background image

3

English

2-3 Electrical specifications

(

<c> in the table indicates the operating condition (shown in the previ-

ous figure).)

2-4 Accessories

Confirm that the following accessories are supplied.

2-5 Main components

For main components and function of the main components, refer to the 
Engineering Data Book.

3.

BEFORE INSTALLATION

<Bringing-in>

Bring in the outdoor unit slowly by holding the lugs provided on the left 
and right sides as shown in the figures below.
(Take care so that hands and objects do not touch the fin on the rear.)

Make sure to use accessories and specified specification parts in the 
installation work.

4.

SELECTION OF INSTALLATION 
LOCATION

The refrigerant R410A itself is nontoxic, nonflammable and safe. If 
the refrigerant should leak however, its concentration may exceed 
the allowable limit depending on room size. Due to this it could be 
necessary to take measures against leakage. Refer to the chapter 
“Caution for refrigerant leaks”.

(1) Select a proper location satisfying the following requirements

with approval of the customer.

Sufficient ventilation is secured.

Adjacent houses are not annoyed.

The foundation is strong enough to support the weight and with-
stand vibrations of the outdoor unit, and the location is safe and 
allows horizontal installation.

The outdoor unit is exposed to rain as less as possible.

The space for installation and servicing is secured around the out-
door unit.

The indoor/outdoor piping length and wiring length are within the 
allowable range.

(2) When installing the outdoor unit in a location affected by strong 

wind, pay special attention to the following items.

If strong wind whose velocity is 11 mph or more blows to the out-
door unit from the air outlet side, the air flow rate of the outdoor 
unit is reduced, the outlet air is sucked again (short-circuit), and 
the following effect may be caused:

The capacity is deteriorated.

The adhered frost increases during heating operation.

The operation is stopped by pressure rise.

If excessive strong wind continuously blows from the air outlet side 
of the outdoor unit, the fan may rotate in the reverse direction at 
high speed, and lead to damage.  Install the outdoor unit in refer-
ence to the following figures.

Position the air outlet side toward the building wall, fence or 
windbreak screen. 

Let the air outlet direction face be at right angles to the wind 
direction.

(3) When installing the outdoor unit in a location with heavy snow-

fall, pay special attention to the following items:

Prepare strong foundation.

Attach the snow hood (optional accessory).

Remove the suction grill on the rear so that snow will not be accu-
mulated in the rear fin.

(4) When there is a possibility of short-circuit depending on the 

ambient situation, use the wind direction adjusting plate 
(optional accessory).

Model

RZQ30PVJU9

RZQ36PVJU9

RZR36PVJU

RZQ42PVJU9

RZR42PVJU

Precaution

Power

Phase

~

Frequency

(Hz)

60

Voltage

(V)

208/230

Voltage tolerance

(%)

±10

Max. Overcurrent 
Protective device

(A)

30

Min. Circuit Amps.

(A)

27.0

<c>

Compressor

Phase

3~

Frequency

(Hz)

60

Voltage

(V)

208/230

Clamp

Insulation tube

Others

Large

Small

• Installation 

manual 

(6 pcs.)

(1 pc.)

(1 pc.)

Outdoor unit

Lug

Discharge grille

If the suction hole area on the side of the casing 
is held, the casing may be deformed.  Make sure 
to hold the corner.

(Rear view)

(Front view)

Suction 
grille

(Secure the space for installation and servicing.)

Strong wind

Strong wind

Air outlet

01_EN_3PN07193-7H.fm  Page 3  Monday, December 27, 2010  4:30 PM

Summary of Contents for SkyAir RZQ36PVJU9

Page 1: ...l installation Conserver ce manuel à portée de main pour référence ultérieure Ce manuel doit être donné au propriétaire de l équipement Lea cuidadosamente estas instrucciones antes de instalar Guarde este manual en un lugar a mano para leer en caso de tener alguna duda Este manual debe permanecer con el propietario del equipo SPLIT SYSTEM Air Conditioners INSTALLATION MANUAL English Français Españ...

Page 2: ...lt in water leakage elec tric shock or fire When installing the unit in a small room take measures to keep the refrigerant concentration from exceeding allowable safety limits Excessive refrigerant leaks in the event of an accident in a closed ambient space can lead to oxygen deficiency Use only specified accessories and parts for installation work Failure to use specified parts may result in wate...

Page 3: ... the air or where volatile flammables such as thinner or gasoline are handled Oper ating the unit in such conditions can cause a fire Take adequate measures to prevent the outdoor unit from being used as a shelter by small animals Small animals making con tact with electrical parts can cause malfunctions smoke or fire Instruct the customer to keep the area around the unit clean NOTE Install the po...

Page 4: ...wind whose velocity is 11 mph or more blows to the out door unit from the air outlet side the air flow rate of the outdoor unit is reduced the outlet air is sucked again short circuit and the following effect may be caused The capacity is deteriorated The adhered frost increases during heating operation The operation is stopped by pressure rise If excessive strong wind continuously blows from the ...

