[4] Use round crimp-style terminals for connecting wires to the 

power supply terminal block.
If unavailable, observe the following points when wiring.

Do not connect wires of different gauge to the same 
power supply terminal.
(Looseness in the connection may cause overheating.)

Use the specified electric wire. Connect the wire securely 
to the terminal. Lock the wire down without applying 
excessive force to the terminal. (Tightening torque: 
131N·cm ±10 %)

[5] Tightening torque for the terminal screws.

Use the correct screwdriver for tightening the terminal 
screws. If the blade of screwdriver is too small, the head 
of the screw might be damaged, and the screw will not be 
properly tightened.

If the terminal screws are tightened too hard, screws 
might be damaged.

Refer to the table below for the tightening torque of the 
terminal screws.

〈〈〈〈

Precautions when connecting the ground

〉〉〉〉

When pulling the ground wire out, wire it so that it comes 
through the cut out section of the cup washer.
(An improper ground connection may prevent a good ground 
from being achieved.)

10. 3 Remote power supply wiring, transmission wir-

ing, computerised control wire

Pass the remote control wiring, the transmission wiring, 
and the computerised control wire into the electric 
parts box through the through-hole and connect to the 
terminals on the X3M terminal block. After connection, 
secure with the included cramping material. 

(Refer to Fig. 18)

[PRECAUTIONS]

Refer to the “Remote Controller Installation Manual” on how 
to install and lay the wiring for the remote controller.

Do not, under any circumstances, connect the power wiring 
to the remote controller or transmission wiring terminal block.
Doing so can destroy the entire system.

Connect the remote controller and transmission wiring their 
respective terminal blocks.

10. 4 Wiring for the humidity regulator 

(locally procured)

 〈 〈 〈 〈

VKM-GMV1 series only

〉〉〉〉

Pass into the electric parts box together with the power 
wire through the power wiring through-hole.

Remove the short-circuit wires (1 and 2) on the X1M 
terminal block and connect the wiring for the humidity 
regulator.

Secure with cramping material together with the power 
wire.

 (Refer to Fig. 17-1)

CAUTION

〈〈〈〈

VKM-GMV1 series only

〉〉〉〉

If using humidistat, install one per HRV unit.
Controlling more than one HRV unit with a single humidity 
controller may prevent normal humidity operation and cause 
water leakage, etc.

10. 5 WIRING EXAMPLE

This unit can be used as part of the combined operation sys-
tem used together with indoor units (VRV

II

 system air condi-

tioners), or as a independent system for processing outside 
air. 

When connecting with a cooling free building multi type and 
bringing the RA (exhaust gas intake) of this unit directly in 
from the ceiling, connect to a BS unit identical to the building 
multi indoor unit (master unit), and use group-linked opera-
tion. (See the Engineering Data for details.)

Tightening torque (N·m)

Treminal block for remote controller/
Transmission wiring (X3M)

0.79 – 0.97

Power supply terminal block
(X1M)

1.18 – 1.44

Ground terminal
(M4)

1.44 – 1.94

Electric wire

Round crimp-style terminal

Attach insulation sleeve

Round crimp-style terminal

Cup washer

Cut out section

Spring washer, flat washer

Ground screw

Wiring specifications

Sheathed wire (2 wire)

Size

0.75 - 1.25mm

2

Length

MAX. 100m

External contact 
specifications

Normally closed contact
(Current tolerance 10mA – 0.5A)

Clamp

Remote controller wiring
Transmission wiring

(accessory)

Detail of terminal block (X3M)

P1 P2 F1 F2 T1 T2

FORCED

OFF

REMOTE

CONTRL

TRANSMISSION

WIRING

Fig. 18

01_3P130768-1A_En.fm  Page 10  Wednesday, March 23, 2005  7:00 PM

Summary of Contents for VKM100GMV1

Page 1: ...grilles d aspiration vacuation d air avant l installation de cette unit HRV Ventilaci n con recuperaci n de calor Por favor lea cuidadosamente el manual de instalacion e instale correctamente la unid...

Page 2: ...ita ku Osaka 530 8323 Japan DAIKIN INDUSTRIES LTD EN60335 2 40 VKM50GMV1 VKM50GV1 VKM80GMV1 VKM80GV1 VKM100GMV1 VKM100GV1 DAIKIN TCF 009 KEMA 59277 KRQ ECM95 4303 3P155750 1 Yoshiaki Hirata Manager Qu...

Page 3: ...age electric shock fire or other accidents Be sure to ground Do not connect the ground wire to gas or water pipes light ning rod or a telephone ground wire Incomplete grounding may result in electric...

Page 4: ...eck the type of R410A refrigerant to be used before installing the unit Using an incorrect refrigerant will prevent normal operation of the unit For the installation of an outdoor unit refer to the in...

Page 5: ...local govern ment office or fire department for details When discharging exhaust air to a common duct the Building Standard Law requires the use of fire proof materials so attach a 2m copper plate st...

Page 6: ...nger bracket without putting force on other parts when unpacking or moving the unit As for the parts to be used for installation work be sure to use the provided accessories and specified parts desig...

Page 7: ...he diameter of the connecting pipe pipe size PT3 4B When piping passes indoors always insulate it all the way to the base of the drain socket In areas where freezing may occur always take steps to pre...

Page 8: ...nnual operating hours 10 hours day 26 days month 5 month 1 300 hours 5 Insulate all piping that passes indoors After checking that the water supply piping connections do no leak insulate them using th...

Page 9: ...sely the refrigerant piping system Do not use anti oxidants or other similar agent when braz ing the pipe joints Residue can clog the pipes and may cause breakdown of parts 8 DUCT CONNECTION Perform d...

Page 10: ...ler This system consists of multiple indoor units Mark each indoor unit as unit A unit B and be sure the terminal board wiring to the outdoor unit and BS unit are properly matched If wiring and piping...

Page 11: ...parts box and secure with the included clamping material after connecting the wires to terminal blocks Refer to Fig 17 1 17 2 Precautions when laying power supply wiring PRECAUTIONS 1 A circuit breake...

Page 12: ...entire system Connect the remote controller and transmission wiring their respective terminal blocks 10 4 Wiring for the humidity regulator locally procured VKM GMV1 series only Pass into the electri...

Page 13: ...40V 50 Hz Fuse Switch Power supply 220 240V 50 Hz F1 F2 F1 F2 L N P1 P2 F1 F2 T1 T2 Transmission wiring Outdoor unit Remote controller wiring IN D OUT D Electric parts box HRV A Outside air processing...

Page 14: ...ernal start stop input settings based on 11 FIELD SETTING AND TEST RUN 10 8 Central control If control is performed with a central device central manage ment controller etc group number needs to be se...

Page 15: ...mode to enter the local setting mode 2 Use the TEMPERATURE ADJUSTMENT button to select the desired Mode No The code display will blink 3 To make settings for individual units under group control when...

Page 16: ...for details on the external input terminal function SECOND CODE NO 04 does not function when in air condi tioner linked mode Description of setting Mode No 1 FIRST CORD NO SECOND CORD NO 01 02 03 04 0...

Page 17: ...upply solenoid valve will be heard every 3 or 4 minutes a clicking sound so listening for that clicking sound let the unit run for 30 minutes to make sure that humidifying operation is normal CAUTION...

Page 18: ...ALVE 2 FIELD WIRING 3 IN CASE USING CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTRUCTION MANUAL 4 IN CASE USING WIRING ADAPTER CONNECT IT TO THE UNIT IN ACCORDA...

Page 19: ...N BE SELECTED BY REMOTE CONTROLLER IN DETAILS REFER TO THE INSTALLATION MANUAL ATTACHED THE UNIT 6 WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE FORCED OFF OR ON OFF CONTROL OPERATION CAN BE SELECTED B...

Page 20: ...EM03A096A 0504 3P130768 1B FS HT 00_3P130768 1B_CV fm Page 2 Friday April 1 2005 8 39 AM...

Reviews: