background image

English

2

Heat exchanger fins are sharp enough to cut.
To avoid injury wear glove or cover the fins when working 
around them.

Install drain piping to proper drainage. Improper drain piping 
may result in water leakage and property damage.

Insulate piping to prevent condensation.

Be careful when transporting the product.

Do not turn off the power immediately after stopping operation. 
Always wait for at least 5 minutes before turning off the power. 
Otherwise, water leakage may occur.

Do not use a charging cylinder. Using a charging cylinder may 
cause the refrigerant to deteriorate.

Refrigerant R410A in the system must be kept clean, dry, and 
tight.
(a) Clean and Dry -- Foreign materials (including mineral oils 

such as SUNISO oil or moisture) should be prevented from 
getting into the system.

(b) Tight -- R410A does not contain any chlorine, does not 

destroy the ozone layer, and does not reduce the earth's 
protection again harmful ultraviolet radiation. R410A can 
contribute to the greenhouse effect if it is released. There-
fore take proper measures to check for the tightness of the 
refrigerant piping installation. Read the chapter Refrigerant 
Piping and follow the procedures.

Since R410A is a blend, the required additional refrigerant must 
be charged in its liquid state. If the refrigerant is charged in a 
state of gas, its composition can change and the system will 
not work properly.

The indoor unit is for R410A. See the catalog for indoor models 
that can be connected. Normal operation is not possible when 
connected to other units.

Remote controller (wireless kit) transmitting distance can be 
shorter than expected in rooms with electronic fluorescent 
lamps (inverter or rapid start types). Install the indoor unit far 
away from fluorescent lamps as much as possible.

Indoor units are for indoor installation only. Outdoor units can 
be installed either outdoors or indoors.

Do not install the air conditioner in the following locations:
(a) Where a mineral oil mist or oil spray or vapor is produced, 

for example, in a kitchen.
Plastic parts may deteriorate and fall off or result in water 
leakage.

(b) Where corrosive gas, such as sulfurous acid gas, is pro-

duced.
Corroding copper pipes or soldered parts may result in 
refrigerant leakage.

(c) Near machinery emitting electromagnetic waves.

Electromagnetic waves may disturb the operation of the 
control system and cause the unit to malfunction.

(d) Where flammable gas may leak, where there is carbon fiber, 

or ignitable dust suspension in the air, or where volatile 
flammables such as thinner or gasoline are handled. Oper-
ating the unit in such conditions can cause a fire.

Take adequate measures to prevent the outdoor unit from being 
used as a shelter by small animals. Small animals making con-
tact with electrical parts can cause malfunctions, smoke, or 
fire. Instruct the customer to keep the area around the unit 
clean.

NOTE

Install the power supply and control wires for the indoor and 
outdoor units at least 3.5 feet away from televisions or radios to 
prevent image interference or noise.
Depending on the radio waves, a distance of 3.5 feet may not be 
sufficient to eliminate the noise.

Dismantling the unit, treatment of the refrigerant, oil and addi-
tional parts must be done in accordance with the relevant local, 
state, and national regulations.

Do not use the following tools that are used with conventional 
refrigerants: gauge manifold, charge hose, gas leak detector, 
reverse flow check valve, refrigerant charge base, vacuum 
gauge, or refrigerant recovery equipment.

If the conventional refrigerant and refrigerator oil are mixed in 
R410A, the refrigerant may deteriorate.

This air conditioner is an appliance that should not be accessi-
ble to the general public.

The wall thickness of field-installed pipes should be selected in 
accordance with the relevant local, state, and national regula-
tions.

Safety Precaution

The PCI Data Station is a class A product. In a domestic environment 
this product may cause radio interference in which case the user may be 
required to take adequate measures.

2.

INTRODUCTION

2-1 Standard operation limit

The figures below assume following operating conditions for indoor and 
outdoor units:

Equivalent pipe length ...................... 25 ft.
Level difference ................................ 0 ft.

A

Outdoor temperature (°FDB)

B

Indoor temperature (°FWB)

C

Outdoor temperature (°FWB)

D

Indoor temperature (°FDB)

Range for continuous operation

Range for pull down operation

Range for warming up operation

Range for operation

2-2 Technical specifications

(

<a> and 

<b>  in the table indicate the operating condition (shown in 

the previous figure).)

Model

RZQ30PVJU9

RZQ36PVJU9

RZR36PVJU

RZQ42PVJU9

RZR42PVJU

Precaution

Refrigerant

R410A

Power

208/230V 60Hz

[FCQ] Ceiling mounted
Cooling (MBh)
Heating (MBh) (RZQ only)


36.0
39.5

40.5
41.5

*<a>
*<b>

[FHQ] Ceiling suspended
Cooling (MBh)
Heating (MBh) (RZQ only)


36.0
37.5

40.5
39.5

*<a>
*<b>

[FTQ] Air handling unit
Cooling (MBh)
Heating (MBh) (RZQ only)

30.0
34.0

36.0
40.0

42.0
47.0

*<a>
*<b>

Dimensions

(inch)

52-15/16 × 35-7/16 × 12-5/8

H × W × D
Weight

(lb.)

283

Connections

Gas

(inch)

5/8

Liquid

(inch)

3/8

Cooling

Heating

<b>

B

<c>

A

C

D

<a>

– 4

5

59

115

41

50

50

43

70

95

81

50

23

77

60

67

82

57

01_EN_3PN07193-7H.fm  Page 2  Monday, December 27, 2010  4:30 PM

Summary of Contents for SkyAir RZQ36PVJU9

Page 1: ...l installation Conserver ce manuel à portée de main pour référence ultérieure Ce manuel doit être donné au propriétaire de l équipement Lea cuidadosamente estas instrucciones antes de instalar Guarde este manual en un lugar a mano para leer en caso de tener alguna duda Este manual debe permanecer con el propietario del equipo SPLIT SYSTEM Air Conditioners INSTALLATION MANUAL English Français Españ...

Page 2: ...lt in water leakage elec tric shock or fire When installing the unit in a small room take measures to keep the refrigerant concentration from exceeding allowable safety limits Excessive refrigerant leaks in the event of an accident in a closed ambient space can lead to oxygen deficiency Use only specified accessories and parts for installation work Failure to use specified parts may result in wate...

Page 3: ... the air or where volatile flammables such as thinner or gasoline are handled Oper ating the unit in such conditions can cause a fire Take adequate measures to prevent the outdoor unit from being used as a shelter by small animals Small animals making con tact with electrical parts can cause malfunctions smoke or fire Instruct the customer to keep the area around the unit clean NOTE Install the po...

Page 4: ...wind whose velocity is 11 mph or more blows to the out door unit from the air outlet side the air flow rate of the outdoor unit is reduced the outlet air is sucked again short circuit and the following effect may be caused The capacity is deteriorated The adhered frost increases during heating operation The operation is stopped by pressure rise If excessive strong wind continuously blows from the ...

Page 5: ...conduit and servicing between the units A When an obstruction is present on the air inlet side When the upward area is open 1 When one outdoor unit is installed individually When an obstruction is present only on the air inlet side When an obstruction is present on the both sides 2 When two or more outdoor units are installed side by side When an obstruction is present on the both sides When an ob...

Page 6: ...tdoor unit is installed individually The dimensional relationship between H L and A is as shown in the table below NOTE Close the area under the frame so that the outlet air does not bypass there 2 When only two outdoor units are installed side by side The dimensional relationship between H L and A is as shown in the table below NOTE 1 Close the area under the frame so that the outlet air does not...

Page 7: ... Only two outdoor units can be installed side by side D When outdoor units are stacked 1 When an obstruction is present on the air outlet side NOTE 1 Only two outdoor units can be stacked 2 About 4 in is required as the drain piping size for the upper outdoor unit 3 Close the area Z gap between the upper outdoor unit and the lower outdoor unit so that the outlet air does not bypass there 2 When an...

Page 8: ...g nut 3 Remove the transportation metal and the washer as shown in the above figure 4 Return and tighten the fixing nut again 5 Return the sound proof cover to achieve the former status CAUTION If the unit is operated with the transportation metal attached abnor mal vibration or sound may be generated 6 REFRIGERANT PIPING WORK CAUTION To piping technician Make sure to open the stop valves after fi...

Page 9: ...rigerant other than the specified refrigerant enter the refrigerant system Do not let any gas such as air enter the refrigerant system Precautions when connecting the piping See the following table for flare dimensions When connecting the flare nuts apply refrigerant oil to the inside and outside of the flares and turn them three or four times at first Use ester oil or ether oil See the following ...

Page 10: ...vacuum pressure indi cated by the vacuum gage does not increase If the vacuum pressure increases the system may contain moisture or have leakage If there is a possibility of moisture remaining in the piping for example when there is a possibility of dew condensation inside the pip ing because the piping work was performed in the rainy season or over a long period of time or when rainwater may have...

Page 11: ... a hexagon wrench into the valve stem and turn the valve stem clockwise 2 When the valve stem cannot be turned any more stop turning Now the valve is closed The valve is sealed in the arrow area Take care not to damage the arrow area After handling the valve make sure to tighten the valve cap securely Use charge hose equipped with push in the work After the work make sure to tighten the valve cap ...

Page 12: ...supply wiring and transmission wiring Let the power supply wiring and transmission wiring with a conduit pass through one of the knockout holes on the front or side piping cover and let the transmission wiring with a conduit pass through another knockout hole For protection from uninsulated live parts thread the power supply wiring and the transmission wiring through the included insulation tube a...

Page 13: ...le below for tightening torque for the terminal screws Model Phase and frequency Voltage Max Overcurrent Protective device Min Circuit Amps RZQ30PVJU9 60Hz 208 230V 30A 27A RZQ36PVJU9 RZR36PVJU RZQ42PVJU9 RZR42PVJU Screw Remove it and open the cover Control box Terminal block Stop valve mounting plate Knockout hole Power supply wiring including ground wire or transmission wiring Power supply wirin...

Page 14: ...RK 5 Piping size and heat insulation Refer to 6 1 Selection of piping material 6 5 Heat insulation of piping 6 Check of stop valve Confirm that the stop valve is open on both the liquid line and gas line 7 Record of amount of additional refrigerant Record the amount on the label stuck on the back of the front panel 8 Measurement of insulation in main power circuit Use the megatester for 500 V Do n...

Page 15: ...outdoor unit may continue to operate for a further 3 minutes If the system has not undergone the check operation by the test run button since it was first installed a malfunction code U3 is dis played In this case perform the check operation by referring to 9 1 Power on and check operation Make sure to turn on the power 6 hours before starting operation for supplying the power to the crankcase hea...

Page 16: ...top valves in the outdoor unit remain closed Open the stop valve on both the gas and liquid lines The refrigerant is overcharged Calculate again the required amount of refrigerant to be charged based on the piping length recover the refrigerant using the refrigerant recovery device then achieve proper amount of refrigerant E4 F3 The stop valves in the outdoor unit remain closed Open the stop valve...

Page 17: ...ons in steps 1 and 2 above 4 Deal with the situations where the result exceeds the maximum con centration level Where the installation of a facility results in a concentration in excess of the maximum concentration level then it will be necessary to revise the system Please consult your dealer total amount of refrigerant in the system maximum concen tration level lb ft 3 volume ft 3 of the room in...

Page 18: ... 1101 HT 3PN07193 7H EM10A070 00_CV_3PN07193 7H fm Page 2 Saturday December 25 2010 1 03 PM ...

Reviews: