SiENBE07-618_C
Field Settings
Trial Operation and Field Settings
127
2. Field Settings
2.1
When 2 Units are Installed in 1 Room
When 2 indoor units are installed in 1 room, 1 of the 2 pairs of indoor unit and infrared remote
control can be set for different addresses.
Both the indoor unit PCB and the infrared remote control need alteration.
Indoor Unit PCB
Cut the jumper JA on PCB.
Infrared remote
control
Cut the jumper J4.
ADDRESS: JA
CUT
EXIST
1
2
ADDRESS
JA
JB
JC
(R12240)
J4
ADDRESS
EXIST
1
CUT
2
J4
(R12241)