8 Air discharge flange 7 Power supply connection 6 Interunit wiring connection 5 Control box inside 4 Ground terminal in control box M4 3 Drain pipe connection VP25 O D 32 I...

Page 13: ...hatch 450mmx450mm Inspection hatch 450 Control box Control box Control box Inspection hatch 3 or more or less or more or more NOTES 1 Location of MANUFACTURE S LABEL Control box surface 2 Mount the a...

Page 14: ...VRV Systems Indoor Units 143 Indoor Units CONCEALED CEILING UNIT FXMQ PVE 6 Dimensional drawing centre of gravity 6 2 Centre of gravity FXMQ P 4D060438 MODEL NAME FXMQ40P FXMQ50 63 80P FXMQ100 125P...

Page 15: ...ts CONCEALED CEILING UNIT FXMQ PVE VRV Systems Indoor Units 144 7 Piping diagram FXMQ P 4D034245C Heat exchanger Fan Gas pipe connection port Liquid pipe connection port Filter Filter Electronic expan...

Page 16: ...250V R2T Thermistor liquid Wired remote control F2U Fuse T 5A 250V R3T Thermistor gas R1T Thermistor air F3U Fuse T 6 3A 250V R4T Thermistor discharge air SS1 Selector switch main sub F4U Fuse T 6 3A...

Page 17: ...hreshold hearing for continuous noise FXMQ50P Scale Air flow rate HH H L A 41 0 39 0 37 0 C 46 0 44 0 42 0 Discharge Suction 1m 2m Duct Duct 1 5m Microphone 4D060447 NOTES 1 Over All dB B G N is alrea...

Page 18: ...hreshold hearing for continuous noise FXMQ100P Scale Air flow rate HH H L A 43 0 41 0 39 0 C 49 0 46 0 44 0 Discharge Suction 1m 2m Duct Duct 1 5m Microphone 4D060449 NOTES 1 Over All dB B G N is alre...

Page 19: ...e value in this figure shows ESP in rating air flow Range of available air flow rate in HH rating EPS HH rating ESP L rating ESP HH min ESP L min ESP mmH2O mmH2O mmH2O mmH2O FXMQ80P 3D060459 External...

Page 20: ...ons are subject to change without prior notice Daikin Europe N V explicitly rejects any liability for any direct or indirect damage In the broadest sense arising from or related to the use and or inte...

Reviews: