1.7.3 Mains Supply 3 x 380-480VAC
Frequency converter
P22K
P30K
P37K
P45K
P55K
P75K
P90K
Typical shaft output (kW)
22.0
30.0
37.0
45.0
55.0
75.0
90.0
Typical shaft output (hp)
30.0
40.0
50.0
60.0
70.0
100.0
125.0
IP54 frame
I6
I6
I6
I7
I7
I8
I8
Max. cable size in terminals (mains, motor) [mm
2
/AWG]
35/2
35/2
35/2
50/1
50/1
95/(3/0)
120/(4/0)
Output current
RELAY 2
130BB632.10
40
°
C ambient temperature
Continuous
(3x380-440V)[A]
44.0
61.0
73.0
90.0
106.0
147.0
177.0
Intermittent
(3x380-440V)[A]
48.4
67.1
80.3
99.0
116.6
161.7
194.7
Continuous
(3x440-480V)[A]
40.0
52.0
65.0
80.0
105.0
130.0
160.0
Intermittent
(3x440-480V)[A]
44.0
57.2
71.5
88.0
115.5
143.0
176.0
Max. input current
RELAY 2
130BB633.10
Continuous
(3x380-440V)[A]
41.8
57.0
70.3
84.2
102.9
140.3
165.6
Intermittent
(3x380-440V)[A]
46.0
62.7
77.4
92.6
113.1
154.3
182.2
Continuous
(3x440-480V)[A]
36.0
49.2
60.6
72.5
88.6
120.9
142.7
Intermittent
(3x440-480V)[A]
39.6
54.1
66.7
79.8
97.5
132.9
157.0
Max. mains fuses
Frequency converter
P22K
P30K
P37K
P45K
P55K
P75K
P90K
Estimated power loss [W], Best case/typical
1)
496
734
705
927
1075
1425
1469
Weight enclosure IP54kg]
27
27
27
45
45
65
65
Efficiency [%], Best case/Typical 1
98.0
97.8
98.3
98.3
98.3
98.3
98.5
Output current
50
°
C ambient temperature
Continuous
(3x380-440V) [A]
35.2
48.8
58.4
63.0
74.2
102.9
123.9
Intermittent
(3x380-440V) [A]
38.7
53.9
64.2
69.3
81.6
113.2
136.3
Continuous
(3x440-480V) [A]
32.0
41.6
52.0
56.0
73.5
91.0
112.0
Intermittent
(3x440-480V) [A]
35.2
45.8
57.2
61.6
80.9
100.1
123.2
Quick Guide
HVAC Basic Drive - DAA101 Quick Guide
MG.18.A2.02 - VLT
®
is a registered Danfoss trademark
31
1
1