Troubleshooting
Service Diagnosis
89
Troubleshooting
Check No.07
Refer to P.97
Check No.08
Refer to P.97
Check No.13
Refer to P.99
(R12016)
Caution
NO
YES
NO
YES
NO
YES
YES
NO
NO
YES
YES
NO
Monitor the supply voltage,
discharge and suction pressures,
and other factors for a long term.
Possible causes
∗
Instantaneous supply voltage
drop
∗
Compressor overloaded
∗
Short circuit
∗
An output overcurrent signal may result from wrong internal wiring. If the wires have been
disconnected and reconnected and the system is interrupted by an output overcurrent, take the
following procedure.
Check No. 08
Check the discharge pressure.
Check No. 13
Check the power module.
Check No. 07
Check the installation condition.
Check with the inverter checker (
∗
).
Turn off the power and disconnect
the harnesses U, V, and W.
Turn off the power, and reconnect
the harnesses. Turn on the power
again and start operation.
Turn off the power and turn it on
again to start the system. See if the
same error occurs.
Check the supply voltage.
Keep on using as it is.
Check the connectors and
other components.
Fully open the stop valve.
Correct the power supply.
Replace the compressor.
Normal?
Error again?
Stop valve fully open?
Voltage as rated?
Any LED off?
Short circuit
or wire breakage
between compressor's coil
phases?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Replace the PM1.
(Replace the outdoor unit
PCB.)
Correct the power supply or
replace the PM1.
(Replace the outdoor unit
PCB.)
∗
Inverter checker
Part No.: 1225477