1.3.4 Electrical Installation in General
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper
conductors required, (75
°
C) recommended.
Power (kW)
Torque (Nm)
Frame
IP class
3 x 200-240V
3 x 380-480
Line
Motor
DC
connection
Control
terminals
Earth
Relay
H1
IP20
0.25-1.5
0.37-1.5
1.4
0.8
0.8
0.5
3
0.5
H2
IP20
2.2
2.2-4
1.4
0.8
0.8
0.5
3
0.5
H3
IP20
3.7
5.5-7.5
1.4
0.8
0.8
0.5
3
0.5
H4
IP20
5.5-7.5
11-15
1.2
1.2
1.2
0.5
3
0.5
H5
IP20
11
18.5-22
1.2
1.2
1.2
0.5
3
0.5
H6
IP20
15-18
30-45
4.5
4.5
-
0.5
3
0.5
H7
IP20
22-30
55
10
10
-
0.5
3
0.5
H7
IP20
-
75
14
14
-
0.5
3
0.5
H8
IP20
37-45
90
24
2
24
2
-
0.5
3
0.5
Power (kW)
Torque (Nm)
Frame
IP class
3 x 380-480
Line
Motor
DC connection
Control
terminals
Earth
Relay
I6
IP54
22-37
4.5
4.5
-
0.5
3
0.6
I7
IP54
45-55
10
10
-
0.5
3
0.6
I8
IP54
75-90
14/24
1
14/24
1
-
0.5
3
0.6
Power (kW)
Torque (Nm)
Frame
IP class
3 x 525-600
Line
Motor
DC connection
Control
terminals
Earth
Relay
H9
IP20
2.2-7.5
1.8
1.8
not
recommended
0.5
3
0.6
H10
IP20
11-15
1.8
1.8
not
recommended
0.5
3
0.6
H6
IP20
22-30
4.5
4.5
-
0.5
3
0.5
H7
IP20
45-55
10
10
-
0.5
3
0.5
H8
IP20
75-90
14/24
1
14/24
1
-
0.5
3
0.5
Table 1.2 Details of Tightening Torques
1
Cable dimensions
≤
95mm
2
2
Cable dimensions > 95mm
2
Quick Guide
HVAC Basic Drive - DAA101 Quick Guide
6
MG.18.A2.02 - VLT
®