background image

8

English

(Refer to figure 21)

1.

Decompression valve

2.

Nitrogen

3.

Vacuum pump

4.

Valve (Open)

5.

Charge hose

6.

Stop valve service port

7.

Indoor unit

8.

Gas line stop valve (Close)

9.

Liquid line stop valve (Close)

10.

Indicates local procurement

11.

Outdoor unit

NOTE

The stop valve must always be turned to “closed”. 
Otherwise the refrigerant in the outdoor unit will pour out.

• The names of parts needed to operate the stop valve are shown in 

the figure below. The unit is shipped from the factory with the stop 
valve turned to the “closed” position.

• Since the side boards may be deformed if only a torque wrench is 

used when loosening or tightening flare nuts, always lock the stop 
valve with a wrench and then use a torque wrench.

• In cases where the unit is run in heating mode when the outside tem-

perature is low or in other situations where the operating pressure 
might drop, seal the gas-side flare nut on the stop valve with silicon 
sealant or the like to prevent it from freezing.

Stop valve operation procedure

Have a hex wrench ready (size: 0.2 in. (4 mm) and 0.3 in. (6 mm)).

Opening the valve

1.

Place the hex wrench on the valve stem and turn counter-clockwise.

2.

Stop when the valve stem no longer turns. It is now open.

Close the valve

1.

Place the hex wrench on the valve stem and turn clockwise.

2.

Stop when the valve stem no longer turns. It is now closed.

• A seal is attached to the point indicated by the arrow.

Take care not to damage it.

• Be sure to tighten the valve cap securely after operating the valves.

• Use a push-rod-provided charging hose for operation.
• Be sure to tighten the valve cap securely after operation.

Tightening torque ................. 8.5 ~ 10.3 ft·lbf (10.8 ~ 14.7 N·m)

7.

ELECTRIC WIRING

CAUTION

To the electrician

• Do not operate until refrigerant piping work is completed.

(Failure to adhere by this caution may lead to irreparable compres-
sor damage.)

7-1 Wiring connection example for whole system

• Electrical wiring work should be done by a certified professional.
• Follow the “Wiring diagram” label when carrying out any electrical 

wiring.
Only proceed with wiring work after turning off all power.

• Make sure the ground resistance is no greater than 4

.

• Ground the indoor and outdoor units.
• Do not connect the ground wire to gas pipes, sewage pipes, lightning 

rods, or telephone ground wires.

Gas pipes:

 can explode or catch fire if there is a gas leak.

Sewage pipes:

 no grounding effect is possible if hard plastic pip-

ing is used.

Telephone ground wires and lightning rods:

 dangerous when 

struck by lightning due to abnormal rise in electrical potential in the 
grounding.

• Use copper wire.
• When doing the electrical wiring, always shut off the power supply 

before working, and do not turn on the switch until all work is com-
plete.

• This unit has an inverter, so it must be grounded in order to reduce 

noise and prevent it affecting other appliances, and also to release 
any electrical build-up in the unit case due to leaked current.

• Do not install a power-factor improving phase-advancing capacitor 

under any circumstances.
(Not only will this not improve the power factor, but it might cause a fire.)

• Connect the wire securely using designated wire and fix it with 

attached clamp without applying external pressure on the terminal 
parts (terminal for power supply wiring, terminal for transmission wir-
ing and ground terminal). See “

7-3 How to connect the power sup-

ply wiring

”.

• Leftover wiring should not be wrapped and stuffed into the unit.
• Secure the wiring with the included clamp so that it does not come in 

contact with the piping or stop valve. 
(See “

7-3 How to connect the power supply wiring

”.)

Stop valve operation procedure

Precautions when handling the stop valve

Servicing port

Valve stem

Flare nut

Valve cap

Field piping connection

Silicon sealing pad

(Make sure that there is no gap)

Direction to open

Direction to open

<Gas pipe>

<Liquid pipe>

Precautions for handling valve cap

Liquid-side tightening torque

Gas-side tightening torque

10.0 ~ 12.2 ft·lbf

(13.5 ~ 16.5 N·m)

16.6 ~ 20.3 ft·lbf

(22.5 ~ 27.5 N·m)

Precautions for handling servicing port

Valve cap

Stop valve 
(cap attachment)

01_EN_3P435164-5M.fm  Page 8  Monday, October 15, 2018  3:35 PM

Summary of Contents for SkyAir RZQ24TAVJU

Page 1: ...ce This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au...

