14
English
■
■
■
■
Settings and setting numbers
NOTE)
1. The
inside the frame indicates the second code no.
set when shipped from factory.
2. The settings are applied to the entire group, but if the mode
no. inside the parentheses is selected, the settings can be
applied to individual indoor units.
However, it is only possible to check any changes made to
the settings inside the parentheses in individual mode. (For
group batch operation, the changes are made but the dis-
play remains as it was when shipped from the factory.)
3. Do not set anything not shown above. If the applicable func-
tions are not available, they will not be displayed.
4. When returning to normal mode, the remote controller is ini-
tialized, so the display might show “88.”
5. When “Filter cleaning time setting” or “Nighttime free cooling
operation setting” is changed, explain set contents to the
customer.
6. See below for details on the settings for cold areas.
– : operate at the set fan strength
In case of Independent operation
– : operate at the set fan strength
L : operate at the weak fan strength
S : Stop
Defrost operation
•
In heating operation, freezing of the outdoor unit’s coil
increases.
Heating capability decreases and the system goes into
defrost operation.
•
The remote controller will read “
” until the hot air starts
blowing.
•
It returns to the heating operation again after 6 to 8 minutes
(10 at the longest).
•
During defrost operation, the fans of the unit continues driv-
ing (factory setting).
The purpose of this is to maintain the amount of ventilation
and humidifying.
•
The change of air discharge grill’s location should be exam-
ined when the cold draft from air discharge grill is feared.
•
Though the fan can be stopped by the setting of remote
controller.
Do not stop the fan in the place where no ventilation by stop-
ping the fan may cause the influence of diffusion of air which
it is dirty and moisture into another room, or the inflow from
outside the room.
(outflow such as viruses from the sickroom, or smell leakage
from the rest room, etc.)
7. See below for details on the external input terminal function.
∗
SECOND CODE NO. “04” does not function when in air condi-
tioner linked mode.
Description of setting
Mode
No.
∗
1
FIRST
CORD
NO.
SECOND CORD NO.
01 02 03 04 05 06 07
Filter cleaning time
setting
NOTE) 5
17
(27)
0
App-
rox.
2500
hours
App-
rox.
1250
hours
No
coun-
ting
–
–
–
–
Nighttime free cooling
operation setting
(Time after air condi-
tioning is stopped.)
NOTE) 5
1
OFF
2
hours
later
4
hours
later
6
hours
later
8
hours
later
–
–
Fan speed initial
setting
4
Nor-
mal
Ultra
high
–
–
–
–
–
Direct duct connec-
tion with VRV
setting
5
Not
direct
duct
(Air
flow
set-
ting)
With
direct
duct
(fan
off)
–
Not
direct
duct
(Air
flow
set-
ting)
–
With
direct
duct
(fan
off)
–
Setting for cold areas
(Fan operation selec-
tion for heater thermo
OFF) NOTE) 6
5
Air
flow
set-
ting
Air
flow
set-
ting
–
Fan
L
–
Fan
L
–
Ventilation air flow
setting when
Nighttime free cooling
setting
17
(27)
6
High
Ult-
ra-
High
–
–
–
–
–
ON/OFF input from
Outside
(Set when ON/OFF is
to be controlled from
outside)
12
(22)
1
For-
ced
off
ON/
OFF
con-
trol
–
–
–
–
–
Power faillure
automatic reset
(Auto Restart)
12
(22)
5
No
equ-
ipp-
ed
Equ-
ipp-
ed
–
–
–
–
–
Humidification on/off
when heating thermo
is off
15
(25)
1
No Yes
–
–
–
–
–
Indication of
ventilation mode/Not
indication
18
(28)
4
Indi-
cat-
ion
No
Indi-
cat-
ion
–
–
–
–
–
Fresh up air supply/
exhaust setting
7
No
Indication
Indication
–
–
–
Supply Exhaust Supply Exhaust
External input termi-
nal function selection
(between J1 and JC)
NOTE) 7
8
Fresh-
up
Overall
alarm
–
–
–
Air flow
incre-
ase
–
KRP50-2 output
switching selection
(between 1 and 3)
9
Fan
on/off
Abno-
rmal
–
–
–
–
–
Ventilation air flow
setting
19
(29)
0
Low Low Low Low High High
Ventilation mode
setting
2
Auto-
matic
Ex-
change
By-
pass
Fresh-up operation
1A
Off
On
–
–
–
–
–
Forced fan on
43
Unit no. allocation
45
Air conditioner fan
01
02
04
06
Heating thermo off
Operation
–
–
L
L
Defrost
Stop
–
Stop
Stop
Stop
Oil return
Stop
–
Stop
Stop
Stop
Air conditioner fan
01
02
04
06
Heating thermo off
Operation
–
–
L
L
Defrost
Stop
–
–
Stop
Stop
Oil return
Stop
–
–
Stop
Stop
SECOND
CODE
NO.
Input
contact
Fan
operation
Operation
lamp
01
a
Operation
On
Fresh-up operation
02
a
Operation
On
Malfunction code “60”
is displayed
06
a
Operation
On
Fan strength up (Low to High,
High to Ultra-High)
01_3P130768-1A_En.fm Page 14 Wednesday, March 23, 2005 7:00 PM