Page 5: ...conduit and servicing between the units A When an obstruction is present on the air inlet side When the upward area is open 1 When one outdoor unit is installed individually When an obstruction is present only on the air inlet side When an obstruction is present on the both sides 2 When two or more outdoor units are installed side by side When an obstruction is present on the both sides When an ob...

Page 6: ...tdoor unit is installed individually The dimensional relationship between H L and A is as shown in the table below NOTE Close the area under the frame so that the outlet air does not bypass there 2 When only two outdoor units are installed side by side The dimensional relationship between H L and A is as shown in the table below NOTE 1 Close the area under the frame so that the outlet air does not...

Page 7: ... Only two outdoor units can be installed side by side D When outdoor units are stacked 1 When an obstruction is present on the air outlet side NOTE 1 Only two outdoor units can be stacked 2 About 4 in is required as the drain piping size for the upper outdoor unit 3 Close the area Z gap between the upper outdoor unit and the lower outdoor unit so that the outlet air does not bypass there 2 When an...

Page 8: ...g nut 3 Remove the transportation metal and the washer as shown in the above figure 4 Return and tighten the fixing nut again 5 Return the sound proof cover to achieve the former status CAUTION If the unit is operated with the transportation metal attached abnor mal vibration or sound may be generated 6 REFRIGERANT PIPING WORK CAUTION To piping technician Make sure to open the stop valves after fi...

Page 9: ...rigerant other than the specified refrigerant enter the refrigerant system Do not let any gas such as air enter the refrigerant system Precautions when connecting the piping See the following table for flare dimensions When connecting the flare nuts apply refrigerant oil to the inside and outside of the flares and turn them three or four times at first Use ester oil or ether oil See the following ...

Page 10: ...vacuum pressure indi cated by the vacuum gage does not increase If the vacuum pressure increases the system may contain moisture or have leakage If there is a possibility of moisture remaining in the piping for example when there is a possibility of dew condensation inside the pip ing because the piping work was performed in the rainy season or over a long period of time or when rainwater may have...

Page 11: ... a hexagon wrench into the valve stem and turn the valve stem clockwise 2 When the valve stem cannot be turned any more stop turning Now the valve is closed The valve is sealed in the arrow area Take care not to damage the arrow area After handling the valve make sure to tighten the valve cap securely Use charge hose equipped with push in the work After the work make sure to tighten the valve cap ...

Page 12: ...supply wiring and transmission wiring Let the power supply wiring and transmission wiring with a conduit pass through one of the knockout holes on the front or side piping cover and let the transmission wiring with a conduit pass through another knockout hole For protection from uninsulated live parts thread the power supply wiring and the transmission wiring through the included insulation tube a...

Page 13: ...le below for tightening torque for the terminal screws Model Phase and frequency Voltage Max Overcurrent Protective device Min Circuit Amps RZQ30PVJU9 60Hz 208 230V 30A 27A RZQ36PVJU9 RZR36PVJU RZQ42PVJU9 RZR42PVJU Screw Remove it and open the cover Control box Terminal block Stop valve mounting plate Knockout hole Power supply wiring including ground wire or transmission wiring Power supply wirin...

Page 14: ...RK 5 Piping size and heat insulation Refer to 6 1 Selection of piping material 6 5 Heat insulation of piping 6 Check of stop valve Confirm that the stop valve is open on both the liquid line and gas line 7 Record of amount of additional refrigerant Record the amount on the label stuck on the back of the front panel 8 Measurement of insulation in main power circuit Use the megatester for 500 V Do n...

Page 15: ...outdoor unit may continue to operate for a further 3 minutes If the system has not undergone the check operation by the test run button since it was first installed a malfunction code U3 is dis played In this case perform the check operation by referring to 9 1 Power on and check operation Make sure to turn on the power 6 hours before starting operation for supplying the power to the crankcase hea...

Page 16: ...top valves in the outdoor unit remain closed Open the stop valve on both the gas and liquid lines The refrigerant is overcharged Calculate again the required amount of refrigerant to be charged based on the piping length recover the refrigerant using the refrigerant recovery device then achieve proper amount of refrigerant E4 F3 The stop valves in the outdoor unit remain closed Open the stop valve...

Page 17: ...ons in steps 1 and 2 above 4 Deal with the situations where the result exceeds the maximum con centration level Where the installation of a facility results in a concentration in excess of the maximum concentration level then it will be necessary to revise the system Please consult your dealer total amount of refrigerant in the system maximum concen tration level lb ft 3 volume ft 3 of the room in...

Page 18: ... 1101 HT 3PN07193 7H EM10A070 00_CV_3PN07193 7H fm Page 2 Saturday December 25 2010 1 03 PM ...

Reviews: