6L86(
7URXEOHVKRRWLQJE\(UURU&RGHV
3DUW6HUYLFH'LDJQRVLV
5HIHUHQFH
7URXEOHVKRRWLQJ
&+(&.
5HIHUWRSDJH
NO
NO
NO
YES
YES
Shut the power supply OFF after
connection and then restart.
Replace the electronic expansion
valve coil.
Replace the relay cables.
When restarting the operation after
shutting the power supply OFF
does not work, replace the indoor
unit main PCB (A1P).
NO
Replace the electronic expansion
valve main body.
Power is supplied.
YES
YES
Electronic
expansion valve is
connected to X7A
of indoor unit
PCB.
Relay cables short
circuit or
disconnected.
Check
of electronic
expansion valve coil
indicates normal.
CHECK 18
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.