FDBQ25B8V1
Split series room air conditioners
Multi system room air conditioners
4PW23698-1

Installation manual

2

Installation

Selection of installation site

Ensure sufficient clearance for maintenance and service.

Make sure that no piping is passing through the hatched area

(See figure 2)

-

condensation can drip on the switch box

-

pipes can prevent you from opening the switch box smoothly

Refer to the installation manual of the outdoor unit and confirm
the maximum allowable piping length.

Preparation before installation

Relation of the ceiling opening to the unit and suspension bolt
position 

(See figure 1)

Making the wall hole to the outdoor side for the electric wiring,
the refrigerant and drain piping
-

The hole must slope down toward the outdoor side.

-

The hole size must be just as large as to hold the protective 
pipe (Ø7–8 cm) (field supply).

-

Use a wall hole cover (field supply) to hide the wall hole as 
much as possible.

The fan speed for this indoor unit is equipped to provide a
standard external pressure.

Install the suspension bolts

Use M10 size bolts for the suspension.
Use anchors for existing ceiling, and a sunken insert, sunken
anchor or other field supplied parts to reinforce the ceiling in
order to bear the weight of the unit.

Installing the indoor unit

Install the indoor unit temporarily. Attach the hanger bracket to the
suspension bolt. Be sure to fix it securely by using a nut and washer
on the upper and lower side of the hanger bracket and tighten the
upper nut.

I

NSTALLING

 

THE

 

OUTDOOR

 

UNIT

Refer to the installation manual of the outdoor unit.

R

EFRIGERANT

 

PIPING

This unit is especially designed for use of R-410A refrigerant.

Field piping

All field piping must be provided by a licensed refrigeration technician
and must comply with the relevant local and national codes.

Pipe connections

Refer to the chapter 

"Outlook drawing" on page 1

  for the

required piping diameters.

If installed as a multi system indoor unit, use the reducers
supplied with the outdoor unit when the piping from the indoor
unit does not fit on the port of the outdoor unit. For instructions,
read the instruction sheet supplied with the outdoor unit.

Be sure to insulate the gas pipe and the liquid pipe separately
with polyethylene foam insulation material (thermal
conductivity=0.041~0.052 kW/mK)

1

protective pipe (field supply)

2

wall hole cover (field supply)

1

anchor (field supply)

2

long nut or turn-buckle (field supply)

3

suspension bolt (field supply)

1

2

Ø7–8 cm

NOTE

Check that the unit is levelled at all 4 corners.

(See figure 3)

1

vinyl tube with water

2

water level

Indoor unit

Insulation

Inside diameter

wall thickness

Gas pipe

12–15 mm

8–10 mm

Liquid pipe

8–10 mm

7–10 mm

NOTE

For the gas pipe, use a polyethylene foam resistant to
a temperature of 110°C.

1

2

3

1

nut

2

washer

3

tighten with a double nut

Summary of Contents for Split Series

Page 1: ...INSTALLATION MANUAL FDBQ25B8V1 Split series room air conditioners Multi system room air conditioners...

Page 2: ...1 2 4 5 6 3 1 2 3 4 5 6...

Page 3: ...e normativ e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi na...

Page 4: ...ORIES COULD RESULT IN ELECTRIC SHOCK SHORTCIRCUIT LEAKS FIRE OR OTHER DAMAGE TO THE EQUIPMENT BE SURE ONLY TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE SPECIFICALLY DESIGNED FOR USE WITH THE EQUIPMENT...

Page 5: ...rily Attach the hanger bracket to the suspension bolt Be sure to fix it securely by using a nut and washer on the upper and lower side of the hanger bracket and tighten the upper nut INSTALLING THE OU...

Page 6: ...Connector interface adaptor for sky air series When inserting the refrigerant piping in the wall hole take care not to let dust or moisture come into the piping Protect the pipes with a cap or seal t...

Page 7: ...n case of installing an electric heater execute the additional wiring and use a separate power supply of 1 50 Hz 230 V Use solid core cables to avoid loosening of the wires Refer to the installation m...

Page 8: ...emark wiring length up to 100 m Master slave unit system mode batting System operation mode cool or heat is determined by the mode the master unit is in When the master unit is in cool mode respective...

Page 9: ...NOTES NOTES...

Page 10: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW23698 1...

Reviews: