![background image](http://html1.mh-extra.com/html/daikin/skyair-alpha-series/skyair-alpha-series_technical-data-manual_3829037011.webp)
3
2
• Split - Sky Air • RZAG-MV1
9
• Outdoor Unit • RZAG-MV1
2
Specifications
Notes
(1) Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m (horizontal); level difference: 0m
(2) Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
Space heating
(Average climate)
Capacity
Pdesign
kW
9.52
SCOP/A
4.08
SCOPnet/A
4.08
η
s,h
%
160
Annual energy consumption
kWh/a
3,267
Required back up heating cap at design
conditions
kW
0.00
TOL
Tol (temperature
operating limit)
°C
-10
Pdh (declared
heating cap)
kW
9.52
COPd (declared COP)
1.86
Power input
kW
5.11
TBivalent
Tbiv (bivalent
temperature)
°C
-10
Pdh (declared
heating cap)
kW
9.52
COPd (declared COP)
1.86
Power input
kW
5.11
A Condition (-7°C)
Pdh (declared
heating cap)
kW
8.42
COPd (declared COP)
2.36
Power input
kW
3.56
B Condition (2°C)
Pdh (declared
heating cap)
kW
5.13
COPd (declared COP)
4.31
Power input
kW
1.19
C Condition (7°C)
Pdh (declared
heating cap)
kW
3.61
COPd (declared COP)
5.03
Power input
kW
0.72
D Condition (12°C)
Pdh (declared
heating cap)
kW
4.22
COPd (declared COP)
6.36
Power input
kW
0.66
Cooling
Cdc (Degradation cooling)
0.25
Heating
Cdh (Degradation heating)
0.25
Cooling function included
Yes
Heating function included
Yes
Average climate included
Yes
Cold season included
No
Warm season included
No
Ecolabel logo
No
Power consumption in
other than active
mode
Off mode
POFF
W
15
Standby mode
Cooling PSB
W
15
Heating PSB
W
15
Thermostat-off
mode
PTO
Heating W
15
Cooling W
0
Crankcase heater
mode
PCK
W
0
Indication if the heater is equipped with a supplementary heater (pair
application)
No
2-4 Capacity and Power input
FDA125A/RZAG125MV1