background image

With DX coil &Humidifier

VKM50GMV1

VKM80GMV1

VKM100GMV1

With DX coil 

VKM50GV1

VKM80GV1

VKM100GV1

Total Heat Exchanger

HRV(Heat Reclaim Ventilation) -with DX Coil-

Installation

manual

English

1

CONTENTS

1 SAFETY CONSIDERATIONS ........................................ 1
2 BEFORE INSTALLATION ............................................... 2
3 SELECTING INSTALLATION SITE ................................ 3
4 PREPARATIONS BEFORE INSTALLATION................... 4
5 THE METHOD OF INSTALLATION ................................ 4
6 DRAIN PIPING AND WATER SUPPLY WORK .............. 5
7 REFRIGERANT PIPING WORK .................................... 6
8 DUCT CONNECTION .................................................... 7
9 ELECTRIC WIRING WORK ........................................... 8

10 WIRING EXAMPLE AND HOW TO SET 

THE REMOTE CONTROLLER ...................................... 9

11 FIELD SETTING AND TEST RUN ............................... 13
12 WIRING DIAGRAM ...................................................... 16

1

SAFETY CONSIDERATIONS

Please read these “SAFETY CONSIDERATIONS” carefully 
before installing HRV and be sure to install it correctly.  

The safety precautions listed here are divided into two catego-
ries. 
In either case, important safety information is listed which must 
be read carefully.

WARNING

............. Failure to observe a warning may 

result in death or serious injury.

CAUTION

............... Failure to observe a caution may result 

in injury or damage to the equipment.
These too might lead to serious injury 
depending on the circumstances.

After completing the installation, make sure that the unit oper-
ates properly during the start-up operation. Please instruct the 
customer on how to operate the unit and keep it maintained.
Also, inform customers that they should store this installation 
manual along with the operation manual for future reference.

WARNING

Ask your dealer or qualified personnel to carry out installation 
work. Do not try to install the machine yourself.
Improper installation may result in water leakage, electric 
shocks or fire.

Installation should be done following the installation manual 
and no changes should be made to the unit.
Incorrect installation may cause leaking, electric shocks, or 
fire. Injuries may result if the HRV falls.

Install the unit on a foundation strong enough to withstand 
the weight of the unit. 
A foundation of insufficient strength may result in the equip-
ment falling and causing injuries.

Do not allow exhaust air to enter the outside air intake vent.
This may cause the air of the room to become contaminated, 
harming the health.

Locate the outside air intake vent so that it does not take in 
exhaust air which contains combustion air, etc.
Incorrect installation may cause a loss of oxygen in the room, 
leading to serious accidents.

Make sure that a separate power supply circuit is provided for 
this unit and that all electrical work is carried out by qualified 
personnel according to local laws and regulations and this 
installation manual. 
An insufficient power supply capacity or improper electrical 
construction may lead to electric shocks or fire.
Insufficient power supply capacity or incorrect wiring may 
cause electrical shocks or fire.

Use only accessories and manufacturer-specified parts 
when installing.
The use of parts other than specified may cause drop of the 
unit, water leakage, electric shock, fire or other accidents.

Be sure to ground.
Do not connect the ground wire to gas or water pipes, light-
ning rod or a telephone ground wire. 
Incomplete grounding may result in electric shocks.

Make sure that all wiring is secured, the specified wires are used, 
and no external forces act on the terminal connections or wires.
Improper connections or installation may result in overheat-
ing or fire.

When wiring the power supply and connecting the remote 
controller wiring and transmission wiring, position the wires 
so that the electric parts box lid can be securely fastened.
Improper positioning of the electric parts box lid may result in 
electric shocks, fire or the terminals overheating.

When installing the unit in a small room, take measures 
against to keep refrigerant concentration from exceeding 
allowable safety limits in the event of refrigerant leakage. 
Contact the place of purchase for more information. 
Excessive refrigerant in a closed ambient can lead to oxygen 
deficiency.

If the refrigerant gas leaks during installation, ventilate the 
area immediately. 
Toxic gas may be produced if the refrigerant gas comes into 
contact with fire.

After completing the installation work, check that the refriger-
ant gas does not leak.
Toxic gas may be produced if the refrigerant gas leaks into 
the room and comes into contact with a source of fire, such 
as a fan heater, stove or cooker.

Do not directly touch any refrigerant which has leaked out of 
refrigerant piping connections, etc.
This may cause frostbite.

CAUTION

Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in elec-
tric shocks or fire.

Install the indoor and outdoor units, power supply wiring and 
connecting wires at least 1 meter away from televisions or 
radios in order to prevent image interference or noise. 
(Depending on the radio waves, a distance of 1 meter may 
not be sufficient enough to eliminate the noise.)

While following the instructions in this installation manual, 
install drain piping in order to ensure proper drainage and 
insulate piping in order to prevent condensation. 
Improper drain piping may result in water leakage and prop-
erty damage.

Install the two outdoor ducts with down slope to prevent rain-
water from entering the unit.
If this is not done completely, water may enter the building, 
may damage furniture, and cause electric shocks and fire.

Insulate the two outdoor ducts and the supply air duct to pre-
vent condensation.
If this is not done completely, water may enter the building, 
may damage furniture, etc.

Insulate the duct and the wall electrically when a metal duct 
is to be penetrated through the metal lattice and wire lattice 
or metal lining of a wooden structure wall.
Inproper duct work may cause electric shocks or fire.

Do not install the unit in the following locations:

a. Place subjected to high temperature or direct flame.

May result in fire or overheating.

b.

Where a mineral oil mist or an oil spray or vapor is pro-
duced, for example in a kitchen. 
This may cause fire. 

01_3P130768-1A_En.fm  Page 1  Wednesday, March 23, 2005  7:00 PM

Summary of Contents for VKM100GMV1

Page 1: ...grilles d aspiration vacuation d air avant l installation de cette unit HRV Ventilaci n con recuperaci n de calor Por favor lea cuidadosamente el manual de instalacion e instale correctamente la unid...

Page 2: ...ita ku Osaka 530 8323 Japan DAIKIN INDUSTRIES LTD EN60335 2 40 VKM50GMV1 VKM50GV1 VKM80GMV1 VKM80GV1 VKM100GMV1 VKM100GV1 DAIKIN TCF 009 KEMA 59277 KRQ ECM95 4303 3P155750 1 Yoshiaki Hirata Manager Qu...

Page 3: ...age electric shock fire or other accidents Be sure to ground Do not connect the ground wire to gas or water pipes light ning rod or a telephone ground wire Incomplete grounding may result in electric...

Page 4: ...eck the type of R410A refrigerant to be used before installing the unit Using an incorrect refrigerant will prevent normal operation of the unit For the installation of an outdoor unit refer to the in...

Page 5: ...local govern ment office or fire department for details When discharging exhaust air to a common duct the Building Standard Law requires the use of fire proof materials so attach a 2m copper plate st...

Page 6: ...nger bracket without putting force on other parts when unpacking or moving the unit As for the parts to be used for installation work be sure to use the provided accessories and specified parts desig...

Page 7: ...he diameter of the connecting pipe pipe size PT3 4B When piping passes indoors always insulate it all the way to the base of the drain socket In areas where freezing may occur always take steps to pre...

Page 8: ...nnual operating hours 10 hours day 26 days month 5 month 1 300 hours 5 Insulate all piping that passes indoors After checking that the water supply piping connections do no leak insulate them using th...

Page 9: ...sely the refrigerant piping system Do not use anti oxidants or other similar agent when braz ing the pipe joints Residue can clog the pipes and may cause breakdown of parts 8 DUCT CONNECTION Perform d...

Page 10: ...ler This system consists of multiple indoor units Mark each indoor unit as unit A unit B and be sure the terminal board wiring to the outdoor unit and BS unit are properly matched If wiring and piping...

Page 11: ...parts box and secure with the included clamping material after connecting the wires to terminal blocks Refer to Fig 17 1 17 2 Precautions when laying power supply wiring PRECAUTIONS 1 A circuit breake...

Page 12: ...entire system Connect the remote controller and transmission wiring their respective terminal blocks 10 4 Wiring for the humidity regulator locally procured VKM GMV1 series only Pass into the electri...

Page 13: ...40V 50 Hz Fuse Switch Power supply 220 240V 50 Hz F1 F2 F1 F2 L N P1 P2 F1 F2 T1 T2 Transmission wiring Outdoor unit Remote controller wiring IN D OUT D Electric parts box HRV A Outside air processing...

Page 14: ...ernal start stop input settings based on 11 FIELD SETTING AND TEST RUN 10 8 Central control If control is performed with a central device central manage ment controller etc group number needs to be se...

Page 15: ...mode to enter the local setting mode 2 Use the TEMPERATURE ADJUSTMENT button to select the desired Mode No The code display will blink 3 To make settings for individual units under group control when...

Page 16: ...for details on the external input terminal function SECOND CODE NO 04 does not function when in air condi tioner linked mode Description of setting Mode No 1 FIRST CORD NO SECOND CORD NO 01 02 03 04 0...

Page 17: ...upply solenoid valve will be heard every 3 or 4 minutes a clicking sound so listening for that clicking sound let the unit run for 30 minutes to make sure that humidifying operation is normal CAUTION...

Page 18: ...ALVE 2 FIELD WIRING 3 IN CASE USING CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTRUCTION MANUAL 4 IN CASE USING WIRING ADAPTER CONNECT IT TO THE UNIT IN ACCORDA...

Page 19: ...N BE SELECTED BY REMOTE CONTROLLER IN DETAILS REFER TO THE INSTALLATION MANUAL ATTACHED THE UNIT 6 WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE FORCED OFF OR ON OFF CONTROL OPERATION CAN BE SELECTED B...

Page 20: ...EM03A096A 0504 3P130768 1B FS HT 00_3P130768 1B_CV fm Page 2 Friday April 1 2005 8 39 AM...

Reviews: