9

English

• Be careful not to let the field piping 

come into contact with the compres-
sor terminal cover.
Adjust the height of the insulation 
material on liquid pipe when it has 
the possibility of getting in contact 
with the terminal.  Also make sure 
that the field piping does not touch 
the mounting bolt of the compressor.

• When it is expected that water con-

densed in the stop valve will reach 
the indoor unit through the gap 
between the heat insulating material 
and the piping (for example, when 
the outdoor unit is installed in a 
higher position than the indoor unit), 
take proper action such as caulking 
the connection area.

[Measures to prevent invasion of small creatures and litter]

• Block all gaps in the piping penetration areas with putty or heat insu-

lating material (arranged in the local field) as shown in the figure 
below.
(If small creatures such as insects or litter enter the outdoor unit, a 
short-circuit may be caused inside the control box.)

6-5 Heat insulation of piping

• Make sure to insulate the field piping (on both the liquid line and gas 

line) and refrigerant branching kit.
(If they are not insulated, water leakage may be caused.)

(The maximum temperature of the piping on the gas line is about 
248 °F during heating operation.  Use an insulation sufficiently resis-
tant to this temperature.)

• Reinforce the refrigerant piping according to the installation environ-

ment. If it is not reinforced, condensate may form on the surface of 
the insulation.

WARNING

• Make sure to insulate the field piping up to the piping connection 

area inside the unit.  If the piping is exposed, dew condensation and 
burn by contact may be caused.

6-6 Airtight test and vacuum drying

The unit has been checked for leaks by the manufacturer.
Confirm that the valves are firmly closed before airtight test or vacuum-
drying.
To prevent entry of any impurities and insure sufficient pressure resis-
tance, always use the special tools dedicated for R410A.

Perform the following inspections securely after the piping work.

Airtight test

 - Make sure to use nitrogen gas. (For the service port 

position, refer to the figure in 

“Stop valve operation method”

.)

[Procedure]  Pressurize the air conditioner from the liquid pipe and 
gas pipe up to 450 psi (Make sure not to exceed 450 psi).  When the 
pressure does not drop for 24 hours, the piping work shall be 
accepted.  
If the pressure drops, check for leakage positions. (Confirm that 
there is no leakage, then release nitrogen.)

Vacuum drying

 - Use a vacuum pump which can evacuate up to 

–14.6 psi or less.
[Procedure] Operate the vacuum pump for evacuation for 2 hours or 
more using both liquid pipe and gas pipe until the vacuum pressure 
reaches –14.6 psi or less.  Leave the air conditioner at –14.6 psi or 
less for 1 hour or more, and confirm that the vacuum pressure indi-
cated by the vacuum gage does not increase.
(If the vacuum pressure increases, the system may contain moisture 
or have leakage.)

If there is a possibility of moisture remaining in the piping

 (for 

example, when there is a possibility of dew condensation inside the pip-
ing because the piping work was performed in the rainy season or over 
a long period of time, or when rainwater may have entered the piping 
during the work)
Perform evacuation described above for 2 hours (vacuum drying), pres-
surize the air conditioner up to 7 psi (vacuum break) with nitrogen gas, 
then evacuate the air conditioner using the vacuum pump for 1 hour to 
achieve –14.6 psi or less (vacuum drying).
(If the vacuum pressure does not reach –14.6 psi or less even after 
evacuation for 2 hours or more, repeat vacuum break and vacuum dry-
ing.) Leave the air conditioner in the vacuum status for 1 hour or more, 
and confirm that the vacuum pressure indicated by the vacuum gauge 
does not increase.

6-7 Additional refrigerant charge

WARNING

• To avoid injury always use protective gloves and eye protection when 

charging refrigerant.

• To avoid injury do not charge with unsuitable substances. Use only 

the appropriate refrigerant.

NOTE

• Refrigerant cannot be charged until field wiring has been completed.

Refrigerant may only be charged after performing the airtight test
and the vacuum drying (see above).
When charging refrigerant into the system, take care that its maxi-
mum allowable charge is never exceeded, in view of the danger of
liquid hammer.
Refrigerant containers shall be opened slowly.
To avoid compressor breakdown, do not charge the refrigerant more
than the specified amount to raise the condensing pressure.

This outdoor unit is factory charged with refrigerant.

• Charge the additional refrigerant calculated by the formula below.

Record the additional amount to the label stuck on the back of front 
panel.

Charge the refrigerant to the liquid pipe in its liquid state. Since R410A
is a mixed refrigerant, its composition changes if charged in a state of
gas and normal system operation would no longer be assured.

Before filling, check whether the tank has a siphon attached or not.

How to fill a tank with a siphon attached.

Other ways of filling the tank

After the vacuum drying is finished, charge the additional refrigerant
in its liquid state through the liquid stop valve service port. 
Taking into account following instructions:

1.

Check that gas and liquid stop valves are closed.

2.

Charge the specified amount of refrigerant.

Cautions on connecting the connection piping

Terminal cover

 Insulation

Bolt

Caulking, etc.

Compressor

Liquid piping

Putty or heat 
insulating material 
(arranged in local field)

Additional charging amount

=

Liquid piping length × 0.036

(lb.)

(ft.)×0.036

There is a siphon tube
inside, so there is no need
to turn the tank upside-down.

Fill with the tank upright.

Fill with the tank upside-down.

01_EN_3PN07193-7H.fm  Page 9  Monday, December 27, 2010  4:30 PM

Summary of Contents for SkyAir RZQ36PVJU9

Page 1: ...l installation Conserver ce manuel à portée de main pour référence ultérieure Ce manuel doit être donné au propriétaire de l équipement Lea cuidadosamente estas instrucciones antes de instalar Guarde este manual en un lugar a mano para leer en caso de tener alguna duda Este manual debe permanecer con el propietario del equipo SPLIT SYSTEM Air Conditioners INSTALLATION MANUAL English Français Españ...

Page 2: ...lt in water leakage elec tric shock or fire When installing the unit in a small room take measures to keep the refrigerant concentration from exceeding allowable safety limits Excessive refrigerant leaks in the event of an accident in a closed ambient space can lead to oxygen deficiency Use only specified accessories and parts for installation work Failure to use specified parts may result in wate...

Page 3: ... the air or where volatile flammables such as thinner or gasoline are handled Oper ating the unit in such conditions can cause a fire Take adequate measures to prevent the outdoor unit from being used as a shelter by small animals Small animals making con tact with electrical parts can cause malfunctions smoke or fire Instruct the customer to keep the area around the unit clean NOTE Install the po...

Page 4: ...wind whose velocity is 11 mph or more blows to the out door unit from the air outlet side the air flow rate of the outdoor unit is reduced the outlet air is sucked again short circuit and the following effect may be caused The capacity is deteriorated The adhered frost increases during heating operation The operation is stopped by pressure rise If excessive strong wind continuously blows from the ...

Page 5: ...conduit and servicing between the units A When an obstruction is present on the air inlet side When the upward area is open 1 When one outdoor unit is installed individually When an obstruction is present only on the air inlet side When an obstruction is present on the both sides 2 When two or more outdoor units are installed side by side When an obstruction is present on the both sides When an ob...

Page 6: ...tdoor unit is installed individually The dimensional relationship between H L and A is as shown in the table below NOTE Close the area under the frame so that the outlet air does not bypass there 2 When only two outdoor units are installed side by side The dimensional relationship between H L and A is as shown in the table below NOTE 1 Close the area under the frame so that the outlet air does not...

Page 7: ... Only two outdoor units can be installed side by side D When outdoor units are stacked 1 When an obstruction is present on the air outlet side NOTE 1 Only two outdoor units can be stacked 2 About 4 in is required as the drain piping size for the upper outdoor unit 3 Close the area Z gap between the upper outdoor unit and the lower outdoor unit so that the outlet air does not bypass there 2 When an...

Page 8: ...g nut 3 Remove the transportation metal and the washer as shown in the above figure 4 Return and tighten the fixing nut again 5 Return the sound proof cover to achieve the former status CAUTION If the unit is operated with the transportation metal attached abnor mal vibration or sound may be generated 6 REFRIGERANT PIPING WORK CAUTION To piping technician Make sure to open the stop valves after fi...

Page 9: ...rigerant other than the specified refrigerant enter the refrigerant system Do not let any gas such as air enter the refrigerant system Precautions when connecting the piping See the following table for flare dimensions When connecting the flare nuts apply refrigerant oil to the inside and outside of the flares and turn them three or four times at first Use ester oil or ether oil See the following ...

Page 10: ...vacuum pressure indi cated by the vacuum gage does not increase If the vacuum pressure increases the system may contain moisture or have leakage If there is a possibility of moisture remaining in the piping for example when there is a possibility of dew condensation inside the pip ing because the piping work was performed in the rainy season or over a long period of time or when rainwater may have...

Page 11: ... a hexagon wrench into the valve stem and turn the valve stem clockwise 2 When the valve stem cannot be turned any more stop turning Now the valve is closed The valve is sealed in the arrow area Take care not to damage the arrow area After handling the valve make sure to tighten the valve cap securely Use charge hose equipped with push in the work After the work make sure to tighten the valve cap ...

Page 12: ...supply wiring and transmission wiring Let the power supply wiring and transmission wiring with a conduit pass through one of the knockout holes on the front or side piping cover and let the transmission wiring with a conduit pass through another knockout hole For protection from uninsulated live parts thread the power supply wiring and the transmission wiring through the included insulation tube a...

Page 13: ...le below for tightening torque for the terminal screws Model Phase and frequency Voltage Max Overcurrent Protective device Min Circuit Amps RZQ30PVJU9 60Hz 208 230V 30A 27A RZQ36PVJU9 RZR36PVJU RZQ42PVJU9 RZR42PVJU Screw Remove it and open the cover Control box Terminal block Stop valve mounting plate Knockout hole Power supply wiring including ground wire or transmission wiring Power supply wirin...

Page 14: ...RK 5 Piping size and heat insulation Refer to 6 1 Selection of piping material 6 5 Heat insulation of piping 6 Check of stop valve Confirm that the stop valve is open on both the liquid line and gas line 7 Record of amount of additional refrigerant Record the amount on the label stuck on the back of the front panel 8 Measurement of insulation in main power circuit Use the megatester for 500 V Do n...

Page 15: ...outdoor unit may continue to operate for a further 3 minutes If the system has not undergone the check operation by the test run button since it was first installed a malfunction code U3 is dis played In this case perform the check operation by referring to 9 1 Power on and check operation Make sure to turn on the power 6 hours before starting operation for supplying the power to the crankcase hea...

Page 16: ...top valves in the outdoor unit remain closed Open the stop valve on both the gas and liquid lines The refrigerant is overcharged Calculate again the required amount of refrigerant to be charged based on the piping length recover the refrigerant using the refrigerant recovery device then achieve proper amount of refrigerant E4 F3 The stop valves in the outdoor unit remain closed Open the stop valve...

Page 17: ...ons in steps 1 and 2 above 4 Deal with the situations where the result exceeds the maximum con centration level Where the installation of a facility results in a concentration in excess of the maximum concentration level then it will be necessary to revise the system Please consult your dealer total amount of refrigerant in the system maximum concen tration level lb ft 3 volume ft 3 of the room in...

Page 18: ... 1101 HT 3PN07193 7H EM10A070 00_CV_3PN07193 7H fm Page 2 Saturday December 25 2010 1 03 PM ...

Reviews: