background image

English

5

(4) Check the unit is horizontally level.

CAUTION

Use a level to make sure that the unit is level and that 
the tilt (downward slope) to the drain piping connection 
is within 1°. (Refer to Fig. 5)

(One thing to watch out for in particular is if it is installed so 
that the slope is not in the direction of the drain piping, as 
this might cause leaking.)

(5) Tighten the upper nut.

(6) Attach the accessory duct connecting flanges using 

the included screws to the outlet and intake holes 
(a total of four).

When attaching, make sure the alignment markings on the 
unit match up with the triangle on the each duct connecting 
flange. 

(Refer to Fig. 6)

6

DRAIN PIPING AND WATER SUPPLY 
WORK

(1) Install the drain piping.

Make sure the drain works properly.

In case of the direct duct connection system, 
there is negative pressure inside the unit relative to atmo-
spheric pressure when the unit is running, so be sure to 
provide drain frap on the drain outlet. (See Fig. 7-1)

CAUTION

Do not connect the drain piping directly to sewage pipes 
that smell of ammonia. The ammonia in the sewage might 
enter the indoor unit through the drain pipes and corrode 
the heat exchanger (Direct expantion coil).

Keep the drain pipe short and sloping downwards at a 
gradient of at least 1/100 to prevent air pockets from 
forming. 

(Refer to Fig. 7-2)

If converging multiple drain pipes, install according to the 
procedure shown below. (Install a drain trap for each 
indoor unit.)

CAUTION

Water accumulating in the drain piping can cause the 
drain to clog.

The diameter of the drain pipe should be greater than or 
equal to the diameter of the connecting pipe. 
(pipe size: PT3/4B)

When piping passes indoors, always insulate it all the 
way to the base of the drain socket.

In areas where freezing may occur, always take steps to 
prevent the pipes from freezing.

Make sure water doesn’t leak from the drain pipes.

Avoid bends and curves in the pipes to prevent them 
getting clogged.

If you are using central drain piping, follow the procedure 
outlined in the figure 7-2.

Select central drain pipes of proper size according to the 
capacity of the connected unit.

Make sure the tip of the drain pipes opens out into a loca-
tion where the drainage can be safely processed.

(2) After piping work is finished, check drainage flows 

smoothly.

Test the drainage by pouring around 1000cc of water into 
the drain pan through the inspection hole by removing the 
maintenance cover (10 screws) or through the outlet duct 
joint of supply air to room (SA). 

(Refer to Fig. 8)

(3) Make sure that heat insulation work is executed on the 

following 2 spots to prevent any possibility water leak-
age due to dew condensation.

• Indoor drain piping
• Drain outlet

Level

Level

Drain hole

Horizontal line

Drain hole

Dact connecting 
flange

1

or

 

less

 

1

or

 

less

 

Fig. 5

Fig. 6

Duct connecting flange marking

Screws (accessory)
(6pcs.×4, total 24pcs.)

(RA is a 

φ

3 indentation)

Duct connecting flange

Duct connecting 
flange

Unit alignment 

Attached drain hose

Bottom of unit

50 mm 

or more

50 mm 

or more

Fig. 7-1

100mm

or more

Fig. 7-2

Central drain piping 

(Install with a downward slope of at least 1/100)

Maintenance cover

Bucket

Portable pump

(Locally procured)

(Figure shows VKM-GMV1)

(Locally procured)

(Locally procured)

Duct connecting flange

Supply air to room (SA)

(accessory)

Drain piping

Drain outlet

Fig. 8

01_3P130768-1A_En.fm  Page 5  Wednesday, March 23, 2005  7:00 PM

Summary of Contents for VKM50GMV1

Page 1: ...grilles d aspiration vacuation d air avant l installation de cette unit HRV Ventilaci n con recuperaci n de calor Por favor lea cuidadosamente el manual de instalacion e instale correctamente la unid...

Page 2: ...ita ku Osaka 530 8323 Japan DAIKIN INDUSTRIES LTD EN60335 2 40 VKM50GMV1 VKM50GV1 VKM80GMV1 VKM80GV1 VKM100GMV1 VKM100GV1 DAIKIN TCF 009 KEMA 59277 KRQ ECM95 4303 3P155750 1 Yoshiaki Hirata Manager Qu...

Page 3: ...age electric shock fire or other accidents Be sure to ground Do not connect the ground wire to gas or water pipes light ning rod or a telephone ground wire Incomplete grounding may result in electric...

Page 4: ...eck the type of R410A refrigerant to be used before installing the unit Using an incorrect refrigerant will prevent normal operation of the unit For the installation of an outdoor unit refer to the in...

Page 5: ...local govern ment office or fire department for details When discharging exhaust air to a common duct the Building Standard Law requires the use of fire proof materials so attach a 2m copper plate st...

Page 6: ...nger bracket without putting force on other parts when unpacking or moving the unit As for the parts to be used for installation work be sure to use the provided accessories and specified parts desig...

Page 7: ...he diameter of the connecting pipe pipe size PT3 4B When piping passes indoors always insulate it all the way to the base of the drain socket In areas where freezing may occur always take steps to pre...

Page 8: ...nnual operating hours 10 hours day 26 days month 5 month 1 300 hours 5 Insulate all piping that passes indoors After checking that the water supply piping connections do no leak insulate them using th...

Page 9: ...sely the refrigerant piping system Do not use anti oxidants or other similar agent when braz ing the pipe joints Residue can clog the pipes and may cause breakdown of parts 8 DUCT CONNECTION Perform d...

Page 10: ...ler This system consists of multiple indoor units Mark each indoor unit as unit A unit B and be sure the terminal board wiring to the outdoor unit and BS unit are properly matched If wiring and piping...

Page 11: ...parts box and secure with the included clamping material after connecting the wires to terminal blocks Refer to Fig 17 1 17 2 Precautions when laying power supply wiring PRECAUTIONS 1 A circuit breake...

Page 12: ...entire system Connect the remote controller and transmission wiring their respective terminal blocks 10 4 Wiring for the humidity regulator locally procured VKM GMV1 series only Pass into the electri...

Page 13: ...40V 50 Hz Fuse Switch Power supply 220 240V 50 Hz F1 F2 F1 F2 L N P1 P2 F1 F2 T1 T2 Transmission wiring Outdoor unit Remote controller wiring IN D OUT D Electric parts box HRV A Outside air processing...

Page 14: ...ernal start stop input settings based on 11 FIELD SETTING AND TEST RUN 10 8 Central control If control is performed with a central device central manage ment controller etc group number needs to be se...

Page 15: ...mode to enter the local setting mode 2 Use the TEMPERATURE ADJUSTMENT button to select the desired Mode No The code display will blink 3 To make settings for individual units under group control when...

Page 16: ...for details on the external input terminal function SECOND CODE NO 04 does not function when in air condi tioner linked mode Description of setting Mode No 1 FIRST CORD NO SECOND CORD NO 01 02 03 04 0...

Page 17: ...upply solenoid valve will be heard every 3 or 4 minutes a clicking sound so listening for that clicking sound let the unit run for 30 minutes to make sure that humidifying operation is normal CAUTION...

Page 18: ...ALVE 2 FIELD WIRING 3 IN CASE USING CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTRUCTION MANUAL 4 IN CASE USING WIRING ADAPTER CONNECT IT TO THE UNIT IN ACCORDA...

Page 19: ...N BE SELECTED BY REMOTE CONTROLLER IN DETAILS REFER TO THE INSTALLATION MANUAL ATTACHED THE UNIT 6 WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE FORCED OFF OR ON OFF CONTROL OPERATION CAN BE SELECTED B...

Page 20: ...EM03A096A 0504 3P130768 1B FS HT 00_3P130768 1B_CV fm Page 2 Friday April 1 2005 8 39 AM...

Reviews: