Field Setting
SiUS28-902_B
56
Test Operation
3.2.4 Setting of Operation Control Mode from Remote Controller
(Local Setting)
The operation control mode is compatible with a variety of controls and operations by limiting
the functions of the operation remote controller. Furthermore, operations such as remote
controller ON/OFF can be limited in accordance with the combination conditions. (Refer to
information in the next page.)
Centralized controller is normally available for operations. (Except when centralized monitor is
connected)
3.2.5 Contents of Control Modes
Twenty modes consisting of combinations of the following 5 operation modes with temperature
and operation mode setting by remote controller can be set and displayed by operation modes 0
through 19.
ON/OFF control impossible by remote controller
Used when you want to turn ON/OFF by centralized remote controller only.
(Cannot be turned ON/OFF by remote controller.)
OFF control only possible by remote controller
Used when you want to turn ON by centralized remote controller only, and OFF by remote
controller only.
Centralized
Used when you want to turn ON by centralized remote controller only, and turn ON/OFF
freely by remote controller during set time.
Individual
Used when you want to turn ON/OFF by both centralized remote controller and remote
controller.
Timer operation possible by remote controller
Used when you want to turn ON/OFF by remote controller during set time and you do not
want to start operation by centralized remote controller when time of system start is
programmed.