Troubleshooting
SiENBE07-618_C
68
Service Diagnosis
4.8
Outdoor Unit PCB Abnormality
Remote Control
Display
E1
Method of
Malfunction
Detection
Detection within the program of the microcomputer
Malfunction
Decision
Conditions
The program of the microcomputer is in abnormal running order.
Supposed
Causes
Defective outdoor unit PCB
Noise
Momentary fall of voltage
Momentary power failure
Troubleshooting
(R7183)
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
YES
NO
NO
YES
Turn on the power again.
Check to see if the unit is
grounded.
Replace the outdoor unit
PCB.
Ground the system.
Error again?
Grounded?
The cause can be external
factors other than
malfunction.Investigate the
cause of noise.
SIENBE07-618_C_FRONT.pdf 80