Connect correctly.
Is the
connector (
!
1)
correctly connected?
NO
YES
Connect correctly.
Is
the limit
switch's connector
(
!
2) correctly
connected?
NO
Replace the indoor unit PCB.
Replace the indoor unit PCB.
208-230 VAC?
NO
YES
Does the
swing flap motor swing?
Does
continuity/no continuity
reverse?
NO
NO
Turn the power supply OFF
once and back ON, and check
whether the swing flap motor
swings when the power
supply is turned back ON.
Turn the power supply OFF
once and restart, and measure
the output voltage of connector
(
!
3) when the power supply is
restarted.
Disconnect the connector
(
!
2), turn the power supply
OFF once and restart, and
check if the limit switch has
continuity when the power
supply is restarted.
YES
YES
Replace the swing flap motor.
YES
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Caution
0RGHO
&RQQHFWRUIRUVZLQJIODSPRWRU
3&%
)+4
;$;$
;$
;$
$3
Summary of Contents for SkyAir RZQ-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811E...
Page 283: ...6L86 3DUW SSHQGL LULQJ LDJUDPV 2XWGRRU 8QLW QGRRU 8QLW Part 7 Appendix...
Page 284: ...LULQJ LDJUDPV 6L86 3DUW SSHQGL LULQJ LDJUDPV 2XWGRRU 8QLW 5 5 7 9 8 5 4 7 9 8 3D115455...
Page 285: ...6L86 LULQJ LDJUDPV 3DUW SSHQGL 5 5 7 9 8 5 4 7 9 8 3D115456...
Page 286: ...LULQJ LDJUDPV 6L86 3DUW SSHQGL QGRRU 8QLW 4 7 9 8 3D115647A...
Page 287: ...6L86 LULQJ LDJUDPV 3DUW SSHQGL 4 39 8 4 09 8 3D048116C...
Page 288: ...LULQJ LDJUDPV 6L86 3DUW SSHQGL 4 7 9 8 3D114844B...
Page 289: ...6L86 LULQJ LDJUDPV 3DUW SSHQGL 4 39 8 3D065984J...