background image

12

English

[PRECAUTIONS]

There is not need to set the indoor unit address when using 
group control. (It is automatically set when the power is turned 
on. ) However, since the HRV (outside air processing type) uses 
two remote control addresses per unit, the number of units 
which can be group controlled is as follows.

10. 6 CONTROL BY 2 REMOTE CONTROLLERS 

(Controlling 1 indoor unit by 2 remote control-
lers)

When using 2 remote controllers, one must be set to “MAIN” 
and the other to “SUB”.

MAIN / SUB CHANGEOVER

(1) Insert a 

 screw driver into the recess between the 

upper and lower part of remote controller and, working 
from the 2 positions, pry off the upper part.

(The remote controller PC board is attached to the upper 
part of remote controller.)

(2) Turn the MAIN/SUB changeover switch on one of the 

two remote controller PC boards to “S”.

(Leave the switch of the other remote controller set to “M”.)

〈〈〈〈

Wiring Method

〉 〉 〉 〉 

(See ‘‘ELECTRIC WIRING WORK’’)

(1) Remove the electric parts box lid.

(2) Add remote controller 2 (slave) to the terminal block for 

remote controller (P

1

, P

2

) in the electric parts box. 

(There is no polarity.)

[PRECAUTIONS]

Crossover wiring is needed when using group control and 
2 remote controllers at the same time.

Connect the indoor unit at the end of the crossover wire 
(P

1

, P

2

) to remote controller 2 (slave).

10. 7 COMPUTERISED CONTROL 

(FORCED OFF AND ON/OFF OPERATION)

Wire specifications and how to perform wiring
Connect the input from outside to terminals T1 and T2 of the 
terminal block for remote controller.

Actuation
The following table explains FORCED OFF and ON/OFF 
OPERATIONS in response to Input A.

How to select FORCED OFF and ON/OFF OPERATION
Enter the FORCED OFF and ON/OFF OPERATION selection 
using the local “external start/stop input” settings based on 

11  FIELD SETTING AND TEST RUN

10. 8 Central control

If control is performed with a central device (central manage-
ment controller, etc.), group number needs to be set with the 
remote controller. See the manual of each central device for 
detail.

10. 9 FRESH-UP OPERATION BY EXTERNAL INPUT 

(HRV UNIT)

PURPOSES AND FUNCTIONS

When the operation is interlocked with the local ventilating 
fan(such as the one for toilet or kitchen), the HRV unit performs 
the over-supply operation to prevent inflow of the odor from out-
side.
The flow rate of supply air becomes higher than that of exhaust 
air.
Both the excessive supply mode(Supply Fresh-up)and the 
excessive exhaust mode (Exhaust Fresh-up) are selectable.
In details, contact your dealer.

No. of indoor air 
conditioner units

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14

No. of 
HRV units

8 7 7 6 6 5 5 4 4 3 3 2 2 1 1

Upper part of remote 
controller

Lower part of 
remote controller

Insert the screwdriver here and gently work 
off the upper part of remote controller.

Only one remote controller 
needs to be changed 
if factory settings have 
remained untouched.

(Factory setting)

S

M

S

S

M

Remote controller 
PC board

Remote controller wiring 
terminal block

Remote 
controller 2
(SUB)

Remote 
controller 1
(MAIN)

1

P

2

P

1

F

2

F

1

T

2

T

FORCED

OFF

REMOTE
CONTRL

TRANSMISSION

WIRING

Wire specification

Sheathed wire (2 wire)

Gauge

0.75 - 1.25 mm

2

Length

Max. 100 m

External terminal

Contact that can ensure the minimum 
applicable load of 15 V DC, 1 mA.

FORCED OFF

ON/OFF OPERATION

Input “ON” stops operation (impos-
sible by remote controllers.)

Input OFF 

→ 

ON turns 

ON unit.

Input OFF enables control by 
remote controller.

Input ON 

→ 

OFF turns 

OFF unit.

Indoor unit 1

Indoor unit 2

Max. No. of 
indoor units

Crossover wire (P

1

.P

2

)

Remote controller 1
(MAIN)

Remote controller 2
(SUB)

F2

T1

T2

FORCED
OFF

Input A

01_3P130768-1A_En.fm  Page 12  Wednesday, March 23, 2005  7:00 PM

Summary of Contents for VKM50GMV1

Page 1: ...grilles d aspiration vacuation d air avant l installation de cette unit HRV Ventilaci n con recuperaci n de calor Por favor lea cuidadosamente el manual de instalacion e instale correctamente la unid...

Page 2: ...ita ku Osaka 530 8323 Japan DAIKIN INDUSTRIES LTD EN60335 2 40 VKM50GMV1 VKM50GV1 VKM80GMV1 VKM80GV1 VKM100GMV1 VKM100GV1 DAIKIN TCF 009 KEMA 59277 KRQ ECM95 4303 3P155750 1 Yoshiaki Hirata Manager Qu...

Page 3: ...age electric shock fire or other accidents Be sure to ground Do not connect the ground wire to gas or water pipes light ning rod or a telephone ground wire Incomplete grounding may result in electric...

Page 4: ...eck the type of R410A refrigerant to be used before installing the unit Using an incorrect refrigerant will prevent normal operation of the unit For the installation of an outdoor unit refer to the in...

Page 5: ...local govern ment office or fire department for details When discharging exhaust air to a common duct the Building Standard Law requires the use of fire proof materials so attach a 2m copper plate st...

Page 6: ...nger bracket without putting force on other parts when unpacking or moving the unit As for the parts to be used for installation work be sure to use the provided accessories and specified parts desig...

Page 7: ...he diameter of the connecting pipe pipe size PT3 4B When piping passes indoors always insulate it all the way to the base of the drain socket In areas where freezing may occur always take steps to pre...

Page 8: ...nnual operating hours 10 hours day 26 days month 5 month 1 300 hours 5 Insulate all piping that passes indoors After checking that the water supply piping connections do no leak insulate them using th...

Page 9: ...sely the refrigerant piping system Do not use anti oxidants or other similar agent when braz ing the pipe joints Residue can clog the pipes and may cause breakdown of parts 8 DUCT CONNECTION Perform d...

Page 10: ...ler This system consists of multiple indoor units Mark each indoor unit as unit A unit B and be sure the terminal board wiring to the outdoor unit and BS unit are properly matched If wiring and piping...

Page 11: ...parts box and secure with the included clamping material after connecting the wires to terminal blocks Refer to Fig 17 1 17 2 Precautions when laying power supply wiring PRECAUTIONS 1 A circuit breake...

Page 12: ...entire system Connect the remote controller and transmission wiring their respective terminal blocks 10 4 Wiring for the humidity regulator locally procured VKM GMV1 series only Pass into the electri...

Page 13: ...40V 50 Hz Fuse Switch Power supply 220 240V 50 Hz F1 F2 F1 F2 L N P1 P2 F1 F2 T1 T2 Transmission wiring Outdoor unit Remote controller wiring IN D OUT D Electric parts box HRV A Outside air processing...

Page 14: ...ernal start stop input settings based on 11 FIELD SETTING AND TEST RUN 10 8 Central control If control is performed with a central device central manage ment controller etc group number needs to be se...

Page 15: ...mode to enter the local setting mode 2 Use the TEMPERATURE ADJUSTMENT button to select the desired Mode No The code display will blink 3 To make settings for individual units under group control when...

Page 16: ...for details on the external input terminal function SECOND CODE NO 04 does not function when in air condi tioner linked mode Description of setting Mode No 1 FIRST CORD NO SECOND CORD NO 01 02 03 04 0...

Page 17: ...upply solenoid valve will be heard every 3 or 4 minutes a clicking sound so listening for that clicking sound let the unit run for 30 minutes to make sure that humidifying operation is normal CAUTION...

Page 18: ...ALVE 2 FIELD WIRING 3 IN CASE USING CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTRUCTION MANUAL 4 IN CASE USING WIRING ADAPTER CONNECT IT TO THE UNIT IN ACCORDA...

Page 19: ...N BE SELECTED BY REMOTE CONTROLLER IN DETAILS REFER TO THE INSTALLATION MANUAL ATTACHED THE UNIT 6 WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE FORCED OFF OR ON OFF CONTROL OPERATION CAN BE SELECTED B...

Page 20: ...EM03A096A 0504 3P130768 1B FS HT 00_3P130768 1B_CV fm Page 2 Friday April 1 2005 8 39 AM...

Reviews: