Field Setting
SiUS28-902_B
68
Test Operation
Detailed Setting Procedure of Quiet Operation and Demand Control
1. Setting mode 1 (H1P off)
(1) In setting mode 2, press the BS1 (MODE button) 1 time.
Setting mode 1 is entered and
H1P off.
During the setting mode 1 is displayed, “In quiet operation” and “In demand control” are
displayed.
2. Setting mode 2 (H1P on)
(1) In setting 1, press and hold the BS1 (MODE button) for more than 5 seconds.
Setting
mode 2 is entered and H1P lights.
(2) Press the BS2 (SET button) several times and match the LED display with the Setting No.
you want.
(3) Press the BS3 (RETURN button) 1 time, and the present setting content is displayed.
Press the BS2 (SET button) several times and match the LED display with the setting
content (as shown on next page) you want.
(4) Press the BS3 (RETURN button) 2 times.
Returns to
.
(5) Press the BS1 (MODE button) 1 time.
Returns to the setting mode 1 and turns H1P off.
: ON
: OFF
l
: Blink
(1)
(2)
(3)
: Factory setting
Setting
No.
Setting
contents
Setting No. indication
Setting No. indication
Setting
contents
Setting contents indication (Initial setting)
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
H1P H2P H3P H4P H5P H6P H7P
12
External
low noise /
Demand
setting
NO
l
YES
l
22
Low night
noise
operation
setting
OFF
Mode 1
l
Mode 2
l
Mode 3
l
l
26
Low night
noise
operation
start setting
PM 8:00
l
PM 10:00
l
PM 0:00
l
27
Low night
noise
operation
end setting
AM 6:00
l
AM 7:00
l
AM 8:00
l
29
Capacity
priority
setting
Low noise
precedence
l
Capacity
precedence
l
30
Demand
setting 1
60 % of
rated power
consumption
l
70 % of
rated power
consumption
l
80 % of
rated power
consumption
l
32
Normal
demand
setting
OFF
l
ON
l
Setting mode indication section
Setting No. indication section
Set contents indication section