Installation manual
5
AZQS7 AZQS100~14 AZQS100~140A7W1B
Split System air conditioners
4PW68422-1 – 03.2011
(C) In case of multiple-row installation (for roof top use, etc.)
1.
In case of installing one unit per row.
2.
In case of installing multiple units (2 units or more) in lateral
connection per row.
Relation of dimensions of H, A and L are shown in the table below.
R
EFRIGERANT
PIPE
SIZE
AND
ALLOWABLE
PIPE
LENGTH
Selection of piping material
■
Piping and other pressure containing parts shall comply with the
national and international codes and shall be suitable for
refrigerant, use phosphoric acid deoxidised seamless copper for
refrigerant.
■
Temper grade: use piping with temper grade in function of the
pipe diameter as listed in table below.
■
The pipe thickness of the refrigerant piping should comply with
relevant local and national regulations. The minimal pipe
thickness for R410A piping must be in accordance with the table
below.
O=Annealed
1/2H=Half hard
Only use annealed material for flare connections.
Allowable pipe length and height difference
See the table below concerning lengths and heights. Refer to
figure
Allowable pipe length
L
A
L
≤
H
0<L
≤
1/2H
150 (250)
1/2H<L
200 (300)
H<L
Installation impossible
Installation shall be done by a licensed refrigeration
technician, the choice of materials and installation shall
comply with the applicable national and international
codes. In Europe, EN378 is the applicable standard that
shall be used.
To persons in charge of piping work:
■
Be sure to open the stop valve after piping installing
and vacuming is complete. (Running the system with
the valve closed may break the compressor.)
■
It is forbidden to discharge refrigerant into the
atmosphere. Collect the refrigerant in accordance
with the freon collection and destruction law.
■
Do not use flux when brazing the refrigerant piping.
For brazing, use phosphor copper brazing filler metal
(BCuP) which does not require a flux.
(If a chlorine flux is used, the piping will corrode, and if
the flux contains fluoride, it will cause the coolant oil to
deteriorate, adversely affecting the coolant piping
system.
≥
500
(1000)
≥
100
(200)
≥
1000
(2000)
≥
50
(100)
≥
1000
(1500)
≥
400 (600)
≥
2000
(3000)
A
H
L
Pipe Ø
Temper grade
of piping material
Minimal thickness t (mm)
6.4 / 9.5 / 12.7
O
0.80
15.9
O
1.00
19.1
1/2H
Allowable pipe length
Model
71
100
125
140
Maximum total one-way piping length
(a)
(a) Parenthesized figure represents the equivalent length.
L1
50 m (70 m)
75 m (95 m)
Maximum height between indoor and outdoor
H1
30 m
Chargeless length
L1
≤
30 m