Analog inputs
Number of analog inputs
2
Terminal number
53, 54
Terminal 53 mode
Parameter 6-19: 1 = voltage, 0 = current
Terminal 54 mode
Parameter 6-29: 1 = voltage, 0= current
Voltage level
0 - 10V
Input resistance, R
i
approx. 10k
Ω
Max. voltage
20V
Current level
0/4 to 20mA (scalable)
Input resistance, R
i
<500
Ω
Max. current
29mA
Analog output
Number of programmable analog outputs
2
Terminal number
42, 45
1)
Current range at analog output
0/4 - 20mA
Max. load to common at analog output
500
Ω
Max. voltage at analog output
17V
Accuracy on analog output
Max. error: 0.4% of full scale
Resolution on analog output
12 bit
1) Terminal 42 and 45 can also be programmed as digital outputs.
Digital output
Number of digital outputs
2
Terminal number
42, 45
1)
Voltage level at digital output
17V
Max. output current at digital output
20mA
Max. load at digital output
1k
Ω
1) Terminals 42 and 45 can also be programmed as analog output.
Control card, RS-485 serial communication
Terminal number
68 (P, TX+, RX+), 69 (N, TX-, RX-)
Terminal number
61 Common for terminals 68 and 69
Control card, 24V DC output:
Terminal number
12
Max. load enclosure frame H1-H8
80mA
Relay output
Programmable relay output
2
Relay 01 and 02
01-03 (NC), 01-02 (NO), 04-06 (NC), 04-05 (NO)
Max. terminal load (AC-1)
1)
on 01-02/04-05 (NO) (Resistive load)
250V AC, 3A
Max. terminal load (AC-15)
1)
on 01-02/04-05 (NO) (Inductive load @ cos
φ
0.4)
250V AC, 0.2A
Max. terminal load (DC-1)
1)
on 01-02/04-05 (NO) (Resistive load)
30V DC, 2A
Max. terminal load (DC-13)
1)
on 01-02/04-05 (NO) (Inductive load)
24V DC, 0.1A
Max. terminal load (AC-1)
1)
on 01-03/04-06 (NC) (Resistive load)
250V AC, 3A
Max. terminal load (AC-15)
1)
on 01-03/04-06 (NC) (Inductive load @ cos
φ
0.4)
250V AC, 0.2A
Max. terminal load (DC-1)
1)
on 01-03/04-06 (NC)
(Resistive load)
30V DC, 2A
Min. terminal load on 01-03 (NC), 01-02 (NO) 24V DC 10mA, 24V AC 20mA
Environment according to EN 60664-1
Overvoltage category III/pollution degree 2
1) IEC 60947 parts 4 and 5.
Control card, 10V DC output
Terminal number
50
Output voltage
10.5V
±
0.5V
Max. load
25mA
Quick Guide
HVAC Basic Drive - DAA101 Quick Guide
MG.18.A2.02 - VLT
®
is a registered Danfoss trademark
35
1
1