background image

English

11

(Refer to figure 26)

1.

R410A Tank (Siphon system)

2.

Measuring instrument

3.

Valve A

4.

Indoor unit

5.

Stop valve service port

6.

Gas line stop valve

7.

Outdoor unit

8.

Liquid line stop valve

3.

Close valve A after charging is complete.

Note: If all the refrigerant to be added cannot be charged using the 

above procedure, re-charge the refrigerant as below.

If all the refrigerant could not be added

Add refrigerant referring to the “Service Precautions” plate attached to 
the outdoor unit for details on the settings for adding refrigerant.

9.

POST-WORK CHECKS

Perform the following checks after work is complete.
(1) Drain pipe connection, removal of transport bracket 

 See “

5. PRECAUTIONS ON INSTALLATION

”. 

(2) Incorrect power supply wiring, loose screws 

 

See “

7-3 How to connect the power supply wiring

”.

(3) Incorrect transmission wiring, loose screws 

 

See “

7-4 Transmission wiring connection procedure

”.

(4) Incorrect refrigerant piping connections 

 

See “

6. REFRIGERANT PIPING

”.

(5) Piping sizes, use of insulation 

 

See: “

6-2 Selecting piping material

”.

6-6 Thermal insulation of piping

”.

(6) Stop valve check 

 

Make sure both the liquid-side and gas-side stop valves are open.

(7) Record of Amount of Refrigerant Added 

 

Record it on “Record of Amount of Refrigerant Added” on the “Ser-
vice Precautions” label.

(8) Measuring the insulation of the main power circuit 

 

• Use a 500V mega-tester. 
• Do not use the mega-tester for low voltage other than 208/230V. 

(Transmission wiring)

CAUTION

To the piping installer

After completing installation, be sure to open the valves.
(Operating the unit with the valve shut will break the compressor.)

10. TEST OPERATION

This unit is equipped with a crank case heater to ensure smooth 
startup. Be sure to turn the power on at least 6 hours before oper-
ation in order to have power running to the crank case heater.

WARNING

When leaving the unit with the power on, be sure to switch 
with another person doing the installation or close the front 
panel.

Precautions before turning the power on

• Using insulating sheets, tape electric parts as described in the “Ser-

vice Precautions” label on the back of the front panel.

• The indoor unit connected to the outdoor unit operates automatically. 

Complete work on the indoor unit in order to ensure maximum safety.

10-1 Power On–Check Operation

• Make sure to perform the check operation after installation. 

(If the air conditioner is operated using the indoor remote controller 
without performing the check operation, the malfunction code “U3” is 
displayed in the indoor remote controller, and normal operation is 
disabled.)

• When making settings on the outdoor unit PC board (A1P or A2P) 

after turning the power on, do not touch anything other than the 
push-button switches and dip switches. 
(See the “Service Precautions” label for the locations of the push-
button switches (BS1-5) and dip switches (DS1-1, 2) on the PC 
board (A1P or A2P).)

• During the operation, monitor the outdoor unit operation status and 

check for any incorrect wiring.

<Precautions During Check Operation>

If operation is performed within 12 minutes of the indoor and 
outdoor units being turned on, H2P will light up, and the com-
pressor will not run.

Only perform operation after checking that the LED display is as 
shown in “

10-1 Power On–Check Operation

” 2. table.

• In order to ensure uniform refrigerant distribution, it may take up to 

around 10 minutes for the compressor to start up after the unit 
begins running. This is not a malfunction.

• The check operation cannot be performed in other modes.
• If the discharge pipe thermistor (R2T), the suction pipe thermistor 

(R3T), and the pressure sensors (S1NPH and S1NPL) are removed 
before operation, the compressor might burn out, so avoid this under 
all circumstances.

State of valve A and the stop valve

Valve A

Liquid 

line stop 

valve

Gas line 

stop 

valve

Before starting to charge the refrigerant

Close

Close

Close

During charging of the refrigerant

Open

Close

Close

1. Close the outdoor unit’s front panel.
 

Turn the power

 on for the outdoor 

  unit and the indoor unit.

2.  • Open the outdoor unit’s front panel.
  • Make sure the LED display on the outdoor unit’s PC board (A1P or A2P) is 
      as shown in the following table. 

6. Close the front panel of the outdoor unit after check operation is complete.

Do not leave any stop valve closed 
otherwise the compressor will fail.

Caution

Be sure to turn the power on at least 
6 hours before operation in order to have 
power running to the crank case heater.

To avoid the risk of electric shock, do not touch anything other than the 
push-button switches on the PC board (A1P or A2P) when making settings.

Caution

LED display 
(Default status 
before delivery)

HAP

<30~48 type>

A1P

H1P

H2P

H3P

H4P

H5P

H6P

H7P

LED display 
(Default status 
before delivery)

HAP

<18·24 type>

A2P

A1P

H1P

H2P

H3P

H4P

H5P

H6P

H7P

LED display:     OFF      ON      Blinking

Use caution to avoid electric shock while 
working, since the outdoor unit is on.

•  Only set the push-button switches (BS1-5) 

after making sure the operation pilot lamp on 
PC board is lit up.

•  See the “Service Precautions” label on the 

back side of the front panel for details on how 
to make the settings. 

  (Do not forget to write the settings down on 

the “Service Precautions” label.)

