SiEN04-306D
Control Specification
Function and Control
69
3.14 Forced Operation Mode
Outline
Forced operating mode includes only forced cooling.
Detail
Forced Cooling
3.15 Additional Function
3.15.1 POWERFUL Operation Mode
Compressor operating frequency is increased to PI Max. (Max. Hz of operating room) and
outdoor unit airflow rate is increased.
3.15.2 Voltage Detection Function
Power supply voltage is detected each time equipment operation starts.
Item
Forced Cooling
Forced operation
allowing conditions
1) The outdoor unit is not abnormal
and not in the 3-minute stand-by
mode.
2) The operating mode of the outdoor
unit is the stop mode.
3) The forced operation is ON.
The forced operation is allowed when
the above “and” conditions are met.
Starting/adjustment
If the forced operation switch is
pressed as the above conditions are
met.
1) Command
frequency
66 Hz
2) Electronic
expansion valve
opening
Depending on the capacity of the
indoor unit.
3) Outdoor unit
adjustment
Compressor is in operation
4) Indoor unit
adjustment
Transmit the command of forced
draft to the indoor unit.
End
1) When the forced operation switch is
pressed again.
2) The operation is to end
automatically after 15 min.
Others
The protect functions are prior to all
others in the forced operation.
Summary of Contents for SiEN04-306D
Page 109: ...Instruction SiEN04 306D 100 System Configuration...
Page 199: ...Outdoor Unit SiEN04 306D 190 Removal Procedure...
Page 203: ...Others SiEN04 306D 194 Others...
Page 214: ...SiEN04 306D Wiring Diagrams Appendix 205 FTKD18 24 28BVMS...
Page 216: ...SiEN04 306D Wiring Diagrams Appendix 207 RKD18 24 28BVMS...