Frequently asked questions
[Q-101]
Error is generated if checker is connected to the system which Wiring Adaptor for Electrical Appendices (1) or (2)
(KRP2A or KRP4A) adapter is installed.
[Phenomenon]
The other supervising system (BMS) controls VRV via Wiring adapter for electrical appendices and checker is
connected to this system, supervising system causes air conditioner error.
[Cause]
Wiring Adaptor for Electrical Appendices (1) or (2) (KRP2A or KRP4A) cannot coexist with the other centralized
controllers because centralized
controller’s
operation command conflicts with the commands from the supervising
system. Checker has centralized controller function, adapter sends status of centralized controller conflicted
condition to BMS. This error itself is just a warning and does not affect operation of VRV system, but BMS system
recognizes error status and record it in its history. Besides VRV system will be in restart stand-by (thermostat-off)
due to connection of checker to the D3-NET line. As a result, it looks like VRV system stopped by error due to
connection of checker.
[Countermeasure]
By connecting checker, error will be submit to supervising system. But VRV system itself is not affected and can be
running without errors. After the removal of checker, alarm on supervising system will stop. In this case
countermeasures listed below are possible to take.
1.
Asking customer to ignore alarms while checker is connected (in case of short term connection).
2.
Using checker option “Centralized operation prohibition mode”
If a network map is already made before, checker can be disabled to work as a centralized controller by this
option (please be aware every time checker software is launched it is necessary to change this option).
Please refer to [7-3-2 Prohibit/permit centralized control]
3.
Cut J5 wire of KRP4A adapter PCB to kill alarm related to function for duplication of centralized controller.
*Please be aware if this wire is cut, duplication of centralized controller can no longer alerted.
◼
D3-NET related topic
AS0112-P-DENV
51
Cut this wire