IM 1227 • MODELS DC THERMOSTATS 18 www.DaikinApplied.com
7-D
ay
P
rogrammable
C
ommerCial
D
igiTal
T
hermosTaTs
Installation Instructions
Remove and Replace the Old Thermostat
To install the thermostat properly, please follow these step by
step instructions. If you are unsure about any of these steps,
call a qualified technician for assistance.
• Assemble tools: Flat blade screwdriver, wire cutters and
wire strippers.
• Make sure your Heater/Air Conditioner is working
properly before beginning installation of the thermostat.
• Carefully unpack the thermostat. Save the screws, any
brackets, and instructions.
• Turn off the power to the Heating/Air Conditioning system
at the main fuse panel. Most residential systems have a
separate breaker for disconnecting power to the furnace.
• Remove the cover of the old thermostat. If it does not
come off easily, check for screws.
• Loosen the screws holding the thermostat base or
subbase to the wall and lift away.
• Disconnect the wires from the old thermostat. Tape the
ends of the wires as you disconnect them, and mark them
with the letter of the terminal for easy reconnection to the
new thermostat.
• Keep the old thermostat for reference purposes, until your
new thermostat is functioning properly.
Wire Connections
If the terminal designations on your old thermostat do not
match those on the new thermostat, refer to the chart below or
the wiring diagrams that follow.
Table 4: Terminal Designations
Wire from the
old thermostat
terminal marked
Function
Install on the
new thermostat
connector marked
G or F
Fan
G
Y1, Y or C
Cooling
Y1
W1, W or H
Heating
W1/0/B
Rh, R, M, Vr, A
Power
R
C
Common
C
O/B
Rev. Valve
W1/O/B*
W2
2nd Stage Heat
W2
Y2
2nd Stage Heat
Y2
W3
3rd Stage Cooling
W3
H, HUM
Humidity
HUM
D, DEHUM
Dehumidity
DEHUM
Ck1
Dry Contact Switch
DRY CONTACT
CKGND
Dry Contact Switch
DRY CONTACT
S1, OUT -
Outdoor Sensor
OUTDOOR
S2, OUT +
Outdoor Sensor
OUTDOOR
AUX
Auxilliary Output
AUX
* O/B is used if your system is a Heat Pump
Figure 18: TSTATD4272C Thermostat Backplate
W1/O/B
1st stage heat/reversing valve
W2
2nd stage heat circuit
W3
3rd stage heat circuit
HUM
Humidity control circuit
DEHUM
Dehumidity control circuit
AUX
Aux output
C
24 VAC common
R
24 VAC Return
OUTDOOR SENSOR
Outdoor Sensor connections
DRY CONTACT
Dry Contact connections
Y2
2nd stage compressor
Y1
1st stage compressor
G
Fan relay
IMPORTANT:
This thermostat requires both R (24 VAC Return)and C (24 VAC
Common) be connected to the backplate terminals.