8
TM-FT
-0415-B
Specifications (R22) - Continued
mm/in
cm³/ fl.oz.
700 / 24.6
INDOOR UNIT
WIRELESS
WIRED
OUTDOOR UNIT
MODEL
FAN
MATERIAL
DRIVE
TYPE
QUANTITY
DIAMETER
COMPRESSOR
TYPE
OIL TYPE
INDEX OF PROTECTION (IP)
FAN MOTOR
OIL AMOUNT
DIRECT
457 / 18.0
PROPELLER
QUANTITY
TYPE
ASG20
455 / 17.9
ATMOS NM56M or SUNISO 4GDID
1
INDUCTION
1
IP23
IP54
ROTARY
V/Ph/Hz
W
A
W
POWER SOURCE
RATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
INSULATION GRADE
POLES
SPEED
RPM
220 - 240 / 1 / 50
CLASS F
CLASS B
121
0.53
874
840
60
6
POWER SOURCE
CAPACITOR
RATED INPUT POWER
RATED RUNNING CURRENT
LOCKED ROTOR AMP.
INSULATION GRADE
V/Ph/Hz
µF
W
A
A
45
2482
11.13
56
CLASS E
220 - 240 / 1 / 50
m²/ft²
mm/in
mm/in
ALUMINIUM
mm/in
0.61 / 6.58
1
20
2
18
MATERIAL
MATERIAL
MATERIAL
ROW
FIN PER INCH
DIAMETER
THICKNESS
THICKNESS
FACE AREA
CASING
COIL
FIN
TUBE
7.00 / 0.276
SEAMLESS INNER GROOVE COPPER
GALVANISED STEEL
0.23 / 0.009
0.11 / 0.0043
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER
AS A RESULT OF AMBIENT CONDITION.
OUTDOOR UNIT
l/s / CFM
755 / 1600
dBA
52
mm/in
756 / 29.8
mm/in
855 / 33.7
mm/in
328 / 12.9
mm/in
793 / 31.2
mm/in
990 / 39.0
mm/in
415 / 16.3
kg/lb
50 / 110.2
LIQUID
mm/in
9.52 / 3/8
GAS
mm/in
15.88 / 5/8
WIDTH
HEIGHT
AIR FLOW
SOUND PRESSURE LEVEL
HEIGHT
PACKING
DIMENSION
DEPTH
DEPTH
UNIT NET WEIGHT
PIPE
CONNECTION
TYPE
SIZE
WIDTH
UNIT
DIMENSION
FLARE VALVE
808 / 1712
56
756 / 29.8
855 / 33.7
328 / 12.9
793 / 31.2
990 / 39.0
415 / 16.3
57 / 126
GLASS REINFORCED ACRYL STYRENE RESIN
139
0.6
75
900 / 31.70
50
2941
12.2
72
0.62 / 6.63
FT25LV1L
FT25MV1I
FT25LV1M
FT25MV1J
R25CV1
FT311V1L
FT311V1M
R31CV1