•  The dip switch (DS1-1) does not need to be 

set, so do not touch it. 

  Doing so may cause malfunction.

• If you have to leave the outdoor unit during 

check operation, either switch with another 
worker or close the front panel. 

• The system operates for about 30 minutes 

(60 minutes at maximum) and automatically 
stops the check operation.

• The system can start normal operation about 

3 minutes 

after the check operation if

 the 

remote controller does not display any 
malfunction code.
The remote controller will show the test 
operation display during check operation. 

3.  • When the customer requests
    quiet operation or demand
    operation, make these settings
    using the push-button switches
    (BS1-5) on the outdoor unit’s
    PC board (A1P or A2P).
  • Operate the push-button
    switches through the opening
    after protecting it with an
  insulation 

cover. 

    (See the “Service Precautions”
    label for details.)

4.  • Check that the liquid and gas-side
    stop valves are open, and if
    they are closed, open them.

5. Press the test operation button 
  (BS4) for at least five seconds and 
  perform check operation. 
  For details, see “How to perform
  check operation” on the “Service
 Precautions” 

label.

01_EN_3P435164-5M.fm  Page 11  Monday, October 15, 2018  3:35 PM

Summary of Contents for SkyAir RZQ24TAVJU

Page 1: ...ce This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au...

Page 2: ...1000 or more 20 500 or less 20 500 or less 40 1000 or more 40 1000 or more 8 200 or more 4 100 or more 4 100 or more 12 300 or more inch mm figure 5 figure 6 1 2 3 4 20 500 or more 4 100 or more 4 100...

Page 3: ...4 100 or more 40 1000 or more 60 1500 or more 8 200 or more 24 600 or more 120 3000 or more 4 100 or more 4 100 or more 80 2000 or more 1 13 16 20 inch mm 1 2 7 3 4 6 5 figure 9 figure 10 figure 11 fi...

Page 4: ...1 2 3 IN D OUT D F1F2 F1F2 L1 L2 F1 IN D OUT D F2 F1 F2 F1 F2 4 1 2 3 4 5 6 7 11 8 9 10 1 2 3 4 5 6 7 8 figure 26 figure 22 2 7 8 3 6 4 5 5 4 1 2 8 7 8 4 2 6 18 24 type 3 1 Conduit mounting plate acc...

Page 5: ...ious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe shock hazard resulting in severe injury or death Addition...

Page 6: ...tdoor use Do not install the air conditioner or heat pump in the following locations a Where a mineral oil mist or oil spray or vapor is produced for example in a kitchen Plastic parts may deteriorate...

Page 7: ...ainst the outdoor unit s exhaust cause a deterioration in the system performance High winds force re circulation of the exhaust air into the inlet which is known to cause the following effects Reducti...

Page 8: ...ir inlet and on both sides of the unit Refer to figure 5 2 2 In case of installing multiple units 2 units or more in lateral connec tion per row In case obstacles exist in front of the air inlet and o...

Page 9: ...ent It is best to screw in the foundation bolt until their length remains 13 16 in 20 mm above the foundation surface Refer to figure 11 1 Diagram of lower surface Drain pipe installation Locations wh...

Page 10: ...copper piping through the through holes and when passing them out to the outside 6 4 Pipe connection See Stop valve operation procedure in 6 7 Air tight test and vac uum drying regarding handling of...

Page 11: ...ture that the gas side piping can reach is around 248 F 120 C so be sure to use insulating material which is sufficiently resistant to this temperature CAUTION For local insulation be sure to insulate...

Page 12: ...y a certified professional Follow the Wiring diagram label when carrying out any electrical wiring Only proceed with wiring work after turning off all power Make sure the ground resistance is no great...

Page 13: ...ck of unit 4 Knockout 5 Side of unit 6 Front of unit 7 Terminal block 8 Control Box Precautions when laying power supply wiring Wiring of different thicknesses cannot be connected to the power supply...

Page 14: ...manual Piping Wiring Air tight test Vacuum drying 8 2 Checking the refrigerant tank Charge the refrigerant to the liquid pipe in its liquid state Since R410A is a mixed refrigerant its composition ch...

Page 15: ...door and outdoor units being turned on H2P will light up and the com pressor will not run Only perform operation after checking that the LED display is as shown in 10 1 Power On Check Operation 2 tabl...

Page 16: ...Y SAVING AND OPTIMUM OPERATION The unit is equipped with advanced energy saving functionality Depending on the priority emphasis can be put on energy saving or comfort level Several parameters can be...

Page 17: ...condition which is defined by the operation method above To activate the powerful comfort setting under cooling opera tion change field setting 2 41 3 This setting is used in conjunction with setting...

Page 18: ...e evolution A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during heating A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36...

Page 19: ...h k h k Mode 6 k h h h k k h Type Description Actions Field setting Shorted between Heating Thermo on Heating Thermo off Heater Fan Heater Fan I Heat pump heating is always locked out 2 16 ON ON ON H...

Page 20: ...ated to outdoor units No Setting item display Setting condition display Setting item MODE H1P TEST H2P C H selection Low noise H6P Demand H7P IND H3P Master H4P Slave H5P Factory setting 57 Heat pump...

Page 21: ...asement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the maximum concentration level in accordance with steps 1 to 4 below an...

Page 22: ...1810 3P435164 5M EM18A002A HT...

Reviews: