5-2 Recording setup
5-2-1 Setup recording
In [Network map display] screen, by pressing [Period. rec set] in [Record mode], [Periodic record set]
screen will appear.
[Periodic record set] screen
[Procedure]
(1) Set [1. Record interval], [2. Record stop method], [3. Record system select]
Set item
Description
1. Record interval
•
Select record interval for writing data to PC data drive. Unit is second (5, 10,
20, 30, 60, 120, 180, 300, 600 sec)
•
Normally 20sec as default set is recommended because shorter interval takes
more disk space.
•
To record data more than days, it is recommended to set interval as 120-300
sec to reduce data amount.
Interval is time in between each record to be stored in PC hard drive but data
update interval depends on specification of VRV units.
2. Record stop
method
Please specify how to stop recording.
Manual: Recording continues until [Period. rec end] button is pressed.
Auto: Recording will end after the time specified in [Recording time] box. Please
enter recording time in “minutes”.
3. Record system
select
•
It is possible to select record/not record by system basis. You can select
multiple systems.
•
Select check box for each corresponding system and click to check/uncheck.
3. Set recording options here
1. [Record mode] button
2. Press [Period. rec set] button
AS0112-P-DENV
32
(Note)
Data update interval differs from model but normally it is fixed at between 1 to 5 minutes (this value
cannot be changed by checker because it is defined by unit). So if you shorten recording interval to
very short time such as 5 sec, same value would be recorded in multiple times.
* Actual data updated time is displayed in present data chart in the right.
(2) To save changes, press [OK] button. To cancel changes, press [Cancel] button to
return to [Network map] screen.