Page 2: ...1000 or more 20 500 or less 20 500 or less 40 1000 or more 40 1000 or more 8 200 or more 4 100 or more 4 100 or more 12 300 or more inch mm figure 5 figure 6 1 2 3 4 20 500 or more 4 100 or more 4 100...

Page 3: ...4 100 or more 40 1000 or more 60 1500 or more 8 200 or more 24 600 or more 120 3000 or more 4 100 or more 4 100 or more 80 2000 or more 1 13 16 20 inch mm 1 2 7 3 4 6 5 figure 9 figure 10 figure 11 fi...

Page 4: ...1 2 3 IN D OUT D F1F2 F1F2 L1 L2 F1 IN D OUT D F2 F1 F2 F1 F2 4 1 2 3 4 5 6 7 11 8 9 10 1 2 3 4 5 6 7 8 figure 26 figure 22 2 7 8 3 6 4 5 5 4 1 2 8 7 8 4 2 6 18 24 type 3 1 Conduit mounting plate acc...

Page 5: ...ious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe shock hazard resulting in severe injury or death Addition...

Page 6: ...tdoor use Do not install the air conditioner or heat pump in the following locations a Where a mineral oil mist or oil spray or vapor is produced for example in a kitchen Plastic parts may deteriorate...

Page 7: ...ainst the outdoor unit s exhaust cause a deterioration in the system performance High winds force re circulation of the exhaust air into the inlet which is known to cause the following effects Reducti...

Page 8: ...ir inlet and on both sides of the unit Refer to figure 5 2 2 In case of installing multiple units 2 units or more in lateral connec tion per row In case obstacles exist in front of the air inlet and o...

Page 9: ...ent It is best to screw in the foundation bolt until their length remains 13 16 in 20 mm above the foundation surface Refer to figure 11 1 Diagram of lower surface Drain pipe installation Locations wh...

Page 10: ...copper piping through the through holes and when passing them out to the outside 6 4 Pipe connection See Stop valve operation procedure in 6 7 Air tight test and vac uum drying regarding handling of...

Page 11: ...ture that the gas side piping can reach is around 248 F 120 C so be sure to use insulating material which is sufficiently resistant to this temperature CAUTION For local insulation be sure to insulate...

Page 12: ...y a certified professional Follow the Wiring diagram label when carrying out any electrical wiring Only proceed with wiring work after turning off all power Make sure the ground resistance is no great...

Page 13: ...ck of unit 4 Knockout 5 Side of unit 6 Front of unit 7 Terminal block 8 Control Box Precautions when laying power supply wiring Wiring of different thicknesses cannot be connected to the power supply...

Page 14: ...manual Piping Wiring Air tight test Vacuum drying 8 2 Checking the refrigerant tank Charge the refrigerant to the liquid pipe in its liquid state Since R410A is a mixed refrigerant its composition ch...

Page 15: ...door and outdoor units being turned on H2P will light up and the com pressor will not run Only perform operation after checking that the LED display is as shown in 10 1 Power On Check Operation 2 tabl...

Page 16: ...Y SAVING AND OPTIMUM OPERATION The unit is equipped with advanced energy saving functionality Depending on the priority emphasis can be put on energy saving or comfort level Several parameters can be...

Page 17: ...condition which is defined by the operation method above To activate the powerful comfort setting under cooling opera tion change field setting 2 41 3 This setting is used in conjunction with setting...

Page 18: ...e evolution A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during heating A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36...

Page 19: ...h k h k Mode 6 k h h h k k h Type Description Actions Field setting Shorted between Heating Thermo on Heating Thermo off Heater Fan Heater Fan I Heat pump heating is always locked out 2 16 ON ON ON H...

Page 20: ...ated to outdoor units No Setting item display Setting condition display Setting item MODE H1P TEST H2P C H selection Low noise H6P Demand H7P IND H3P Master H4P Slave H5P Factory setting 57 Heat pump...

Page 21: ...asement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the maximum concentration level in accordance with steps 1 to 4 below an...

Page 22: ...1810 3P435164 5M EM18A002A HT...

Reviews: