3
10
• Split - Sky Air • RZAG-MV1
37
• Outdoor Unit • RZAG-MV1
10
Wiring diagrams
10 - 1 Wiring Diagrams - Single Phase
4D109936
RZAG71MV1, RZASG100MV1, AZAS100MV1
NOTES
1. Refer to the wiring diagram sticker (on the back of the front plate)
for how to use the BSI~BS3 and DS1 switches.
2. When operating, do not short-circuit protection device(s) S1PH,
S1PL and Q1E.
3. Refer to the combination table and the option manual for how to
connect the wiring to X6A, X28A and X77A.
4. Colours: BLK: Black, RED: Red, BLU: Blue, WHT: White, GRN:
Green.
5. Windings: L-N: 2 - Earth: 1
LEGEND
Part n°
Description
A1P
Printed circuit board (main)
BS1~3 (A1P)
Push-button switch
DS1 (A1P)
Dipswitch
E1~3 (AAP)
Connector
E1H
*
Bottom plate heater
F1U (A1P)
Fuse T 31,5 A 250 V
F2U (A1P)
Fuse T 6,3 A 250 V
F3U (A1P)
Fuse T 6,3 A 250 V
F6U (A1P)
Fuse T 5 A 250 V
F8~9U
*
Fuse F 1 A 250 V
HAP (A1P)
Light-emitting diode (service monitor is green)
K1R (A1P)
Magnetic relay (Y1S)
K2R (A1P)
Magnetic relay (Y2S)
K4R (A1P)
Magnetic relay (E1H)
K13R~K15R,
K10R (A1P)
Magnetic relay
K11M (A1P)
Magnetic contactor
L (A1P)
Connector
M1C
Compressor motor
M1F
Fan motor
N (A1P)
Connector
PFC (A1P)
Power factor correction
PS (A1P)
Switching power supply
Q1DI
Earth leakage circuit breaker (30mA)
Q1E
Overload protection
R1T
Thermistor (air)
R2T
Thermistor (discharge)
R3T
Thermistor (suction)
R4T
Thermistor (heat exchanger)
R5T
Thermistor (heat exchanger middle)
R6T
Thermistor (liquid)
R7T
7KHUPLVWRU¿Q
R8 (A1P)
Resistor
S1PH
High pressure switch
S1PL
Low pressure switch
SEG1~3 (A1P)
7-segment display
TC1 (A1P)
Signal transceiver circuit
U, V, W (A1P)
Connector
V1D (A1P)
Diode
V*R (A1P)
Diode module
X1M
Terminal strip
Y1E, Y3E
Electronic expansion valve
Y1~2S
Solenoid valve (4-way valve)
Z*C
1RLVH¿OWHUIHUULWHFRUH
Z*F (A1P)
1RLVH¿OWHU
# : Field supply
* Optional
: Connection
: Main terminal
: Earth wiring
: Field supply
: Option
: Switch box
: PCB
: Wiring depending on model
: Protective earth
: Field wire
OUTDOOR
Layout
N = note 5
INDOOR
Position of compressor terminal
SEE NOTE 3
Upper EEV
Lower EEV
SEE
NOTE 3
SEE NOTE 3
4D109863
RZAG100-140MV1, RZASG125-140MV1, AZAS125-140MV1
NOTES
1. Refer to the wiring diagram sticker (on the back of the front plate)
for how to use the BSI~BS3 and DS1 switches.
2. When operating, do not short-circuit protection device(s) S1PH,
S1PL and Q1E.
3. Refer to the combination table and the option manual for how to
connect the wiring to X6A, X28A and X77A.
4. Colours: BLK: Black, RED: Red, BLU: Blue, WHT: White, GRN:
Green.
LEGEND
Part n°
Description
A1P
Printed circuit board (main)
A2P
3ULQWHGFLUFXLWERDUGQRLVH¿OWHU
BS1~3 (A1P)
Push-button switch
DS1 (A1P)
Dipswitch
E1~3 (A1~2P)
Connector
E1H
*
Bottom plate heater
F3U (A1P)
Fuse T 6,3 A 250 V
F5U (A2P)
Fuse T 56 A 250 V
F6U (A1P)
Fuse T 5 A 250 V
F7U (A2P)
Fuse T 6,3 A 250 V
F8U (A2P)
Fuse F 6,3 A 250 V
F9~10U
*
Fuse F 1 A 250 V
HAP (A1P)
Light-emitting diode (service monitor is green)
K1R (A1P)
Magnetic relay (Y1S)
K2R (A1P)
Magnetic relay (Y2S)
K4R (A1P)
Magnetic relay (E1H)
K13~15R, K10R
(A1P)
Magnetic relay
K11M (A1P)
Magnetic contactor
L* (A1~2P)
Connector
M1C
Compressor motor
M1~2F
Fan motor
PFC (A1P)
Power factor correction
PS (A1P)
Switching power supply
Q1DI
Earth leakage circuit breaker (30mA)
Q1E
Overload protection
R1T
Thermistor (air)
R2T
Thermistor (discharge)
R3T
Thermistor (suction)
R4T
Thermistor (heat exchanger)
R5T
Thermistor (heat exchanger middle)
R6T
Thermistor (liquid)
R7T
7KHUPLVWRU¿Q
R8 (A1P)
Resistor
S1PH
High pressure switch
S1PL
Low pressure switch
SEG1~3 (A1P)
7-segment display
TC1 (A1P)
Signal transceiver circuit
U, V, W (A1P)
Connector
V1 (A2P)
Varistor
V1D (A1P)
Diode
V*R (A1P)
Diode module
X*A (A1~2P)
Connector
X1M
Terminal strip
Y1E, Y3E
Electronic expansion valve
Y1~2S
Solenoid valve (4-way valve)
Z*C
1RLVH¿OWHUIHUULWHFRUH
Z*F (A1~2P)
1RLVH¿OWHU
# : Field supply
* Optional
: Connection
: Main terminal
: Earth wiring
: Field supply
: Wiring dependong on model
: option
: switch box
: PCB
: Several wiring possibilities
: Protective earth
: Field wire
Layout
Position of compressor terminal
Back
Front
Only for
RZASG125/140*
and AZAS125/140*
SEE
NOTE 3
SEE NOTE 3
Only for
RZAG100/125/140*
INDOOR
Only for RZAG100/125/140*
Lower fan
SEE NOTE 3
Upper EEV
Lower EEV
OUTDOOR