background image

12

English

10-2 Temperature control operation checklist

• After check operation is complete, check the temperature control 

using normal operation.
(Heating is not possible if the outdoor temperature is 75°F (24°C) or 
higher.)
(1) Make sure the indoor and outdoor units are operating normally.

(If liquid compression by the compressor or other abnormal 
noises can be heard, stop the unit immediately, heat the crank 
case for a sufficient amount of time, and try again.)

(2) Check to see if cold (or hot) air is coming out of the indoor unit.
(3) Press the fan direction and fan speed buttons on the indoor unit 

to see if they operate properly.

<Precautions during temperature control checks>

• For around 5 minutes after the compressor stops, the compressor 

will not run even if the “On/Off” button on the remote controller is 
pressed.

• When the system operation is stopped by the remote controller, the 

outdoor unit may continue operating for up to 1 minute.

• Malfunction code “U3” is displayed if check operation is not per-

formed using the test operation button the first time after installation. 
Perform the check operation in accordance with “

10-1 Power On–

Check Operation

”.

[Remote controller displays malfunction code]
(Check on a remote controller)

• When using a central controller, see the installation manual or ser-

vice manual which came with the central controller.

[If nothing is displayed on the remote controller]

• There might be a problem with the connections or communication 

between the indoor unit and the remote controller.
Make sure all the wiring is properly connected.

CAUTION

To the piping installer, To the electrician

After the test operation, when handing the unit over to the customer, 
make sure the front panel on the unit and all screws are attached.

10-3 Final refrigerant charge adjustment

It is not necessary to do this final adjustment normally, but perform the 
following operation only when the most adequate refrigerant charge for 
the best performance is required and the piping length between the out-
door and indoor units is less than 50 ft. (15 m).
The outdoor temperature must be between 65°F (18°C) and 105°F (40°C).

The number of revolutions of the compressor must be greater than or 
equal to the charge mode. (It can be confirmed by LED display on PC 
board)

The number of revolutions of the compressor LED display.

 :Chargeable  

 :Impossible to charge)

Run the system for 60 minutes in cooling by the forced operation using 
the field setting mode 2, No.20 LED 

:ON, mode 2, No.7 LED 

:ON, 

(Refer to Service Manual.) to allow pressures to stabilize.

Check subcooling of outdoor unit at LSV. Systems should have the tar-
get subcooling in the table below.

a. If the subcooling is low, add charge little by little to raise subcooling 

to the target value. (The maximum additional charge is 2.2 lbs. (1kg))

b. If the subcooling is high, remove charge to lower the subcooling to 

the target value.

11. ENERGY SAVING AND OPTIMUM 

OPERATION

The unit is equipped with advanced energy saving functionality. 
Depending on the priority, emphasis can be put on energy saving or 
comfort level. Several parameters can be selected, resulting
in the optimal balance between energy consumption and comfort for the 
particular application.

Several patterns are available and explained below. Modify the param-
eters to the needs of your building and to realize the best balance 
between energy consumption and comfort.

Refer to Service Manual for changing the field settings.
Setting definition: [A-B]=C; A=mode, B=setting NO., C=setting value.

Malfunc-

tion code

Installation error

Remedial action

E3

The stop valve of outdoor unit 
is left closed.

Open the gas-side stop valve and the liq-
uid-side stop valve.

Refrigerant overcharge.

Recalculate the required amount of refrig-
erant from the piping length and correct 
the refrigerant charge level by recovering 
any excessive refrigerant with a refriger-
ant recovery unit.

F6

Refrigerant overcharge.

Recalculate the required amount of refrig-
erant from the piping length and correct 
the refrigerant charge level by recovering 
any excessive refrigerant with a refriger-
ant recovery unit.

E4

The stop valve of outdoor unit 
is left closed.

Open the gas-side stop valve and the liq-
uid-side stop valve.

Insufficient refrigerant.

Check if the additional refrigerant charge 
has been finished correctly.

Recalculate the required amount of refrig-
erant from the piping length and add an 
adequate amount of refrigerant.

F3

Refrigerant overcharge.

Recalculate the required amount of refrig-
erant from the piping length and correct 
the refrigerant charge level by recovering 
any excessive refrigerant with a refriger-
ant recovery unit.

The stop valve of outdoor unit 
is left closed.

Open the gas-side stop valve and the liq-
uid-side stop valve.

Insufficient refrigerant.

Check if the additional refrigerant charge 
has been finished correctly.

Recalculate the required amount of refrig-
erant from the piping length and add an 
adequate amount of refrigerant.

U2

Insufficient power supply volt-
age

Check to see if the power supply voltage 
is supplied properly.

U3

If check operation has not been 
performed.

Perform check operation.

U4

No power is supplied to out-
door unit.

Turn the power on for the outdoor 
unit.

UA

If no dedicated indoor unit is 
being used.

Check the indoor unit. If it is not a dedi-
cated unit, replace the indoor unit.

UF

The stop valve of outdoor unit is 
left closed.

Open the gas-side stop valve and the liq-
uid-side stop valve.

If the right indoor unit piping and 
wiring are not properly con-
nected to the outdoor unit.

Make sure that the right indoor unit piping 
and wiring are properly connected to the 
outdoor unit.

UH

If the transmission wiring has 
not be connected or it has 
shorted.

Make sure the transmission wiring is cor-
rectly attached to terminals (X2M) F1/F2 
(TO IN/D UNIT) on the outdoor unit circuit 
board.

Model

Target subcooling

18·24 type

6±1°F (3.33±0.56°C)

30·36 type

7±1°F (3.89±0.56°C)

42 type

8±1°F (4.44±0.56°C)

48 type

9±1°F (5.00±0.56°C)

01_EN_3P435164-5M.fm  Page 12  Monday, October 15, 2018  3:35 PM

Summary of Contents for SkyAir RZQ24TAVJU

Page 1: ...ce This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au...

Page 2: ...1000 or more 20 500 or less 20 500 or less 40 1000 or more 40 1000 or more 8 200 or more 4 100 or more 4 100 or more 12 300 or more inch mm figure 5 figure 6 1 2 3 4 20 500 or more 4 100 or more 4 100...

Page 3: ...4 100 or more 40 1000 or more 60 1500 or more 8 200 or more 24 600 or more 120 3000 or more 4 100 or more 4 100 or more 80 2000 or more 1 13 16 20 inch mm 1 2 7 3 4 6 5 figure 9 figure 10 figure 11 fi...

Page 4: ...1 2 3 IN D OUT D F1F2 F1F2 L1 L2 F1 IN D OUT D F2 F1 F2 F1 F2 4 1 2 3 4 5 6 7 11 8 9 10 1 2 3 4 5 6 7 8 figure 26 figure 22 2 7 8 3 6 4 5 5 4 1 2 8 7 8 4 2 6 18 24 type 3 1 Conduit mounting plate acc...

Page 5: ...ious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe shock hazard resulting in severe injury or death Addition...

Page 6: ...tdoor use Do not install the air conditioner or heat pump in the following locations a Where a mineral oil mist or oil spray or vapor is produced for example in a kitchen Plastic parts may deteriorate...

Page 7: ...ainst the outdoor unit s exhaust cause a deterioration in the system performance High winds force re circulation of the exhaust air into the inlet which is known to cause the following effects Reducti...

Page 8: ...ir inlet and on both sides of the unit Refer to figure 5 2 2 In case of installing multiple units 2 units or more in lateral connec tion per row In case obstacles exist in front of the air inlet and o...

Page 9: ...ent It is best to screw in the foundation bolt until their length remains 13 16 in 20 mm above the foundation surface Refer to figure 11 1 Diagram of lower surface Drain pipe installation Locations wh...

Page 10: ...copper piping through the through holes and when passing them out to the outside 6 4 Pipe connection See Stop valve operation procedure in 6 7 Air tight test and vac uum drying regarding handling of...

Page 11: ...ture that the gas side piping can reach is around 248 F 120 C so be sure to use insulating material which is sufficiently resistant to this temperature CAUTION For local insulation be sure to insulate...

Page 12: ...y a certified professional Follow the Wiring diagram label when carrying out any electrical wiring Only proceed with wiring work after turning off all power Make sure the ground resistance is no great...

Page 13: ...ck of unit 4 Knockout 5 Side of unit 6 Front of unit 7 Terminal block 8 Control Box Precautions when laying power supply wiring Wiring of different thicknesses cannot be connected to the power supply...

Page 14: ...manual Piping Wiring Air tight test Vacuum drying 8 2 Checking the refrigerant tank Charge the refrigerant to the liquid pipe in its liquid state Since R410A is a mixed refrigerant its composition ch...

Page 15: ...door and outdoor units being turned on H2P will light up and the com pressor will not run Only perform operation after checking that the LED display is as shown in 10 1 Power On Check Operation 2 tabl...

Page 16: ...Y SAVING AND OPTIMUM OPERATION The unit is equipped with advanced energy saving functionality Depending on the priority emphasis can be put on energy saving or comfort level Several parameters can be...

Page 17: ...condition which is defined by the operation method above To activate the powerful comfort setting under cooling opera tion change field setting 2 41 3 This setting is used in conjunction with setting...

Page 18: ...e evolution A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during heating A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36...

Page 19: ...h k h k Mode 6 k h h h k k h Type Description Actions Field setting Shorted between Heating Thermo on Heating Thermo off Heater Fan Heater Fan I Heat pump heating is always locked out 2 16 ON ON ON H...

Page 20: ...ated to outdoor units No Setting item display Setting condition display Setting item MODE H1P TEST H2P C H selection Low noise H6P Demand H7P IND H3P Master H4P Slave H5P Factory setting 57 Heat pump...

Page 21: ...asement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the maximum concentration level in accordance with steps 1 to 4 below an...

Page 22: ...1810 3P435164 5M EM18A002A HT...

Reviews: