IOM 1206-13 • TRAILBLAZER
®
MODEL AGZ CHILLERS
54 www.DaikinApplied.com
Unit Controller Operation
EXV Module 1 and 2
These modules will be used only when the expansion valve type is electronic.
Table 30: Digital Inputs
Description
Output Off
Output On
DI1
Circuit 1 or 2 MLP Switch
Fault
No Fault
X2
Heat Recovery Request
Switch
No Request
Request
Table 31: Digital Outputs
Description
Output Off
Output On
DO1
Circuit 1 or 2 Fan
Output 5
Fan(s) Off
Fan(s) On
Table 32: Analog Outputs
Description
Output Signal
X1
Heat Recovery Pump/
Valve
0-10VDC
X3
Heat Recovery Pump/
Valve
4-20 mA
Current
Table 33: Stepper Motor Output
Description
M1+, M1-
EXV Stepper Coil 1
M2+, M2-
EXV Stepper Coil 2
Condenser Fan Output Labels
All condenser fan output labels, both the digital outputs and analog speed signals, will be labeled according to which fans are
connected to each one. The following tables show the fans connected to each output for each configuration.
Table 34: AGZ-E Models without VFDs
Output Descr .
Physical
Output
Number of Fans
4
6
8
10
12
14
Circuit 1
Speed 1
UC X5
Speed 2
UC X2
Fan Output 1
UC DO3
Fan 11
Fan 11
Fan 11
Fan 11
Fan 11
Fan 11/13
Fan Output 2
UC DO4
Fan 12
Fan 12
Fan 12
Fan 12
Fan 12
Fan 12
Fan Output 3
UC DO5
Fan 13
Fan 13
Fan 13
Fan 13
Fan 14/16
Fan Output 4
UC DO6
Fan 14
Fan 14
Fan 14/16
Fan 15
Fan Output 5
EEXV1 DO1
Fan 15
Fan 15
Fan 17
Circuit 2
Speed 1
UC X6
Speed 2
UC X3
Fan Output 1
UC DO7
Fan 21
Fan 21
Fan 21
Fan 21
Fan 21
Fan 21/23
Fan Output 2
UC DO8
Fan 22
Fan 22
Fan 22
Fan 22
Fan 22
Fan 22
Fan Output 3
UC DO9
Fan 23
Fan 23
Fan 23
Fan 23
Fan 24/26
Fan Output 4
UC DO10
Fan 24
Fan 24
Fan 24/26
Fan 25
Fan Output 5
EEXV2 DO1
Fan 25
Fan 25
Fan 27